BRUGERMANUAL BACnet Protocol EXHAUSTO AIR 2

Størrelse: px
Starte visningen fra side:

Download "BRUGERMANUAL BACnet Protocol EXHAUSTO AIR 2"

Transkript

1 BACnet Protocol, EXHAUSTO AIR 2 BRUGERMANUAL BACnet Protocol EXHAUSTO AIR 2 EXHAUSTO A/S Tel Odensevej 76 Fax DK-5550 Langeskov exhausto@exhausto.dk

2 EXHAUSTO AIR 2, Program version 2.00 og efterfølgende versioner. Oversigt Luftbehandlingsaggregat (AHU), der er udstyret med en EXHAUSTO Air 2 Master styreenhed. BACnet funktionaliteten er implementeret i EXHAUSTO Air 2 Masters med software version 2.00 eller nyere. EXHAUSTO Air 2 Master er en BACnet Application Specific Controller (B-ASC) med understøttede data link layer valgmuligheder: BACnet IP. Der henvises desuden til dokumentet "OJ-Air2 EDE" (Engineering Data Exchange). Kommunikation TCP/IP: 1 stk. 10/100 Mbit Ethernet, RJ45 kontakt BACnet Interoperability Building Blocks understøttes Datadeling DS-RP-B Datadeling Læsning af egenskab B Datadeling DS-WP-B Datadeling Skrivning af egenskab B Device Management DM-DDB-B Device Management Dynamic Device Binding B Device Management DM-DOB-B Device Management Dynamic Object Binding B Device Management DM-DCC-B Device Management Dynamic Communication Control B BACnet IP standard objekttyper understøttes Standard objekttyper Binær værdi DO (R/W) Binær indgang DI (RO) Analog indgang AI (RO) Analog værdi AO (R/W) Enhed Egenskaber Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_Service, Priority_Array, Relinquish_Default. Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_Service, Priority_Array, Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_Service, enheder, Min_Pres_Value, Max_Pres_Value, opløsning, pålidelighed, COV_Increment Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_Service, enheder, Priority_Array, Relinquish_Default, COV_Increment. Object_Identifier, Object_Name, Object_Type, Present_Value, Vendor_Name, Vendor_Identifier, Model_Name, Firmware_Revision, Aplication_Software_Version, Location, Description, Protocol_Version, Protocol_Revision, Protocol_Services_Supported, Protocol_Object_Types_Supported, Object_list, Max_APDU_Length_Accepted, Segmentation_Supported, APDU_Timeout, Number_Of_APDU_Retries, Device_Address_Binding, Database_Revision. RO = Read Only R/W = Read / Write Kommentarer: Object_Identifier indstilles automatisk for den sidste halvdel af IP-adressen i EXHAUSTO-Air2 Master styreenheden. Maksimalt 300 værdier kan indlæses i COV'en (Change Of Value) samtidig Binary Value SIDE 6 Binary Input SIDE 7 Analog Input SIDE 11 Analog Value SIDE 16 2/32

3 BACnet / IP forbindelse BACnet IP 3/32

4 AI = Analog Input AV = Analog Value BI = Binary Input BV = Binary Value OI = Object Instance Varmevekselniveau AI; OI, 68 Aktuel udsugningflow AI; OI, 7 Udsugning motorsignal setpunkt AI; OI, 60 Udsugning setpunkt lav AV; OI, 12 Udsugning setpunkt høj hast ighed AV; OI, 13 Aktuel driftform AI; OI, 0 Manuel driftfunktion AV; OI, 0 Indstilling av temp. reg. form AV; OI, 133 Drift ON/OFF BI; OI, 0 Forlænget lav aktiv BI; OI, 3 Forlænget høj aktiv BI; OI, 4 A-alarm aktiv BI; OI, 30 B-alarm aktiv BI; OI, 31 Alarm reset BV; OI, 0 Rumtemperatur AI; OI, 21 Temp setpunkt aktuel reg.form AV;OI, 134 Udsugning filtertryk AI; OI, 28 Alarm grænse afkast filter AI; OI, 32 Aktuel afkasttemperatur AI; OI, 22 Aktuel udsugningtemperatur AI; OI, 18 Temp setpunkt aktuel reg.form AV; OI, 134 Aktuel kanaltryk udsugning AI; OI, 3 Setp. kanaltryk lav hast. udsug. AV; OI, 6 Setp. kanaltryk høj hast. udsug. AV; OI, 7 Aktuel udetemperatur AI; OI, 20 Aktuel indblæsningtemperatur AI; OI, 16 Temp setpunkt aktuel reg.form AV; OI, 134 Min begrænsning indbl. temp. AV; OI, 135 Max. begrænsning indbl. temp. AV; OI, 136 Aktuel kanaltryk indblæsning AI; OI, 1 Setp. kanaltryk lav hast. indbl. AV; OI, 2 Setp. kanaltryk høj hast. Indbl. AV; OI, 3 Indblæsning filtertryk AI; OI, 27 Alarm grænse indtags filter AI; OI, 31 Varmeniveau AI; OI, 36 Varme relæ 1 BI; OI, 26 Køleniveau AI; OI, 38 Køle relæ 1 BI; OI, 27 El-Batteri høj temperatur BI; OI, 34 Frostfri temperatur AI; OI, 26 Aktuel indblæsningflow AI; OI, 5 Indblæsningmotorsignal setpunkt AI; OI, 51 Indblæsning setpunkt lav AV; OI, 10 Indblæsning setpunkt høj hast ighed AV; OI, 11 4/32

5 Binary Value DO (R/W) NAVN ENHED ADRESSE MIN MAX BEMÆRKNINGER Alr_Reset Alarm reset-signal (Autoreturn til nul) CoolRecovFunc Kølegenvinding ON/OFF SN_Func Sommernat køling; ON/OFF SWTC_Func Sommer/Vinter temp. kompensering; ON/OFF FlwTmpCmpFunc Flow-/Udetemperatur kompensering; ON/OFF RecircFunc Recirkulation funktion; ON/OFF CoolFlwForceFc Forceret flow ved kølebehov; ON/OFF TimeSw-SumFunc Automatisk sommer-/vinter tid; ON/OFF ExtDrfHiPeriod Indgang for forceret høj ExtDrfPeriodON Efterløb på forceret høj aktiv ManZeroCali Start manual 0 -kalibrering (kan bruges samtidig med automatisk 0 -kalibrering) Tilbagestilles automatisk til 0 (OFF), når kalibreringen er afsluttet AutoZeroCali Automatisk 0 -kalibrering funktion ON/OFF FiltDynAlrFunc Filter dynamisk alarm funktion -> ON/OFF OFF -> Statisk alarm grænse (Konstant) ON -> Dynamisk alarm grænse (grænse på basis af flow) FiltCalibrate Start Filter kalibrering. Tilbagestilles automatisk til 0 (OFF), når kalibreringen er afsluttet. OBS! KUN NÅR INDSTILLET TIL DYNAMIC-MODE FiltCaliDone Filter Kalibrering udført (valide filter data) OBS! KUN NÅR INDSTILLET TIL DYNAMIC-MODE 5/32

6 Binary Input DI (RO) NAVN ENHED ADRESSE MIN MAX BEMÆRKNINGER Operation Drift ON/OFF ExtStop Ekstern stop ExtHiSpeed Ekstern høj ExtDrfLoSpeed Forlænget lav -> aktiv ExtDrfHiSpeed Forlænget høj -> aktiv ElBattPowerRed Energi til el-varmebatteri reduceret p.g.a. lavt flow SN_Drift Sommernat køling er aktiv SN_Reset Reset parametre for sommer natkøling (ny beregning startes) SWTC_WintComp Vinter -temperatur kompensering er aktiv SWTC_SumComp Sommer -temperatur kompensering er aktiv SW_Status Sommer/Vinter aktuel status (SW_Mode = 1..3) OFF > Vinter Drift ("0") ON Sommer Drift ("1") RecircStatus Recirkulation status EXC_Exercise Motion af varmeveksler -> aktiv ExhaustPowRed Signal til krydsveksler reduceret (frost beskyttelse) SupDuctMinFlow Indblæsning kanal tryk-regulator regulereret til min. flow SupDuctMaxFlow Indblæsning kanal tryk-regulator regulereret til max. flow ExtDuctMinFlow Udsugning kanal tryk-regulator regulereret til min. flow ExtDuctMaxFlow Udsugning kanal tryk-regulator regulereret til max. flow CoolRecovery Kølegenvinding -> Status HW_FrosrReg Cirkulationspumpe på varmebatteri; Frost regulering -> aktiv HW_PumpExer Cirkulationspumpe på varmebatteri; Pumpemotion -> aktiv CW_PumpExer Cirkulationspumpe på kølebatteri; Pumpemotion -> aktiv Heat_FlwDnReg Signal til varmebatteri reduceret (for lavt flow) -> aktiv 6/32

7 NAVN ENHED ADRESSE MIN MAX BEMÆRKNINGER TempRegMinSup når min. indblæsningstemperatur regulering er aktiv. Kun aktivt når TempRegMode er 1 eller 2 (Rum-regulering) TempRegMaxSup når max. indblæsningstemperatur Regulering er aktiv. Kun aktivt når TempRegMode er 1 eller 2 (Rum-regulering) BattEXC_Exer Cirkulationspumpe på varme genvingsbatteri; Pumpemotion -> aktiv Heat_RE Varme relæ 1 Cool_RE Køle relæ 1 BattEXC_PumpRE Cirkulationspumpe på varme genvingsbatteri; Pumpe -> kører AlrActive Mindst én aktiv alarm Alr_RE Alarmrelæ-1 (A-alarm) Alr_RE Alarmrelæ-2 (B-alarm) Alr_FireSignal Brand alarm-signal (Rumføler) Alr_SmokeSig Røg / Brand alarm-signal (Føler i kanal) ElBattOverHeat EL-Batteri; Høj temperatur alarm signal FiltSupalarm Filter alarm for indblæsnings-filter (Trykfald over indstillet Grænse) FiltExtalarm Filter alarm for udsugnings-filter (Trykfald over indstillet grænse) SupTempSensErr Indblæsnings temparatur føler følerfejl ExtTempSensErr Udsugnings temparatur føler følerfejl OutDoorSensErr Ude temparatur føler følerfejl RoomSensErr Rum temparatur føler følerfejl ExhaustSensErr Afkast temparatur føler følerfejl HW_SensErr Varmebatteri temparatur føler følerfejl BattEXC_SensEr Varmegenvindings batteri temperatur føler følerfejl HW_FrostAlr Varmebatteri frost alarm Cool_Sumalarm Køling fælles alarm Cool_DI1_alarm Køling digital alarm-1 Indgang Cool_DI2_alarm Køling digital alarm-2 Indgang 7/32

8 NAVN ENHED ADRESSE MIN MAX BEMÆRKNINGER Cool_DI3_alarm Køling digital alarm-3 Indgang Cool_DI4_alarm Køling digital alarm-4 Indgang SupmotorON Indblæsningsmotor ON/OFF Supmotoralarm Alarm fra indblæsningsmotor ON/OFF FCsupMtrAlrVlo Indblæsningsmotor spænding lav alarm (kun ved OJ-FC) FCsupMtrAlrVHi Indblæsningsmotor høj spændingsgrænse alarm (kun ved OJ-FC) FCsupMtrAlrIHi Indblæsningsmotor høj strøm alarm (kun ved OJ-FC), motorbeskyttelse FCsupMtrAlrTmp Indblæsningsmotor temperatur alarm (kun ved OJ-FC) FCsupMtrAlrPhs Indblæsningsmotor fasefejl alarm (kun ved OJ-FC) FCsupMtrAlrRip Indblæsningsmotor ripple-spænding alarm (kun ved OJ-FC) FCsupMtrIHiLim Indblæsningsmotor høj strøm grænse; kortslutningsbeskyttelse (kun ved OJ-FC) ExtmotorON Udsugningsmotor ON/OFF (kun ved OJ-FC) Extmotoralarm alarm Udsugningsmotor ON/OFF (kun ved OJ-FC) FCextMtrAlrVlo Udsugningsmotor alarm for lav spænding (kun ved OJ-FC) FCextMtrAlrVHi Udsugningsmotor høj spændingsgrænse alarm (kun ved OJ-FC) FCextMtrAlrIHi Udsugningsmotor høj strømgrænse alarm (kun ved OJ-FC) FCextMtrAlrTmp Udsugningsmotor temperatur alarm (kun ved OJ-FC) FCextMtrAlrPhs Udsugningsmotor alarm for fasefejl (kun ved OJ-FC) 8/32

9 NAVN ENHED ADRESSE MIN MAX BEMÆRKNINGER FCextMtrAlrRip Udsugningsmotor høj strømgrænse (kun ved OJ-FC) FCextMtrIHiLim Roterende varmeveksler - motorregulering ON/OFF (kun ved OJ-RHX2M) EXC_ON Roterende varmeveksler - reset signal (kun ved OJ-RHX2M) EXC_Reset Roterende varmeveksler - omdrejningsretning (kun ved OJ-RHX2M) EXC_Direction Roterende varmeveksler - rotation alarm (kun ved OJ-RHX2M) EXC_Rotalarm Roterende varmeveksleralarm for underspænding (kun ved OJ-RHX2M) EXC_Vloalarm Roterende varmeveksleralarm for overspænding (kun ved OJ-RHX2M) EXC_VHialarm Roterende varmeveksleralarm for høj strøm (kun ved OJ-RHX2M) EXC_IHialarm Roterende varmeveksler - temperatur alarm (kun ved OJ-RHX2M) EXC_Tempalarm Roterende varmeveksler - rotation signal (kun ved OJ-RHX2M) EXC_RotSignal Roterende varmeveksler - moment overbelastning (kun ved OJ-RHX2M) EXC_Overload Udsugningsmotor høj strømgrænse (kun ved OJ-FC) 9/32

10 Analog Input AI (RO) NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER DriftMode Aktuel Driftform :Anlæg Stop :Anlæg Lav :Anlæg Høj :Anlæg Spec RegMode SupDuctPa Pa Aktuel kanaltryk indblæsning [Pa] SupDuctPaRgSet Pa Regulator setpunkt for kanal tryk regulator [Pa] ExtDuctPa Pa Aktuel kanaltryk udsugning [Pa] ExtDuctPaRgSet Pa Regulator setpunkt for kanaltryk regulering [Pa] SupFlow l/s Aktuel flow indblæsning [l/s] SupFlowRegSet l/s Regulator indblæsning flow-setpunkt [l/s] ExtFlow l/s Aktuel udsugning flow [l/s] ExtFlowRegSet l/s Regulator udsugning flow-setpunkt [l/s] CO2_ppmMeas ppm CO2 føler ppm Måling [ppm] MtrFanSupVin % VDC signal til indblæsning motor MtrFanExtVin % VDC signal til udsugning motor FAN_SupPrcMeas % Spænding på FAN-Optimizer indgang; Indblæsning sgnal [1/100%] FAN_ExtPrcMeas % Spænding på FAN-Optimizer indgang; Udsugning signal [1/100%] SupFC_MaxFlow l/s Indblæsning FC-Max Flow [l/s] / [m3/h] ExtFC_MaxFlow l/s Udsugning FC-Max Flow [l/s] / [m3/h] SupTemp C Aktuel indblæsningstemperatur [1/100 C] SupTempRegSet C Regulator indblæsningtemperatur-setpunkt [1/100 C] ExtTemp C Aktuel udsugningstemperatur [1/100 C] ExtTempRegSet C Regulator udsugningtemp-setpunkt [1/100 C] OutDoorTemp C Aktuel udetemperatur [1/100 C] RoomTemp C Aktuel rumtemperatur [1/100 C] ExhaustTemp C Aktuel afkast [1/100 C] 10/32

11 NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER TempRegMeas C Temp. måling for aktuel reguleringsvalg [1/100 C] TempRegVal C Reguleringsværdi for aktuel reguleringsvalg [1/100 C] BattEXC_Temp C Vandbatteri temperatur efter varmeveksler [1/100 C] HW_BattTemp C Aktuel varmebatteri temperatur [1/100 C] SupFiltPaAvr Pa Indblæsning filtertryk [Pa] ExtFiltPaAvr Pa Udsugning filtertryk [Pa] SupMotorSet % Indblæsning motorsignal setpunkt [%] ExtMotorSet % Udsugning motorsignal setpunkt [%] FiltSupAlrPa Pa Indblæsning filterovervågning max. alarm-grænse[pa] KUN DYNAMICMODE ("0" er STATICMODE) FiltExtAlrPa Pa Udsug. filterovervågning max. alarm-grænse [Pa] KUN DYNAMICMODE ("0" er STATICMODE) FlwTmpCmpOut % Temp. korrigeret flow setpunkt procent [1/100%] SWTC_ActSetOfs C Sommer/Vinter-Temp. kompensering på aktuel Setpunkt offset [1/100 C] HeatEXCPower % Varmeveksler-regulator varme-effekt [1/100 %] HeatPower % Aktuel varme-effekt [1/100 %] CoolPower % Køling regulator effekt [1/100 %] CoolActPower % Aktuel køling-effekt [1/100%] CoolFlwForcePw % Køle forcering flow effekt [1/100 %] CoolVin1Alarm % Køle Alarm-1 transducersignal [1/100 %] CoolVin2Alarm % Køle Alarm-2 transducersignal [1/100 %] CoolVin3Alarm % Køle Alarm-3 transducersignal [1/100 %] CoolVin4Alarm % Køle Alarm-4 transducersignal [1/100 %] C_LoPress1Bar Bar Aktuel LavtrykFøler-1 Bar [1/100 Bar] C_HiPress1Bar Bar Aktuel HøjtrykFøler-1 Bar [1/100 Bar] C_LoPress2Bar Bar Aktuel LavtrykFøler-2 Bar [1/100 Bar] C_HiPress2Bar Bar Aktuel HøjtrykFøler-2 Bar [1/100 Bar] FCsupMtrType Indblæsningmotor type (kun OJ-FC) FCsupMtrFC_SW Indblæsningmotor software vers. [1/100] (kun OJ-FC) 11/32

12 NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER FCsupMtrIO_SW Indblæsningmotor IO-kort software vers. [1/100] (kun OJ-FC) FCsupMtrPrcOut % Indblæsningmotor procent udgang [1/100%] (kun OJ-FC) FCsupMtrHzOut Hz Indblæsningmotor frekvens udgang [1/100 Hz] (kun OJ-FC) FCsupMtrIout ma Indblæsningmotor aktuel strømudgang [ma] (kun OJ-FC) FCsupMtrPowOut W Indblæsningmotor aktuel effekt udgang [Watt] (kun OJ-FC) FCsupMtrPrcSet % Indblæsningmotor setpunkt [%] SupSFP J/m Indblæsning specific fan power (SFP) [Ws/m 3 = J/m 3 ] (kun OJ-FC) FCextMtrType Udsugningmotor type (kun OJ-FC) FCextMtrFC_SW Udsugningmotor software vers. [1/100] (kun OJ-FC) FCextMtrIO_SW Udsugningmotor IO-kort software vers. [1/100] (kun OJ-FC) FCextMtrPrcOut % Udsugningmotor procent udgang [1/100%] (kun OJ-FC) FCextMtrHzOut Hz Udsugningmotor frekvens udgang [1/100 Hz] (kun OJ-FC) FCextMtrIout ma Udsugningmotor udgang aktuel strøm [ma] (kun OJ-FC) FCextMtrPowOut W Udsugningmotor aktuel effekt udgang [Watt] (kun OJ-FC) FCextMtrPrcSet % Udsugningmotor udgang setpunkt [%] ExtSFP J/m Udsugning specific fan power (SFP) [Ws/m 3 = J/m 3 ] (kun OJ-FC) EXC_Type Roterende varmeveksler - motortype (kun OJ RHX2M) EXC_Software Roterende varmeveksler - software vers. [1/100] (kun OJ RHX2M) EXC_PrcOut % Roterende varmeveksler-procent [1/100%] 12/32

13 NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER EXC_RpmOut U/min Roterende varmeveksler-omdr./min. udgang [1/100rpm] EXC_Iout ma Roterende varmeveksler-aktuel udgang [ma] (kun OJ RHX2M) EXC_Power W Roterende varmeveksler-udgang effekt [W] (kun OJ RHX2M) EXC_DriftDays Day Roterende varmeveksler - antal driftdage (kun OJ RHX2M) EXC_PrcSet % Roterende varmeveksler procent setpunkt [1/100%] (kun OJ RHX2M) EXTM1_SW_Ver ExtensionModul-1 software ver. [1/100] EXTM2_SW_Ver ExtensionModul-2 software vers. [1/100] TimeSw-WeekDay Aktuel ugedag (0-Man..6-Søn) ExtDrfDaysLeft Forlænget drift resterende antal dage ExtDrfMinLeft Min Forlænget drift resterende antal minutter Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) 13/32

14 NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER Alr_Released Stack for aktive alarmer (0 indikerer slutningen af stack) MasterSW_Ver Master software vers. [1/100] DisplaySW_Ver Display software vers. [1/100] 14/32

15 Analog Value AO (R/W) NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER ManDriftMode Auto, 1-Manuel Stop, 2-Manuel Lav, 3-Manuel Høj MtrRegMode Tryk, 1-Flow, 2-Udsugning Slave, 3-Indblæsning Slave 4-Extern VDC Setpunkt, 5 FAN-Optimizer Indbl./Udsug., 6 FAN-Optimizer med Udsugning Slave SupDuctPaLoSet Pa Setpunkt for kanaltryk lav indblæsning [Pa] SupDuctPaHiSet Pa Setpunkt for kanaltryk høj indblæsning [Pa] SupDuctMinFlow l/s Indblæsning min. flow for kanal regulering [l/s] / [m3/h] SupDuctMaxFlow l/s Indblæsning max. flow for kanal regulering [l/s] / [m3/h] ExtDuctPaLoSet Pa Setpunkt for lav kanaltryk udsugning [Pa] ExtDuctPaHiSet Pa Setpunkt for høj kanaltryk udsugning [Pa] ExtDuctMinFlow l/s Udsugning min. flow for kanalregulering [l/s] / [m3/h] ExtDuctMaxFlow l/s Udsugning max. flow for kanalregulering [l/s] / [m3/h] SupLoSpeedSet l/s Setpunkt indblæsning flow-lav [l/s] / [m3/h] SupHiSpeedSet l/s Setpunkt indblæsning flow-høj [l/s] / [m3/h] ExtLoSpeedSet l/s Setpunkt udsugning flow-lav [l/s] / [m3/h] ExtHiSpeedSet l/s Setpunkt udsugning flow-høj [l/s] / [m3/h] MtrRegOffset % Offset for indblæsning/udsugning motor slave og CO2 reg [1/100%] MtrRegMinFlow l/s Min. flow for indblæsning/udsugning motor slave regulering [l/s] / [m3/h] MtrRegMaxFlow l/s Max. flow for indblæsning/udsugning motor slave regulering [l/s] / [m3/h] CO2_BrugerSetLP ppm CO2 regulator setpunkt for lav periode (HI CO2 Val) [ppm] CO2_BrugerSetHP ppm CO2 regulator setpunkt for høj periode (HI CO2 Val) [ppm] 15/32

16 NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER CO2_MinFlow l/s CO2 regulator min. flow [l/s] / [m3/h] CO2_MaxFlow l/s CO2 regulator max. flow [l/s] / [m3/h] CO2_SupFlwOffs % CO2 regulator indblæsning flow offset [1/100%] CO2_AlrLimit ppm CO2 ppm alarm grænse setpunkt [ppm] CO2_PB ppm CO2 Regulator P-Bånd [ppm] CO2_I_Time sec CO2 Regulator I-Tid [sec] FAN_SupMinFlow l/s FAN-Optimizer indblæsning regulator min.flow [l/s] / [m3/h] FAN_SupMaxFlow l/s FAN-Optimizer indblæsning regulator max. flow [l/s] / [m3/h] FAN_ExtMinFlow l/s FAN-Optimizer udsugning regulator min. flow [l/s] / [m3/h] FAN_ExtMaxFlow l/s FAN-Optimizer udsugning regulator max. flow [l/s] / [m3/h] FAN_ExtFlwOffs % FAN-Optimizer regulator udsugning flow offset [1/100%] SupMtr_I_Time s Indblæsning motor reg I-tid setpunkt [Sec] ExtMtr_I_Time s Udsugning motor reg I-tid setpunkt [Sec] SupFlowFireSet % Setpunkt indblæsning motor ved brandalarm [1/100%] ExtFlowFireSet % Setpunkt udsugning motor ved brandalarm [1/100%] HS_AfterRunSet Efterløbstid høj [Min] FlwTmpCmpSet % Reduktion af flow / procent af setpunkt [1/100%] FlwTmpCmpStart C Reduktion af flow / start temp. setpunkt [1/100 C] FlwTmpCmpStop C Reduktion af flow / stop temp. setpunkt [1/100 C] TimeSw-Year Aktuel År TimeSw-Month Aktuel Måned TimeSw-Date Aktuel Dag TimeSw-Hour h Aktuel Time 16/32

17 NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER TimeSw-Minute min Aktuel Minutter TimeSw-Second s Aktuel Sekunder ExtDrfStartDay Forlænget drift start - dag (0-Man..6-Søn) ExtDrfStartMin Min Forlænget drift start - minut (Timer*60+Min) ExtDrfStopDay Forlænget drift stop - dag (0-Man..6-Søn) ExtDrfStopMin Min Forlænget drift stop - minut (Timer*60+Min) TimeSw-DayMode Tidsprogram type (0..2) 0-Man..Søn, 1-Man..Fre+Weekend, 2-Uge TimeSw-Start00 Min Mandag start 1. tidsperiode [Minutter fra midnat] TimeSw-Start01 Min Tirsdag start 1. tidsperiode [Minutter fra midnat] TimeSw-Start02 Min Onsdag start 1. tidsperiode [Minutter fra midnat] TimeSw-Start03 Min Torsdag start 1. tidsperiode [Minutter fra midnat] TimeSw-Start04 Min Fredag start 1. tidsperiode [Minutter fra midnat] TimeSw-Start05 Min Lørdag start 1. tidsperiode [Minutter fra midnat] TimeSw-Start06 Min Søndag start 1. tidsperiode [Minutter fra midnat] TimeSw-Start07 Min Mandag start 2. tidsperiode [Minutter fra midnat] TimeSw-Start08 Min Tirsdag start 2. tidsperiode [Minutter fra midnat] TimeSw-Start09 Min Onsdag start 2. tidsperiode [Minutter fra midnat] TimeSw-Start10 Min Torsdag start 2. tidsperiode [Minutter fra midnat] TimeSw-Start11 Min Fredag start 2. tidsperiode [Minutter fra midnat] TimeSw-Start12 Min Lørdag start 2. tidsperiode [Minutter fra midnat] TimeSw-Start13 Min Søndag start 2. tidsperiode [Minutter fra midnat] TimeSw-Start14 Min Mandag start 3. tidsperiode [Minutter fra midnat] 17/32

18 NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER TimeSw-Start15 Min Tirsdag start 3. tidsperiode [Minutter fra midnat] TimeSw-Start16 Min Onsdag start 3. tidsperiode [Minutter fra midnat] TimeSw-Start17 Min Torsdag start 3. tidsperiode [Minutter fra midnat] TimeSw-Start18 Min Fredag start 3. tidsperiode [Minutter fra midnat] TimeSw-Start19 Min Lørdag start 3. tidsperiode [Minutter fra midnat] TimeSw-Start20 Min Søndag start 3. tidsperiode [Minutter fra midnat] TimeSw-Start21 Min Mandag start 4. tidsperiode [Minutter fra midnat] TimeSw-Start22 Min Tirsdag start 4. tidsperiode [Minutter fra midnat] TimeSw-Start23 Min Onsdag start 4. tidsperiode [Minutter fra midnat] TimeSw-Start24 Min Torsdag start 4. tidsperiode [Minutter fra midnat] TimeSw-Start25 Min Fredag start 4. tidsperiode [Minutter fra midnat] TimeSw-Start26 Min Lørdag start 4. tidsperiode [Minutter fra midnat] TimeSw-Start27 Min Søndag start 4. tidsperiode [Minutter fra midnat] TimeSw-Stop00 Min Mandag stop 1. tidsperiode [Minutter fra midnat] TimeSw-Stop01 Min Tirsdag stop 1. tidsperiode [Minutter fra midnat] TimeSw-Stop02 Min Onsdag stop 1. tidsperiode [Minutter fra midnat] TimeSw-Stop03 Min Torsdag stop 1. tidsperiode [Minutter fra midnat] TimeSw-Stop04 Min Fredag stop 1. tidsperiode [Minutter fra midnat] TimeSw-Stop05 Min Lørdag stop 1. tidsperiode [Minutter fra midnat] TimeSw-Stop06 Min Søndag stop 1. tidsperiode [Minutter fra midnat] TimeSw-Stop07 Min Mandag stop 2. tidsperiode [Minutter fra midnat] TimeSw-Stop08 Min Tirsdag stop 2. tidsperiode [Minutter fra midnat] TimeSw-Stop09 Min Onsdag stop 2. tidsperiode [Minutter fra midnat] TimeSw-Stop10 Min Torsdag stop 2. tidsperiode [Minutter fra midnat] 18/32

19 NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER TimeSw-Stop11 Min Fredag stop 2. tidsperiode [Minutter fra midnat] TimeSw-Stop12 Min Lørdag stop 2. tidsperiode [Minutter fra midnat] TimeSw-Stop13 Min Søndag stop 2. tidsperiode [Minutter fra midnat] TimeSw-Stop14 Min Mandag stop 3. tidsperiode [Minutter fra midnat] TimeSw-Stop15 Min Tirsdag stop 3. tidsperiode [Minutter fra midnat] TimeSw-Stop16 Min Onsdag stop 3. tidsperiode [Minutter fra midnat] TimeSw-Stop17 Min Torsdag stop 3. tidsperiode [Minutter fra midnat] TimeSw-Stop18 Min Fredag stop 3. tidsperiode [Minutter fra midnat] TimeSw-Stop19 Min Lørdag stop 3. tidsperiode [Minutter fra midnat] TimeSw-Stop20 Min Søndag stop 3. tidsperiode [Minutter fra midnat] TimeSw-Stop21 Min Mandag stop 4. tidsperiode [Minutter fra midnat] TimeSw-Stop22 Min Tirsdag stop 4. tidsperiode [Minutter fra midnat] TimeSw-Stop23 Min Onsdag stop 4. tidsperiode [Minutter fra midnat] TimeSw-Stop24 Min Torsdag stop 4. tidsperiode [Minutter fra midnat] TimeSw-Stop25 Min Fredag stop 4. tidsperiode [Minutter fra midnat] TimeSw-Stop26 Min Lørdag stop 4. tidsperiode [Minutter fra midnat] TimeSw-Stop27 Min Søndag stop 4. tidsperiode [Minutter fra midnat] TimeSw-Mode Mandag 1.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2- Høj TimeSw-Mode Tirsdag 1.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Onsdag 1.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Torsdag 1.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2- Høj 19/32

20 NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER TimeSw-Mode Fredag 1.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Lørdag 1.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Søndag 1.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Mandag 2.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2- Høj TimeSw-Mode Tirsdag 2.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Onsdag 2.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Torsdag 2.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2- Høj TimeSw-Mode Fredag 2.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Lørdag 2.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Søndag 2.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Mandag 3.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2- Høj TimeSw-Mode Tirsdag 3.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Onsdag 3.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Torsdag 3.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2- Høj TimeSw-Mode Fredag 3.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj 20/32

21 NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER TimeSw-Mode Lørdag 3.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Søndag 3.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Mandag 4.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2- Høj TimeSw-Mode Tirsdag 4.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Onsdag 4.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Torsdag 4.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2- Høj TimeSw-Mode Fredag 4.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Lørdag 4.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TimeSw-Mode Søndag 4.tidsperiode. drift tilstand. 0-OFF, 1-Lav, 2-Høj TempRegMode Indblæsning, 1-Udsugning, 2-Rum, 3-Indbl./Udsug. diff TempRegSet C Temperatur setpunkt for aktuel reguleringsform [1/100 C] SupTempMinSet C Min. begrænsning indblæsnings temperatur [1/100 C] SupTempMaxSet C Max. begrænsning indblæsnings temperatur [1/100 C] SupTempDiffSet C Setpunkt: Temperatur differens mellem indbl./udsug. KUN AKTUEL for TempRegMode = 3-Indbl./Udsug. diff (Konst Indbl./Udsug. -diff.tempreg) [1/100 C] SupTempDiffAlr C Alarm grænse for temp. diff. mellem indblæsning setpunkt og aktuel værdi [1/100 C] 21/32

22 NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER SupTempPB C P-Bånd for indblæsning temp. regulering [1/100 C] SupTempCool_It s I-Tid for reg. køling indblæsning[sec] SupTempEXC_It s I-Tid for reg. veksler indblæsning [sec] SupTempHeat_It s I-Tid for reg. varme indblæsning [sec] SupTempDnRegIt s I-Tid for flow nedregulering af indblæsning ved lav indblæsningstemp. [sec] ExtTempDiffAlr C Alarm grænse for temp. diff. mellem setpunkt og aktuel værdi på udsugningstemperatur [1/100 C] ExtTempPB C P-Bånd for udsugning temp. regulering [1/100 C] ExtTempCool_It s I-Tid for reg. køling udsugning [sec] ExtTempEXC_It s I-Tid for reg. veksler udsugning [sec] ExtTempHeat_It s I-Tid for reg. varme udsugning [sec] ExtTempDnRegIt s I-Tid for flow nedregulering af udsugning ved lav indblæsningstemp.[sec] SWTC_WintX1 C Sommer/Vinter-temp.komp. vinter lav ude temp.setpunkt [1/100 C] SWTC_WintX2 C Sommer/Vinter-temp.komp. vinter høj ude temp.setpunkt [1/100 C] SWTC_SumX1 C Sommer/Vinter-temp.komp. sommer lav ude tempset [1/100 C] SWTC_SumX2 C Sommer/Vinter-temp.komp. sommer høj Uude tempset [1/100 C] SWTC_WintComp C Sommer/Vinter-temp.komp. vinter kompensation [1/100 C] SWTC_SumComp C Sommer/Vinter-temp.komp sommer kompensation [1/100 C] 22/32

23 NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER SW_Mode Valg af sommer/vinter skift 0 - OFF (Ingen sommer/vinter-skift) 1 - Skift i henhold til udetemperatur 2 - Sommer/Vinter-skift i henhold til dato 3 - Manuel sommer 4 - Manuel vinter SW_OutWinterON C Ude Temp. for start vinter drift (SW_Mode = 1) [1/100 C] SW_OutSummerON C Ude Temp. for start sommer drift (SW_Mode = 1) [1/100 C] SW_MonthWintON Måned for start vinter drift (SW_Mode = 2) SW_DateWintON Dato for start vinter drift (SW_Mode = 2) SW_MonthSumON Måned for start sommer drift (SW_Mode = 2) SW_DateSumON Dato for start sommer drift (SW_Mode = 2) RecicStartTmp C Start Temp. for recirk. funktion [1/100 C] RecicStopTmp C Stop Temp. for recirk. funktion [1/100 C] SupTempFireAlr C Setpunkt for intern brand alarm i indbl. [1/100 C] ExtTempFireAlr C Setpunkt for intern brand alarm i udsug. [1/100 C] CoolFlwForcePc % Forøgelse af når køling er aktiv [1/100%] CoolOutTmpMin C Min. udetemperatur for start af køleanlæg [1/100 C] CoolSupMinTmp C Min. indbl. temp. når køling er aktiv (KUN for Rumregulering) [1/100 C] SN_ExtTmpStart C Sommer nat udsug./rum temp. start [1/100 C] SN_ExtTmpStop C Sommer nat udsug./rum temp. stop [1/100 C] SN_OutTmpStart C Sommer nat ude temp. start [1/100 C] SN_SupTmpSet C Sommer nat indbl. Ttmp. reg. set [1/100 C] SN_StartTid Min Sommer nat start [Min] SN_StopTid Min Sommer nat stop [Min] ExhaustBypass C Min. afkast temp. setpunkt på krydsvarmeveksler [1/100 C] 23/32

24 NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER ExhaustBypasPB C P-Bånd for by-pass regulator på krydsvarmeveksler [1/100 C] BattEXC_PumpFc Funktion af cirk. pumpe på varmevekslerbatteri: 0 -> Pumpe kører konstant 1 -> Pumpe kører når genvindingsbehov > 0 (AutoMode) 2 -> Pumpe kører når udetemp. < pumpe start temp. setpunkt BattEXC_PumpSt C Start setpunkt for cirk.pumpe på væskekobletbatteri Bruges KUN sammen med BattEXC_PumpFunc (Address 224) = 2. Pumpe kører når udetemperatur < temp. setpunkt pumpe start BattEXC_AlrSet C Temp.Diff. alarm setpunkt på væskekobletbatteri Alarm når Temp.Diff. (i forhold til UdeTemp.) efter varmevekslerbatteri ved 50% effekt (eller mere) er lavere end alarm setpunkt, HW_UpStartPow % Varmebatteri: Opstart effekt setpunkt [1/100%] HW_PumpFunc Funktion af cirk. pumpe på varmebatteri: 0 -> Pumpe kører konstant 1 -> Pumpe kører ved varmekrav > 0 (AutoMode) 2 -> Pumpe kører når udetemperatur < pumpe start temp. setpunkt HW_PmpStartTmp C Starttemperatur for cirk.pumpe på varmebatteri Bruges KUN sammen med WaterPumpFunc (Address 230) = 2 Pumpe kører når udetemperatur < temp. setpunkt pumpe start HW_FrzStopSet C Setpunkt for anti-frost reg når anlægget = stop [1/100 C] 24/32

25 NAVN ENHED OBJECT INSTANCE MIN MAX BEMÆRKNINGER HW_FrzDriftSet C Setpunkt for anti-frost reg når anlægget = drift [1/100 C] HW_FreezePB C P-Bånd for anti-frost reg [1/100 C] HW_FrzAlrTpSet C Setpunkt for anti-frost temp. alarm [1/100 C] CW_PumpFunc Funktion af cirk.pumpe køle: 0 -> Pumpe kører konstant 1 -> Pumpe kører når køleeffekt > 0 (AutoMode) 2 -> Pumpe kører når udetemperatur > pumpe start temp. setpunkt CW_PmpStartTmp C Temp. setpunkt for start af kølebatteri pumpe Bruges KUN sammen med WaterPumpFunc (Address 239) = 2 Pumpe kører når UdeTemp. > pumpe start temp. setpunkt [1/100 C] FiltSupStatAlr Pa Alarm grænse for trykfald indtags filter (static mode) FiltExtStatAlr Pa Alarm grænse for trykfald afkast filter (static mode) FiltSupDynAlr % Alarm grænse for trykfald indtags filter (dynamic mode) [1/100%] FiltExtDynAlr % Alarm grænse for trykfald afkast filter (dynamic mode) [1/100%] Alr_MailSetup Alarm mail opsætning 0 - Mail er ikke sendt 1 - Mail er sendt på A-alarm 2 - Mail er sendt på B-alarm 3 - Mail er sendt på A og B alarm BrugerRE_Func Funktion på alarmrelæ 2: 0 - B-alarm 1 - Lav indikator 2 - Høj indikator 25/32

26 ANNEX A - PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE) (This annex is part of this Standard and is required for its use.) BACnet Protocol Implementation Conformance Statement Date: Vendor Name: OJ Electronics A/S (Vendor Identifier: 368) Product Name: OJ-Air2 Product Model Number: OJ-Air2Master Application Software Version: 1.0 Firmware Revision: BACnet Protocol Revision: 1.5 Product Description: The BACnet driver enables BACnet control and supervision of a complete Air Handling Unit (AHU), which have an embedded OJ-Air2Master controller. The BACnet driver is embedded in OJ-Air2Masters with software version 2.0 or higher. BACnet Standardized Device Profile (Annex L): o BACnet Operator Workstation (B-OWS) o BACnet Building Controller (B-BC) o BACnet Advanced Application Controller (B-AAC) x BACnet Application Specific Controller (B-ASC) o BACnet Smart Sensor (B-SS) o BACnet Smart Actuator (B-SA) List all BACnet Interoperability Building Blocks Supported (Annex K): Data Sharing DS-RP-B Data Sharing-Read Property-B Data Sharing DS-WP-B Data Sharing-Write Property-B Device Management DM-DDB-B Device Management-Dynamic Device Binding-B Device Management DM-DOB-B Device Management-Dynamic Object Binding-B Device Management DM-DCC-B Device Management-Dynamic Communikation Control-B Segmentation Capability: o Segmented requests supported o Segmented responses supported Window Size Window Size Standard Object Types Supported: 1) The CreateObject service is not supported 2) The DeleteObject service is not supported 3) Writeable properties are listed in bold 4) In general, no property range restrictions exist, some specific applications may have specific restrictions. 26/32

27 27/32 Object type Properties Analog Input Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Units Min_Pres_Value Max_Pres_Value Resolution Reliability COV_Increment Analog Output Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Units Priority_Array Relinquish_Default COV_Increment Binary Input Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Polarity Reliability Binary Output Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Priority_Array Relinquish_Default Device Object_Identifier Object_Name Object_Type System_Status Vendor_Name Vendor_Identifier Model_Name Firmware_Revision Application_Software_Version Location Description Protocol_Version Protocol_Revision Protocol_Services_Supported Protocol_Object_Types_Supported Object_List Max_APDU_Length_Accepted Segmentation_Supported APDU_Timeout Number_Of_APDU_Retries Device_Address_Binding Database_Revision

28 Data Link Layer Options: x BACnet IP, (Annex J) o BACnet IP, (Annex J), Foreign Device o ISO , Ethernet (Clause 7) o ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8) o ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) o MS/TP master (Clause 9), baud rate(s): o MS/TP slave (Clause 9), baud rate(s): o Point-To-Point, EIA 232 (Clause 10), baud rate(s): o Point-To-Point, modem, (Clause 10), baud rate(s): o LonTalk, (Clause 11), medium: o Other: Device Address Binding: Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) oyes x No Networking Options: o Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc. o Annex H, BACnet Tunneling Router over IP o BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices? o Yes o No Character Sets Supported: Indicating support for multiple character sets does not imply that they can all be supported simultaneously. x ANSI X3.4 o IBM /Microsoft DBCS x ISO o ISO (UCS-2) o ISO (UCS-4) o JIS C 6226 If this product is a communication gateway, describe the types of non-bacnet equipment/networks(s) that the gateway supports: Not applicable 28/32

29 29/32

30 30/32

31 31/32

32 EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov Tel.: Fax: NOVEMA Aggregater AS Industriveien 25 N-2021 Skedsmokorset Tel.: Fax: EXHAUSTO AB Verkstadsgatan 13 S Mariestad Tel.: Fax: /32

BRUGERMANUAL Metasys N2 Open Protocol EXHAUSTO AIR 2

BRUGERMANUAL Metasys N2 Open Protocol EXHAUSTO AIR 2 Metasys N2 Open Protocol, EXHAUSTO AIR 2 BRUGERMANUAL Metasys N2 Open Protocol EXHAUSTO AIR 2 EXHAUSTO A/S Tel. +45 65 66 12 34 Odensevej 76 Fax +45 65 66 11 10 DK-5550 Langeskov exhausto@exhausto.dk www.exhausto.dk

Læs mere

Modbus data modellen er opbygget af fire primære data typer. I nedenstående skema er en kort oversigt over disse.

Modbus data modellen er opbygget af fire primære data typer. I nedenstående skema er en kort oversigt over disse. Modbus RTU protokol Indledning Modbus er en application layer messaging protocol, placeret på 7. lag i OSI modellen, der sørger for client/server kommunikation mellem enheder koblet på forskellige typer

Læs mere

Nedenstående oversigt henviser til alle alarmtyper og -tekster der kan forekomme i under driften af AIRTS aggregatet.

Nedenstående oversigt henviser til alle alarmtyper og -tekster der kan forekomme i under driften af AIRTS aggregatet. ALARM OVERSIGT Nedenstående oversigt henviser til alle alarmtyper og -tekster der kan forekomme i under driften af AIRTS aggregatet. Den enkelte alarm har et nummer der sammen med alarmteksten registreres

Læs mere

Ventilationsaggregater. Topvex FR, SR, TR

Ventilationsaggregater. Topvex FR, SR, TR Topvex FR, SR, TR 206951-DK 22-08-2011V.A004 (C. 3.0-1-06) Indhold 1... 1 1.1 Funktionsindstillinger... 1 1.2 Indstilling af ugeprogram... 5 1.3 Alarmkonfiguration... 6 1.4 Noter og underskrift... 9 1

Læs mere

TX electronic controller

TX electronic controller TX electronic controller Version 1.1 Rev. 14. Dec. 2011 Side 1 af 20 1.0.0 Indhold 1.0.0 Indhold... 2 2.0.0 Oversigt... 3 3.0.0 Funktionsbeskrivelse... 4 3.1.0 Bruger funktioner... 4 3.1.1 Dagsdrift...

Læs mere

EX-EC ikke tilsluttet bus i FanIO stik B, Fejl i buskabel, Buskabel i EX-EC monteret i stik B i stedet for A

EX-EC ikke tilsluttet bus i FanIO stik B, Fejl i buskabel, Buskabel i EX-EC monteret i stik B i stedet for A forsink grænse stop WEB text Pop-up text 1 A 3 N/A Brand alarm Brandalarm 1 Brand alarm udløst. 2 A 3 N/A X Ekstern brandtermostat alarm Ekstern Brandtermostat 2 Ekstern brandtermostat 3 A 3 N/A X Intern

Læs mere

BRUGERMANUAL WEBSERVER V1.18 EXHAUSTO AIR 2

BRUGERMANUAL WEBSERVER V1.18 EXHAUSTO AIR 2 Webserver V1.18, EXHAUSTO AIR 2 BRUGERMANUAL WEBSERVER V1.18 EXHAUSTO AIR 2 EXHAUSTO A/S Tel. +45 65 66 12 34 Odensevej 76 Fax +45 65 66 11 10 DK-5550 Langeskov exhausto@exhausto.dk www.exhausto.dk IDRIFTSÆTTELSE

Læs mere

Overvågning af punktsug, URANOS LOCAL EXHAUST GUARD

Overvågning af punktsug, URANOS LOCAL EXHAUST GUARD Sikkert arbejde ved brug af punktsug Uranos Local Exhaust Guard kan fungere efter to forskellige principper: 1. Flowovervågning. 2. Trykovervågning. Flowovervågning Anvendes fortrinvis når hvert enkelt

Læs mere

NETLON NETLON 1.1 Variabel liste VSD1

NETLON NETLON 1.1 Variabel liste VSD1 1.1 Variabel liste VSD1 VSD1_1q.xif ProgramID: 90 56 53 44 31 5F 31 70 Generated at: 7. januar 2005, 12:16 No. Variable name Dir SNVT type Default Connect 0 nvioccmancmd In SNVT_occupancy (109) Start stop

Læs mere

MICROCHILLER 2 Manual 001721B02

MICROCHILLER 2 Manual 001721B02 MICROCHILLER 2 Manual 001721B02 Udgave 07.08 Erstatter 06.05 Brugervejledning BRUGER Version Brugergrænseflade Grønt 3 cifret display (plustegn og komma), gult driftssignal og rødt alarmsignal. Betydning

Læs mere

Udgivet af BMS. Danmarks Tekniske Universitet DTU Campus Service

Udgivet af BMS. Danmarks Tekniske Universitet DTU Campus Service VEJLEDNING I INDKØB OG INSTALLATION AF BACNET ENHEDER Denne standard er en del af DTU s standarder til entreprenører og kunder omhandlende BMS (Building Management System). Standardc:\users\topl\dropbox\dtu\bms\standarder\

Læs mere

NETLON. 1.1 Variabel liste BL2_5B. BL2_5_variabelliste.doc Side 1 af 13

NETLON. 1.1 Variabel liste BL2_5B. BL2_5_variabelliste.doc Side 1 af 13 1.1 Variabel liste BL2_5B No. Variable name Dir SNVT type Default Connect 0 nvitimeset In SNVT_time_stamp (84) Indstilling af klokken 1 nviisholiday In SNVT_lev_disc (22) Signal ved ferie fra CTS-anlæg

Læs mere

Servicerapport. Dato: Init. : Ordre nr : Kontaktperson : Tlf.: Placering: Baglokale. 28 05 2013 Deichmann - Herning RSV 20195V-13. Butik.

Servicerapport. Dato: Init. : Ordre nr : Kontaktperson : Tlf.: Placering: Baglokale. 28 05 2013 Deichmann - Herning RSV 20195V-13. Butik. Servicerapport Kunde : Ordre nr : Kontaktperson : Tlf.: Betjeningsområde: Komponenter: Indtags-/Afkastriste Filter Varmeflade Ventilator Motor Svingningsdæmpere Remtræk Lejer Luftbefugter Termometre Varmegenvinding

Læs mere

Digital elektronisk termostat med afrimning styring. Brugermanual. Læs og arkiver Disse instruktioner

Digital elektronisk termostat med afrimning styring. Brugermanual. Læs og arkiver Disse instruktioner Digital elektronisk termostat med afrimning styring Brugermanual Læs og arkiver Disse instruktioner Denne manual indeholder vejledning i brugen af følgende 2 styringer. PJEZS00000 kun køl Vigtigt! Begge

Læs mere

LAD NATUREN KOMME INDENFOR

LAD NATUREN KOMME INDENFOR LAD NATUREN KOMME INDENFOR NOVEMBER 2015 2 TX KOMFORT Decentral ventilation med en kapacitet på 250 til 1000 m³/h, kan anvendes følgende steder: skoler kontorer mødelokaler kantiner institutioner pavilloner

Læs mere

Variabel liste NETLON. RS1_variabelliste Side 1 af 8

Variabel liste NETLON. RS1_variabelliste Side 1 af 8 Variabel liste No. Variable name Dir SNVT Type NV Description Default 0 nvolampvalfbl2 Out SNVT_switch (95) Aktuel lys niveau lys 2 1 nvimasterin In SNVT_state (83) Bindes til, fra slave out, ved slave/master

Læs mere

Montage og brugsanvisning

Montage og brugsanvisning Montage og brugsanvisning System JA 3000 Standalone styring for befugter og affugter for relativ fugtighed eller dugpunkt. Indholdsfortegnelse Ophavsrettigheder... 3 EU overensstemmelseserklæring... 4

Læs mere

Introduktion...3 Input Status Register...4 Coil Status Register...5 Input Register...6 Holding Register...14

Introduktion...3 Input Status Register...4 Coil Status Register...5 Input Register...6 Holding Register...14 PASCAL Regula Master Lindab Pascal Regula master Introduktion...3 Input Status Register...4 Coil Status Register...5...6 Holding Register...14 Rev. Pascal-Signals 15-12-2014-3 Introduktion Signaltyper

Læs mere

BACnet Protokol. Brugermanual EXcon SW vers fm. EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov

BACnet Protokol. Brugermanual EXcon SW vers fm. EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov BACnet Protokol Brugermanual EXcon SW vers. 3.19 EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov Tel. +45 65 66 12 34 Fax +45 65 66 11 10 exhausto@exhausto.dk www.exhausto.dk Produktinformation......................................................3

Læs mere

16. september 2013 InClimate funktionalitets og modbus setup version 7.1 Side 2

16. september 2013 InClimate funktionalitets og modbus setup version 7.1 Side 2 InClimate Indhold InClimate funktionalitet setup... 4 Mode 0, Transmitter mode:... 6 Mode 1, Transmitter med stiller funktion.... 6 Mode 2, PI Regulator 1:... 6 Vout1, VAV output.... 6 Valg af PI styreparametre

Læs mere

PAR-555-SYS Konstanttrykregulering

PAR-555-SYS Konstanttrykregulering PAR-555-SYS Konstanttrykregulering www.oeland.dk Side 1 af 16 1. Produktinformation... 3 2. Installation.. 4 3. Oversigtstegning.. 5 4. Funktioner.. 6 5. Tekniske data. 9 6. Tilslutning... 10 7. Problemløsning..

Læs mere

Netværk & elektronik

Netværk & elektronik Netværk & elektronik Oversigt Ethernet og IP teori Montering af Siteplayer modul Siteplayer teori Siteplayer forbindelse HTML Router (port forwarding!) Projekter Lkaa Mercantec 2009 1 Ethernet På Mars

Læs mere

www.ojelectronics.com Alle specifikationer og oplysninger kan ændres uden yderligere varsel.

www.ojelectronics.com Alle specifikationer og oplysninger kan ændres uden yderligere varsel. www.ojelectronics.com Generelt Standard KNX produkter som eks. PIR følere, CO2-følere, fugtfølere (%rh), VOCog temperaturfølere kan anvende sammen med OJ GreenZone systemet. Følerne skal være placeret

Læs mere

111570DK-05 2015-11 CS60. Tilslutnings- og konfigurationsvejledning Styringsautomatik

111570DK-05 2015-11 CS60. Tilslutnings- og konfigurationsvejledning Styringsautomatik DK-0 0- CS0 Tilslutnings- og konfigurationsvejledning Styringsautomatik Tilslutning af CU0. Kredsløbslayout Art.nr. Art.nr. P Art.nr. P P P Art.nr. P P P P P P P P P P P Stik til styrepaneler Kontakt til

Læs mere

TX Controller Betjeningsvejledning

TX Controller Betjeningsvejledning TX Controller Betjeningsvejledning Version 1.7 Rev. 2015.05.29 Indholdsfortegnelse 1.0.0 Oversigt... 3 1.1.0 Forceret drift... 4 1.2.0 Forlænget drift... 4 1.3.0 Styringsmenu... 5 1.4.0 Temperatur Setpunkt...

Læs mere

Bruger manual AGAM kontrolboks

Bruger manual AGAM kontrolboks Bruger manual AGAM kontrolboks Kontrol boks set- up Front tavle (dør) 1. LED : Indikerer hvilke funktioner der er tilsluttet. (Lys tændt = funktion tændt ; lys slukket = funktion slukket). #1- Hovedpumpe

Læs mere

BAS 914S/929S Datablad

BAS 914S/929S Datablad BAS 914S/929S BA Systems Petershvilevej 1 DK-3200 Helsinge http://www.basystems.dk BAS 914S/929S tilhører en familie af programmerbare kontrollere der er målrettet til mindre samt medium størrelse installationer.

Læs mere

OJ Air2 Master. BACnet Protocol

OJ Air2 Master. BACnet Protocol 67012E- 01/16-osh OJ Air2 Master BACnet Protocol Fra SW 3.25 Dansk 2016 OJ Electronics A/S The Trade Mark OJ is an registered Trade Mark belonging to OJ Electronics A/S Alle specifikationer og oplysninger

Læs mere

www.ic-electronic.com

www.ic-electronic.com www.ic-electronic.com Soft starter med indbygget motorbeskyttelse, strøm og spændingskontrol 3 faset kontrolleret med indbygget by-pass Nominel driftspænding 400VAC Frekvens 45... 65Hz selvindstilling

Læs mere

FSystem beskrivelse PAR 200 CLOCK

FSystem beskrivelse PAR 200 CLOCK FSystem beskrivelse PAR 200 CLOCK Driftvejledningsnr: PAR-200-SYS-DK-041223 Beskrivelse Billede PAR-200-SYS er den overordnede og komplette beskrivelse af Ølands nye tidsstyring inden for analoge regulatorer.

Læs mere

Teknisk datablad Brandautomatik

Teknisk datablad Brandautomatik Teknisk datablad Brandautomatik Brandautomatik www.air2trust.com Indeks VEJLEDNINGER 4 Brugervejledning 6 Menuoversigt 7 Displayvejledning ELDIAGRAMMER 9 Eldiagram for 1-5 spjæld 10 Eldiagram for 6-20

Læs mere

IDRIFTSÆTTELSE OG PROGRAMMERING

IDRIFTSÆTTELSE OG PROGRAMMERING 3003959-2011-06-24 Styring og Funktion V1.24,, EXHAUSTO AIR 2 STYRING OG FUNKTION V1.24 EXHAUSTO AIR 2 EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov Tel. +45 65 66 12 34 Fax +45 65 66 11 10 exhausto@exhausto.dk

Læs mere

Kalibrering af Vejeceller og Flowmålere i processen INSA 1 / 48

Kalibrering af Vejeceller og Flowmålere i processen INSA 1 / 48 Kalibrering af Vejeceller og Flowmålere i processen INSA 1 / 48 INSA 2 / 48 Hvordan man bygger en flowvogn Målsætning: at udnytte tidligere erfaringer med bygning af flowvogne. Fokus på kompakt design

Læs mere

Axel Kiers Vej 32 8270 Højbjerg Tlf.: 8736 0414 Mobil: 2046 0414

Axel Kiers Vej 32 8270 Højbjerg Tlf.: 8736 0414 Mobil: 2046 0414 CorrigoE og ETool ETool:...2 Opdatering af regulator...2 Første gang:...2 E-Cable-USB...2 ETool Programmet...3 Kommunikations indstilling...3 Regulator søgning...5 Log On / Off...6 Downloade...7 Konfigurering

Læs mere

Billede. Boksventilator BVB. Generel funktionsbeskrivelse

Billede. Boksventilator BVB. Generel funktionsbeskrivelse Driftvejledning snr: PAR-550-SYS-DK-041223 F System beskrivelse PAR 550 Konstant tryk regulering Beskrivelse Billede Forsyning 1x230V+PE Konstanttrykregulering plug & play RS 485 kontrolleret PAR-550-SYS

Læs mere

Delta Elektronik A/S - AKD

Delta Elektronik A/S - AKD Delta Elektronik A/S - AKD Hardware og type oversigt Grundlæggende oplysninger med forbindelser Opsætning af IP adresser på drev alle muligheder Gennemgang af WorkBench Up/Down load parametre filer Mest

Læs mere

Beskrivelse af vejrstation OM1 NETLON NETLON. Dette dokument indeholder en beskrivelse af en vejrstation OM1 fra Netlon.

Beskrivelse af vejrstation OM1 NETLON NETLON. Dette dokument indeholder en beskrivelse af en vejrstation OM1 fra Netlon. Beskrivelse af vejrstation OM1 NETLON Dette dokument indeholder en beskrivelse af en vejrstation OM1 fra Netlon. Indholdsfortegnelse Kort beskrivelse... 4 1.1 Anvendelse... 4 1.2 Konstruktion... 4 Funktionsbeskrivelse...

Læs mere

VERSO-P & VERSO-R. Luftbehandlingsaggregater Installations - og betjeningsvejledning for OJ Air2. Uniq Comfort

VERSO-P & VERSO-R. Luftbehandlingsaggregater Installations - og betjeningsvejledning for OJ Air2. Uniq Comfort VERSO-P & VERSO-R Luftbehandlingsaggregater Installations - og betjeningsvejledning for OJ Air2 Uniq Comfort Juli 2011 Indholdsfortegnelse 1.0 Installationsvejledning 1.1 Samling af sektioner...3 1.2 Tilslutning

Læs mere

Seitron digital trådløs rumtermostat

Seitron digital trådløs rumtermostat Seitron digital trådløs rumtermostat Drift og vedligeholdelse KONTAKT INFO Golan Pipe Systems ApS Lollandsvej 14 DK-5500 Middelfart Tlf. +45 6441 7732 info@golan.dk www.golan.dk SEITRON DIGITAL TRÅDLØS

Læs mere

WIO200A INSTALLATIONS MANUAL Rev Dato:

WIO200A INSTALLATIONS MANUAL Rev Dato: WIO200A INSTALLATIONS MANUAL 111686-903 Rev. 1.01 Dato: 10.01.2013 Side 1 af 14 Contents Contents... 2 Introduction... 3 Pin assignment of the terminal box connector for customer... 4 Pin assignment of

Læs mere

VENTILATIONSAGGREGAT VUT 160V/350VB/550VB EC

VENTILATIONSAGGREGAT VUT 160V/350VB/550VB EC AIR COMFORT AIR DIFFUSION VE: DK. CC VENTILATIONSAGGREGAT» TEKNISKE DATA Til A Til A PRODUKTFAKTA: Ventilationsaggregat i varme- og lydisoleret kabinet Luftmængde op til m³/h Virkningsgrad op til 9% Ventilationsaggregaterne

Læs mere

LAD NATUREN KOMME INDENFOR

LAD NATUREN KOMME INDENFOR LAD NATUREN KOMME INDENFOR OKTOBER 2012 2 TX KOMFORT Decentral ventilation med en kapacitet på 250 til 1000 m³/h, kan anvendes følgende steder: skoler kontorer mødelokaler kantiner institutioner pavilloner

Læs mere

MultiProgrammer Manual

MultiProgrammer Manual MultiProgrammer Manual MultiProgrammeren bruges til at læse og skrive værdier til ModBus register i LS Controls frekvensomformer E 1045. Dansk Version side 2 til 4 The MultiProgrammer is used for the writing

Læs mere

Video Projector Controller. Brugermanual

Video Projector Controller. Brugermanual Jægergårdsgade 152/05A DK-8000 Aarhus C DENMARK WWW.WAHLBERG.DK l Video Projector Controller Brugermanual WWW.WAHLBERG.DK TELEPHONE +45 86 18 14 20 CELL PHONE +45 40 52 20 88 EMAIL: mads@wahlberg.dk Feb

Læs mere

Danvent DV og TIME. Systemair E28 Styring. Betjeningsvejledning. Ændring af tid, temperatur og luftydelse. Version 3.1

Danvent DV og TIME. Systemair E28 Styring. Betjeningsvejledning. Ændring af tid, temperatur og luftydelse. Version 3.1 Ventilatorer Brand- og røgprodukter Ventilationsaggregater Luftfordeling Tilbehør Ventilationssystemer Systemair E28 Styring Version 1 Betjeningsvejledning Danvent DV og TIME Ændring af tid, temperatur

Læs mere

Installationsguide. ECL Comfort 310, applikation A333 Ekstrakt. 1.0 Indhold. 1.0 Indhold... 1

Installationsguide. ECL Comfort 310, applikation A333 Ekstrakt. 1.0 Indhold. 1.0 Indhold... 1 1.0 Indhold 1.0 Indhold... 1 2.0 Indstillinger... 2 2.1 Reguleringsparametre, cirkulationspumpe(r)................. 2 2.2 Pumpekontrol...................................................... 6 3.0 Blandet...

Læs mere

Revision (sidste opdatering) Software Version 8:29

Revision (sidste opdatering) Software Version 8:29 Instruktion TWIN enhed (til brug ved 1 så-enhed) Revision 1.7 20130514 (sidste opdatering) Software Version 8:29 Index Program version... 1 Skift af værdier... 2 Tilpasning af parametre... 2 Kalibrering...

Læs mere

Syddansk erhvervsskole

Syddansk erhvervsskole Syddansk erhvervsskole Allan Tingkær Bygningsreglement 2010 Særlige krav til klimaskærm: Luftskiftet gennem utætheder i klimaskærmen må ikke overstige 1,5 l/s pr. m 2 opvarmet areal ved trykprøvning med

Læs mere

LON I/O modul. 3001988-2005-11-16.fm. EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov

LON I/O modul. 3001988-2005-11-16.fm. EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov DK LON I/O modul EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov Tel. +45 65 66 12 34 Fax +45 65 66 11 10 exhausto@exhausto.dk www.exhausto.dk 1 Produktinformation... 3 2 Placering og montage af LON I/O modulet...

Læs mere

Instruktion. SEEDER+ unit. Revision (last update) Software Version 8:32. Indhold

Instruktion. SEEDER+ unit. Revision (last update) Software Version 8:32. Indhold Instruktion SEEDER+ unit Revision 1.82 20140825 (last update) Software Version 8:32 Indhold Beskrivelse... 1 Program version... 1 Skift af værdier... 2 Justering af parametre... 2 Kalibrering... 4 Kalibrering

Læs mere

PAR-600-CO2. Datablad. ØLAND A/S Vi arbejder for din succes Energivej 3-7, 2750 Ballerup, Tel. 7020 1911, Fax 4453 1051 www.oeland.

PAR-600-CO2. Datablad. ØLAND A/S Vi arbejder for din succes Energivej 3-7, 2750 Ballerup, Tel. 7020 1911, Fax 4453 1051 www.oeland. -DK-17-01-08 Anvendelse Øland automatik PAR-600- anvendes, hvor der ønskes at måle og eller/regulerer rumluftens indhold, temperatur og relativ fugtighed. Automatikken er særdeles velegnet til styring

Læs mere

Rumtemperaturregulator med ugekontaktur og LCD

Rumtemperaturregulator med ugekontaktur og LCD 3 035 Rumtemperaturregulator med ugekontaktur og LCD for varmesystemer RDE10 opunktregulering med ON/OFF-styresignaludgang for opvarmning Driftsformer: Normal- og sparetemperatur Ugekontaktur og manuel

Læs mere

SPEED-Commander Frekvensomformer. Program nr. 1 Software version 5.0.3. PI-regulering

SPEED-Commander Frekvensomformer. Program nr. 1 Software version 5.0.3. PI-regulering SPEED-Commander Frekvensomformer Driftsvejledning Bemærk: Speciel Software Program nr. 1 Software version 5.0.3 PI-regulering Til parameterliste og tilslutninger af styreklemmer anvendes vedhæftede programbeskrivelse.

Læs mere

Vejledning ECC Styring. ECC Styring. enervent.dk / ECC vejledning

Vejledning ECC Styring. ECC Styring. enervent.dk / ECC vejledning ECC Styring ECC Styring for Enervent boligventilationsaggregater Enervent boligaggregater er beregnet til kontinuerlig drift og bør af hensyn til kondensdannelse i aggregat og kanaler aldrig stoppes. Aggregaterne

Læs mere

ØLAND ØLAND. Drift og vedligeholdelse (bruger) Brugervejledning nr. AHU-250-brugervejledning 01-03-12-1. Luftbehandlingsaggregat AHU-250-M-EC

ØLAND ØLAND. Drift og vedligeholdelse (bruger) Brugervejledning nr. AHU-250-brugervejledning 01-03-12-1. Luftbehandlingsaggregat AHU-250-M-EC Brugervejledning Aggregat Betjeningspanel PAR-AHU-250 A/S Park Allé 366, 2605 Brøndby, Tel. 7020 1911, Fax 4453 1051 www.oeland.dk 1 Drift og vedligeholdelse (bruger) Automatikfunktioner og betjeningspanel

Læs mere

BRUGERMANUAL LON Protocol EXHAUSTO AIR 2

BRUGERMANUAL LON Protocol EXHAUSTO AIR 2 LON Protocol, EXHAUSTO AIR 2 BRUGERMANUAL LON Protocol EXHAUSTO AIR 2 EXHAUSTO A/S Tel. +45 65 66 12 34 Odensevej 76 Fax +45 65 66 11 10 DK-5550 Langeskov exhausto@exhausto.dk www.exhausto.dk INDLEDNING

Læs mere

DUKA PLUS L180E. DUKA Ventilation. din tryghed for et sundt indeklima

DUKA PLUS L180E. DUKA Ventilation. din tryghed for et sundt indeklima DUKA PLUS L180E DUKA Ventilation din tryghed for et sundt indeklima DUKA PLUS L180E Beskrivelse DUKA PLUS L180E er et fuldautomatisk ventilation aggregat med varmegenvinding, der tilføjer frisk filtreret

Læs mere

BETJENINGSVEJLEDNING KLIMASTAT TYPE 5610

BETJENINGSVEJLEDNING KLIMASTAT TYPE 5610 Side 1 af 7 Betjening af Klimastaten sker direkte på den trykfølsomme skærm. På skærmen findes 5 betjeningselementer. INFO, DRIFT, MANUEL, DATO, SETUP. Ved at klikke på et af ovenstående elementer åbnes

Læs mere

LAD NATUREN KOMME INDENFOR

LAD NATUREN KOMME INDENFOR LAD NATUREN KOMME INDENFOR JANUAR 2015 2 TX INDUSTRI Decentral ventilation med en kapacitet på 1400-3000 m³/h, kan anvendes følgende steder: autoværksteder produktionsvirksomheder idrætshaller byggemarkeder

Læs mere

Installatør Guide. CTS6000 Webcontrol

Installatør Guide. CTS6000 Webcontrol Installatør Guide CTS6000 Webcontrol Version 1.00, 30.06.2010 Indholdsfortegnelse Indholdsfortegnelse... 2 Figur oversigt... 3 Indledning... 4 Hurtigt i gang... 5 VAV med én tryktransmitter... 6 VAV med

Læs mere

SVINGNING. 2 x 5,3 kw AC

SVINGNING. 2 x 5,3 kw AC SVINGNING 2 x 5,3 kw AC SIDE 1/8 MOTOR TEGNING SIDE 2/8 JUSTERINGSVEJLEDNING FOR AC SVINGNING FUNKTIONSBESKRIVELSE AF SVINGNING Svingningen er drevet af to parallel koblet kortslutningsmotorer. Fra frekvensomformer

Læs mere

BAS 920. Datablad. BA Systems Petershvilevej 1 DK-3200 Helsinge http://www.basystems.dk

BAS 920. Datablad. BA Systems Petershvilevej 1 DK-3200 Helsinge http://www.basystems.dk BAS 920 BA Systems Petershvilevej 1 DK-3200 Helsinge http://www.basystems.dk BAS 920 tilhører en familie af frit programmerbare kontrollere designet til at være skalerbare fra helt små til meget store

Læs mere

INSTRUKTION. OJ-DV Hterm. OJ Drives A DRIVES PROGRAMME DEDICATED TO VENTILATION SOLUTIONS. 67436 05/15 (OSH) 2015 OJ Electronics A/S

INSTRUKTION. OJ-DV Hterm. OJ Drives A DRIVES PROGRAMME DEDICATED TO VENTILATION SOLUTIONS. 67436 05/15 (OSH) 2015 OJ Electronics A/S INSTRUKTION 67436 05/15 (OSH) 2015 OJ Electronics A/S OJ-DV Hterm OJ Drives A DRIVES PROGRAMME DEDICATED TO VENTILATION SOLUTIONS GENERELT OJ-DV Hterm er en håndbetjeningsenhed, som anvendes til indstilling

Læs mere

DIN modul eller færdig IBI boks

DIN modul eller færdig IBI boks Komfort og Lysregulering oct. 2004 DIN modul eller færdig IBI boks IBI boks arbejdsgang Finde DIN hardware Specificere software versioner Projektere bokse Producere bokse Komfort- og lysregulering Lonbox

Læs mere

Monteringsvejledning. Calefa TD og S. Montage og opsætning af cirkulation

Monteringsvejledning. Calefa TD og S. Montage og opsætning af cirkulation Monteringsvejledning Calefa TD og S Montage og opsætning af cirkulation Styringen skal være med software version 3.2 eller nyere for at den kan styre cirkulationen. Software versionen findes ved at følge

Læs mere

TEKNISK INFORMATION - HRV 501 Boligventilation med rotorveksler og fugtoverførsel

TEKNISK INFORMATION - HRV 501 Boligventilation med rotorveksler og fugtoverførsel TEKNISK INFORMATION - HRV 501 Boligventilation med rotorveksler og fugtoverførsel HRV 501 1 Generel beskrivelse 3 2 Tekniske data 5 3 Tilbehør 7 Forbehold for ændringer og trykfejl. September 2014. Generel

Læs mere

HP Color LaserJet Professional CP5225n Laser

HP Color LaserJet Professional CP5225n Laser HP Color LaserJet Professional CP5225n Laser Description HP Color LaserJet Professional CP5225n - Printer - color - laser - A3 - - up to 20 ppm (mono) / up to 20 ppm (color) - capacity: 350 sheets - USB,

Læs mere

TILSLUTNINGSANVISNING

TILSLUTNINGSANVISNING TILSLUTNINGSANVISNING STYREENHED TIL ROTERENDE VARMEVEKSLERE MiniMax V / VK Revideret 2014-10-06 Version 1.5.1 F21037901DK Overensstemmelseserklæring Producentens forsikring om produktets overensstemmelse

Læs mere

MultiController E 0-100% 24V og 230V

MultiController E 0-100% 24V og 230V MultiController E 0-100% 24V og 230V Manuel udgangsstyring 0-100% eller On/Off og Mod-bus interface Software Version 2.1 08 Indholdsfortegnelse 1 Montering... 2 2 Funktioner... 4 2.1 Bruger interface...

Læs mere

Total bygningsautomatik så enkelt kan det gøres

Total bygningsautomatik så enkelt kan det gøres Total bygningsautomatik så enkelt kan det gøres Indhold Total bygningsautomatik så enkelt kan det gøres Peter Christensen Brian Egeberg Lillian Andersen EcoBuilding EcoBuilding EcoBuilding Projektchef

Læs mere

Fjernbetjening Flex Service manual

Fjernbetjening Flex Service manual Fjernbetjening Flex Service manual Symboler på luftretning på anlæg Blå Rød Blå Rød 1 Teknikker indstillinger: Menu-Advance-Service Kodeord: 4444 1.Exit: retur til hovedmenu DER ANBEFALES IKKE AT ÆNDRE

Læs mere

CO2 Control Box E-Cab-980

CO2 Control Box E-Cab-980 CO2 Control Box E-Cab-980 CO2 Control Box E-Cab-980 er beregnet til detektering og alarmereing ved utætheder i CO2 køleanlæg i køle- og fryserum. CO2 Control Box E-Cab-980 er designet til at fungere sammen

Læs mere

LAD NATUREN KOMME INDENFOR

LAD NATUREN KOMME INDENFOR LAD NATUREN KOMME INDENFOR DECEMBER 2014 2 TX KOMFORT Decentral ventilation med en kapacitet på 250 til 00 m³/h, kan anvendes følgende steder: skoler kontorer mødelokaler kantiner institutioner pavilloner

Læs mere

Systemair Connect. Opsætning

Systemair Connect. Opsætning Systemair Connect Opsætning Opsætning af Systemair Connect Denne vejledning er lavet for at hjælpe dig i gang med opsætningen af Systemair Connect. Du kan bl.a. læse om, hvordan du opbygger en understruktur

Læs mere

TILSLUTNINGSANVISNING STYREENHED TIL ROTERENDE VARMEVEKSLERE

TILSLUTNINGSANVISNING STYREENHED TIL ROTERENDE VARMEVEKSLERE TILSLUTNINGSANVISNING STYREENHED TIL ROTERENDE VARMEVEKSLERE MicroMax180 Overensstemmelseserklæring Producentens forsikring om produktets overensstemmelse med kravene i EMC-DIREKTIVET 89/336/EØF samt tillæg

Læs mere

TX 3000. Turbovex. Turbovex A/S Industrivej 45 9600 Aars Tlf. 96 98 14 62 Fax 98 62 42 24 E-mail: info@turbovex.dk. Udvendig.

TX 3000. Turbovex. Turbovex A/S Industrivej 45 9600 Aars Tlf. 96 98 14 62 Fax 98 62 42 24 E-mail: info@turbovex.dk. Udvendig. Turbovex Decentral ventilation med varmegenvinding TX 3000 er et nyudviklet koncept for luftskifte I værksteder, industrihaller og lagerbygninger etc. Ventilationsaggregatet monteres gennem taget med kun

Læs mere

Ventilationsaggregat

Ventilationsaggregat Ventilationsaggregat Med modstrømsveksler MVE 700 1200-1900 Ventilationsaggregater med højeffektive modstrømsvekslere til brug i større boliger, kontorer og andre opvarmede områder. Geovent MVE udmærker

Læs mere

GSM SMS Modem MODEL: SA RTU-1 V1.01

GSM SMS Modem MODEL: SA RTU-1 V1.01 GSM SMS Modem MODEL: SA RTU1 V1.01 Brugervejledning Indgange: Der er fire indgange på modulet. De kan programmeres som normale indgange. De kan programmeres som tæller. Udgange: Der er en udgang på modulet

Læs mere

Oversigts billedet: Statistik siden:

Oversigts billedet: Statistik siden: 1 Tilslutning: Tilslut et nætværks kabel (medfølger ikke) fra serverens ethernet port til din router. Forbind derefter bus kablet til styringen, brun ledning til kl. 29, hvid ledning til kl. 30 Forbind

Læs mere

CLIMATIX TM. GBS Kontrolboks GBS Display Installations manual

CLIMATIX TM. GBS Kontrolboks GBS Display Installations manual CLIMATIX TM GBS Kontrolboks GBS Display Installations manual 1. Anvendelse 1.1. GBS Display til opsætning og overvågning Med GBS system, temperatur sensor i kanal, røgdetektor og pressostat sikrer korrekt

Læs mere

UNISONIC TECHNOLOGIES CO.,

UNISONIC TECHNOLOGIES CO., UNISONIC TECHNOLOGIES CO., 3 TERMINAL 1A NEGATIVE VOLTAGE REGULATOR DESCRIPTION 1 TO-263 The UTC series of three-terminal negative regulators are available in TO-263 package and with several fixed output

Læs mere

IBM Network Station Manager. esuite 1.5 / NSM Integration. IBM Network Computer Division. tdc - 02/08/99 lotusnsm.prz Page 1

IBM Network Station Manager. esuite 1.5 / NSM Integration. IBM Network Computer Division. tdc - 02/08/99 lotusnsm.prz Page 1 IBM Network Station Manager esuite 1.5 / NSM Integration IBM Network Computer Division tdc - 02/08/99 lotusnsm.prz Page 1 New esuite Settings in NSM The Lotus esuite Workplace administration option is

Læs mere

Fjernbetjening Flex Teknisk manual

Fjernbetjening Flex Teknisk manual Fjernbetjening Flex Teknisk manual VEKA INT. Indblæsnings aggregat 1 Beskrivelse Flex fjernbetjening kan bruges til at styre ventilationsanlæg med V1 og V2 printkort. Tekniske data Knapper på display Knap

Læs mere

Operation Manual SMS Air Conditioner Remote Controller Model No.: SR-001

Operation Manual SMS Air Conditioner Remote Controller Model No.: SR-001 Operation Manual SMS Air Conditioner Remote Controller Model No.: SR-001 Ls venligst denne instruktions manual igennem inden brug af produktet Thank you for purchasing our product. This smart unit is not

Læs mere

A. S1-knappen BEMÆRK! I M-modeller kan de viste målingsoplysninger også vælges via Modbus.

A. S1-knappen BEMÆRK! I M-modeller kan de viste målingsoplysninger også vælges via Modbus. V1.0.0 (20.02.201) 1 (10) ONTERING Enheden kan installeres i tørre omgivelse (I20) med skruer på væg eller en standardindbygningsboks. Den anbefalede installationshøjde er 1 180 cm. Enhedens placering

Læs mere

Maskindirektivet og Remote Access. Arbejdstilsynet Dau konference 2015 Arbejdsmiljøfagligt Center Erik Lund Lauridsen

Maskindirektivet og Remote Access. Arbejdstilsynet Dau konference 2015 Arbejdsmiljøfagligt Center Erik Lund Lauridsen Maskindirektivet og Remote Access Arbejdstilsynet Dau konference 2015 Arbejdsmiljøfagligt Center Erik Lund Lauridsen ell@at.dk Marts 2015 1 MD - Personsikkerhed og Remoten Hvad er spillepladen for personsikkerhed

Læs mere

KEB Combivert Frekvensomformer F5-B version (0,37-15kW)

KEB Combivert Frekvensomformer F5-B version (0,37-15kW) Quickguide KEB Combivert Frekvensomformer F5-B version (0,37-15kW) Forord Denne quickguide er et supplement til manualer udgivet af KEB og kan således ikke erstatte KEBs manualer. Det er kun en lille del

Læs mere

Zoneregulator, URANOS ZONE REGULATOR

Zoneregulator, URANOS ZONE REGULATOR Regulering af zone Reguleringssystemet, Uranos Zone Regulator, anvendes til regulering af: Luftbalance. Maksimums- og minimumsluftmængder. Temperatur (⁰C) og luftkvalitet (CO 2 ). Energidrift (højt/lavt

Læs mere

B. Rum sensor C. Rum sensor med gulv sensor som begrænser Tæthedsgrad (fugt/støv) Terminaler Max. 2.5mm 2 Gulvføler med 3,5m kabel NTC, 100kΩ / 25 C

B. Rum sensor C. Rum sensor med gulv sensor som begrænser Tæthedsgrad (fugt/støv) Terminaler Max. 2.5mm 2 Gulvføler med 3,5m kabel NTC, 100kΩ / 25 C NTC 700 Logisk programmerbar termostat for el-gulvvarme Introduktion NTC 700 er en logisk programmerbar termostat som forenkler indstilling og brug uafhængig af manual. NTC 700 er produceret iht. EN60730-1

Læs mere

ISC2100 kan kommunikere via RS232, RS485, Ethernet og LON, bruge USB enhed og USB host.

ISC2100 kan kommunikere via RS232, RS485, Ethernet og LON, bruge USB enhed og USB host. DK-1 ISC2100 er en frit programmerbar regulator, som er skalérbar til styring af helt små og op til meget store anlæg. ISC2100 kan eksempelvis anvendes til styring af varme, brugsvand og ventilation, samt

Læs mere

SeeTool - KNX løsninger til

SeeTool - KNX løsninger til SeeTool - KNX løsninger til Erhversbygninger Program 8.0.0.0.0.3 Kontinuert dagsregulering med PIR og manuel betjening - enkelt Lysreguleringsfunktioner Lyset tændes og slukkes automatisk afhængigt af

Læs mere

Brugermanual. KVU vekslere. 110-00038 Version 01.05

Brugermanual. KVU vekslere. 110-00038 Version 01.05 Brugermanual KVU vekslere 110-00038 Version 01.05 2 af 11 Indholdsfortegnelse Setpunktstabel:...4 Betjeningspanel KVU...5 Kontrolenhed...5 Menustruktur...5 Display visning...5 Display visning...6 Displayet...6

Læs mere

Vejledning til varmevekslerstyring SILVER C RX, RECOnomic str. 100/120, RECOsorptic str. 50-120

Vejledning til varmevekslerstyring SILVER C RX, RECOnomic str. 100/120, RECOsorptic str. 50-120 Vejledning til varmevekslerstyring SILVER C RX, RECOnomic str 100/120, RECOsorptic str 50-120 1 Generelt Varmevekslerstyringen er et styresystem til stepmotor, 380 W Det er beregnet til nøjagtig og lydsvag

Læs mere

Fundamentals of HVAC Control Systems

Fundamentals of HVAC Control Systems ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 4 Sensors and Auxiliary Devices 2007 ASHRAE Hong

Læs mere

Climaster ZCF luftbehandlingsaggregat. Brugervejledning - Quickguide

Climaster ZCF luftbehandlingsaggregat. Brugervejledning - Quickguide Climaster ZCF luftbehandlingsaggregat Brugervejledning - Quickguide EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov Tel. +45 65 66 12 34 Fax +45 65 66 11 10 exhausto@exhausto.dk www.exhausto.dk 1 Generelt

Læs mere

Danfoss Frekvensomformere & Softstartere VLT Drives

Danfoss Frekvensomformere & Softstartere VLT Drives Danfoss Frekvensomformere & Softstartere VLT Drives Indholdsfortegnelse VLT MICRO DRIVE FC-51.... 2 VLT HVAC DRIVE FC-102.... 4 VLT AQUA DRIVE FC-202.... 7 VLT AUTOMATION DRIVE FC-302....10 VLT 2800....13

Læs mere

BRUGERVEJLEDNING FLTA

BRUGERVEJLEDNING FLTA V2.2 (5.06.202) () FUNKTIONSPRINCIP fungerer som en basisstation for trådløse transmittere. Controller og målinger kan transmitteres via basestationen til de kontrolsystemer, der understøtter Modbus RTU-protokollen.

Læs mere

SERIES. Frekvensomformermotor

SERIES. Frekvensomformermotor SD Frekvensomformermotor Modeller SD Med et design, der er rettet mod mange forskellige applikationer, er Motovarios frekvensomformermotor lavet med kvalitetskomponenter og bliver styret af eksklusivt

Læs mere

InClimate. Funktionalitets setup og Modbus beskrivelse. Version 7200 Software. Version Senmatic A/S.

InClimate. Funktionalitets setup og Modbus beskrivelse. Version 7200 Software. Version Senmatic A/S. InClimate Funktionalitets setup og Modbus beskrivelse Version 7200 Software Version 7.200 Senmatic A/S www.senmatic.dk: Indhold InClimate funktionalitet setup... 4 Digital input... 6 Udvælgelsesguide for

Læs mere

Tænk på driften og ikke anlægsinvesteringerne. v/ Mads Møller - Leanvent

Tænk på driften og ikke anlægsinvesteringerne. v/ Mads Møller - Leanvent Tænk på driften og ikke anlægsinvesteringerne v/ Mads Møller - Leanvent Agenda 1. LCC og ventilation 2. Præsentation af LEANVENTs dråbespjæld LCC og ventilation Helhedsbetragtning LCCo Økonomi Der er ofte

Læs mere