VENTILATION I RUM MED INVASIVE INDGREB, HERUNDER OP-STUER

Størrelse: px
Starte visningen fra side:

Download "VENTILATION I RUM MED INVASIVE INDGREB, HERUNDER OP-STUER"

Transkript

1 VEJLEDENDE RETNINGSLINJER FOR VENTILATION I RUM MED INVASIVE INDGREB, HERUNDER OP-STUER VERSION 1.0, AF 1. SEPTEMBER 2014

2 INDHOLDSFORTEGNELSE 1 FORORD 5 2 INDLEDNING BAGGRUND UDVALGTE PRIMÆRE KILDER FOR OMRÅDET 7 3 PROJEKTERING DEFINITIONER LUFTSKIFTER ZONEOPDELING AF RUM OPRENSNING FILTRERING VENTILATIONSPRINCIPPER VARMEGENVINDINGSMETODE TEMPERATUR OG FUGTFORHOLD REGULERING; ANBEFALINGER VED DE FORSKELLIGE RUMTYPER LYD ENERGIFORBRUG COMMISSIONING DRIFT OG VEDLIGEHOLD 19 BILAG 1 KOMPONENTER 20 BILAG 2: PARTIKLERS FALDHASTIGHED 24 BILAG 3: KONTROL AFLEVERING, IBRUGTAGNING OG DRIFT 25 LITTERATURLISTE 28 2

3 FØLGENDE PERSONER HAR DELTAGET I UDARBEJDELSEN AF VEJLEDNINGEN: Kaj Hyldgaard Teknisk koordinator Nyt Aalborg Universitetshospital Lars Sloth Maskinmester Aalborg Universitetshospital Pernille Ripadal Hygiejnesygeplejerske Region Nordjylland Hans Hagelkvist Bloch Maskinmester Aarhus Universitetshospital Claus Berntsen Bygningschef Slagelse-Næstved Sygehuse Elsebeth Tvenstrup Overlæge, Mikrobiologi Jensen & Infektionskontrol Statens Serum Institut Dorthe Bechmann Civilingeniør, Chefkonsulent energi Region Hovedstaden Henning Pedersen Maskinmester Privat konsulent Hans Theil Civilingeniør, HVAC hospitaler Søren Jensen Johnny Nielsen Projektchef Fournais Energi Jan W. Holsøe Civilingeniør, VVS & ventilation, afdelingsleder Balslev Lars Nielsen HVAC-ingeniør Søren Jensen Jørgen Pedersen Civilingeniør, specialist ventilation og renrum Carsten Rasmussen Ingeniør Rambøll Thøger Haugstrup Projektleder, diplomingeniør Alectia Anders Kobbelgaard Civilingeniør, Energi og indeklima NNE Pharmaplan Midtconsult Bjørn Barbré Pedersen Seniorrådgiver Sundhed Midtconsult 3

4 1 FORORD Denne Vejledning er en opdateret og revideret udgave af vejledningen fra 1998 Ventilation i Operationsstuer udarbejdet af FSD. Opdateringen af vejledningen er sket på initiativ af: FSD (Foreningen af Sygehusmaskinemestre i Danmark) og FSTA (Forum for Sygehus Teknik og Arkitektur) Gruppen, som har gennemført arbejdet, er etableret via annoncering om arbejdet i relevante medier og ved foreningernes årsmøde om sygehus teknik. Alle medlemmer har tilsluttet sig gruppen af egen interesse og har ikke modtaget honorar for arbejdet. Gruppens faglige sammensætning har bestået af personer med erfaring inden for områder som projektering, daglig drift, hygiejne, energi og commissioning. FSD / FSTA har udpeget Midtconsult til at foretage det praktiske arbejde med revisionen, mens de øvrige medlemmer af arbejdsgruppen har bidraget med input og leveret den faglige sparring Gruppen har, via 10 møder, gennemgået alle processer og elementer i opgaven med at etablere og drifte et ventilationsanlæg til en oprationsstue, og udarbejdet en vejledning, der kan lede interesserede igennem den omfattende opgave. Som leder af gruppen takker Kaj Hyldgaard for det fantastiske engagement gruppens deltager har udvist, hvor debatlyst, høj faglig vidensniveau og forståelse for den samlede kompleksitet, har været bærende elementer i gruppens arbejdsform. 4

5 2 INDLEDNING I ventilationsmæssig sammenhæng skal operationsstuer ses både som rum med høje hygiejnekrav i forbindelse med invasive indgreb, ligesom krav til et godt arbejdsmiljø i arbejdsrum i henhold til regelsæt i Bygningsreglement og Arbejdstilsynets bestemmelser skal overholdes. Det er således både komfortkrav og hygiejnekrav, der er bestemmende for luftkvaliteten i forbindelse med installation af ventilationsanlæg som betjener rum med invasive indgreb. Denne vejledning indeholder forslag og anbefalinger til forhold, der i særlig grad bør være i fokus i forløbet med projektering, etablering, commissioning forud for klinisk ibrugtagning såvel som den efterfølgende drift og vedligehold af ventilationsanlæg, som betjener et rum hvor der foretages invasive indgreb. Vejledningen kan anvendes såvel ved nyetablering som ved renovering af operationsstuer og undersøgelsesrum etc. Det kan ofte være en kompleks og omfattende opgave at skulle opfylde krav til hygiejne og komfort samt indfri lokale forventninger ved etablering af ventilationsanlæg og -systemer til sådanne rum.denne vejledning kan derfor heller ikke betragtes som komplet dækkende for emnet. Vejledningen skal alene ses som et supplement til gældende standarder, regler og anvisninger, som i forvejen foreligger fra relevante myndigheder. Målgruppen omfatter bredt alle interessenter med opgaver i og omkring operationsstuer, herunder hygiejneorganisationen, bygherre, rådgiver, leverandør, driftsorganisation for teknisk drift såvel som det kliniske driftspersonale. Vejledningen skal således understøtte forståelsen af det komplekse system, som påvirkes af såvel tekniske forhold som personalets adfærd. Med vejledningen ønsker FSD/FSTA, at krav til og design af ventilation til Operationsstuer og rum, hvor der sker invasive indgreb, bliver lettere tilgængeligt for de personer der planlægningsmæssigt, projekteringsmæssigt og driftsmæssigt arbejder med etablering og drift af operationsstuer. Vejledningen er desuden udarbejdet med emner, der i dagligdagen kan være til gavn for de personalegrupper, som har deres arbejde i de respektive områder. 5

6 2.1 BAGGRUND Med henblik på at reducere antallet af postoperative sårinfektioner, skal operationsstuer være af en høj hygiejnisk standard. Høj hygiejnisk standard fordrer etablering af et kontrolleret miljø, som sikrer passende lave mikrobiologiske niveauer. Derudover etableres foranstaltninger, som bryder mulige smitteveje. For at opnå en god hygiejnisk standard skal samtlige angivne smitteveje være under kontrol. Formålet med nærværende vejledning er alene relateret til den luftbårne smitte. Dvs. de smitteveje som har luften som bærer af smitte. Der er i vejledningen særligt fokus på de ventilationstekniske tiltag, der kan sikre, at luftstrømmen mod operationssår og operationsinstrumenter holdes på et passende lavt niveau. Vejledning i tiltag, som bidrager til god hygiejnisk standard, men som ikke direkte er relateret til ventilationsmæssige tiltag såsom beklædning, adfærd, rummets udførelse og udformning, rengøring-, oprensning-, desinfektion- og sterilisations metoder findes i supplerende litteratur. Nærværende vejledning vedrører de ventilationsmæssige forhold i selve operationstuen. Denne vejledning behandler ikke krav til ventilation i tilstødende rum ud over differenstryk mellem lokalerne. 2.2 UDVALGTE PRIMÆRE KILDER FOR OMRÅDET For ventilationsanlæg, der betjener en op-stue findes der en omfattende mængde af regelsæt, standarder og retningsliner. I det efterfølgende er listet nogle få heraf, som er meget vigtige at kende til. I bilag findes en mere omfattende liste, som dog stadig ikke må betragtes som komplet. Statens Serum Institut udgiver en række Nationale Infektionshygiejniske Retningslinjer, i det efterfølgende benævnt NIR, hvoraf følgende er særligt relevante: NIR om nybygning og renovering i sundhedssektoren NIR om operativ infektionsprofylakse. (i høring 2. maj-5. juni 2014, se Serien af NIR udgør et nationalt enstrenget, frit tilgængeligt og direkte anvendeligt system af retningslinjer på det infektionshygiejniske område. Målgruppen er primært lokale infektionshygiejniske enheder, 6

7 øvrige infektionshygiejniske eksperter samt sundhedspersonale, der arbejder med infektionshygiejniske problemstillinger. NIR vil afløse serien af infektionshygiejniske standarder (2451-serien), der blev udarbejdet i et samarbejde mellem Dansk Standard, SSI og en række faglige eksperter i perioden En række af disse er revideret og udgivet i perioden Dette gælder dog ikke DS :2003; Krav til indkøb og vedligehold af teknisk og medicinsk-teknisk udstyr. Ventilationsrelevante dele af denne er inkorporeret i NIR om nybygning og renovering i sundhedssektoren, NIR om perioperativ forebyggelse samt dette kompendium fra FSD/FSTA. Institut for Kvalitet og Akkreditering i Sundhedsvæsenet; IKAS, skal sikre en upartisk vurdering af det danske sundhedsvæsens forudsætninger for at levere ydelser af høj kvalitet. Vurderingen baseres på offentliggjorte kriterier, udarbejdet i samarbejde med sundhedsvæsenets parter og interessenter. Konkret udvikler og driver IKAS Den Danske Kvalitetsmodel; DDKM. DDKM skal gennem akkrediteringsstandarder understøtte kvalitetsudviklingen i det danske sundhedsvæsen. Den skal desuden, gennem en uafhængig vurdering af opfyldelsesgraden af standarderne, evaluere og synliggøre indsatsen. Med den uafhængige vurdering stimuleres læring i sundhedsvæsenet samtidigt med, at sundhedsvæsenets ledere ansvarliggøres over for opdragsgiverne og offentligheden. DDKM skal sikre løbende udvikling af kvaliteten i alle offentligt finansierede sundhedsydelser skabe bedre og mere sammenhængede patientforløb forebygge fejl og utilsigtede hændelser i sundhedsvæsenet DDKM for sygehuse er en del af den nationale strategi for kvalitetsudvikling i sundhedsvæsenet og indeholder en række kvalitetsstandarder, som udgør rammerne for arbejdet med kvalitet. Særligt relevante for denne publikation er de organisatoriske standarder: Bygningers og lokalers egnethed Tekniske forsyninger Svigt af patientkritiske tekniske forsyninger 7

8 DDKM gælder for alle offentlige sygehuse samt privathospitaler af en vis størrelse, der har indgået aftale om det udvidede frie sygehusvalg. DDKM udstikker rammerne for, hvordan de enkelte hospitaler/regioner skal opbygge deres kvalitetssystem, og det vil være disse regionale/lokale retningslinjer, der vil være gældende i de enkelte byggeprojekter. Af øvrig relevant litteratur kan nævnes: Bygningsreglementet DS 447 Ventilation i bygninger Mekaniske, hybride og naturlige ventilationssystemer DS Commissioning-processen til bygninger - Installationer i nybyggeri og større ombygninger Ventilation på operationsstuer en medicinalteknisk vurdering 3 PROJEKTERING I sundhedsvæsenet foretages mange forskellige typer af invasive indgreb fra fjernelse af små gevækster på huden til indsættelse af fremmedlegemer og transplantation af organer. Udviklingen har desuden gjort det muligt, uden for operationsafdelingen, at udføre indgreb via kikkertinstrumenter og katetre. Luftkvaliteten har ikke samme betydning for risikoen for sårinfektion ved de forskellige typer indgreb, men der kan opstilles nogle hovedkategorier. Nedenstående tabel definerer de tekniske forhold og kravene til luftens kvalitet, i forhold til den planlagte aktivitet på stuen, og kan anvendes i forbindelse med projektering. 8

9 (1) Kim koncentration er vejledende værdier fra SSI. Disse vil ikke nødvendigvis være opfyldt ved anvendelse af de anbefalede minimumsluftmængder. Det vil altid være nødvendigt at udføre en konkret ventilationskalkulation for det enkelte projekt. Her indgår analyse af alle beladstningskilder som vigtige input. 9

10 3.1 DEFINITIONER Type: Entydig betegnelse for rumtyperne, som bliver anvendt i hele vejledningen Vejledende EU-renrumsklasse: Den EU renrumsklasse, der har de samme krav, som er stillet i denne vejledning. Eventuelle skærpende krav som måtte være til den pågældende EU renrumsklasse er ikke en del af denne vejledning. Dimensionsgivende krav til arbejdsmiljø og indeklima: Vejledende antal personer, som kan opholde sig i OP-rummet, i forhold til indeklima og arbejdsmiljø. Antallet er angivet som et interval, da det faktiske antal bør fastlægges af bygherre og brugerne i hvert individuelle tilfælde. Maksimalt kimtal under operation i kritisk zone: Grænseværdi for det maksimale antal smittebærende partikler pr. m³ luft i det kritiske område omkring operationslejet. På grund af tidsperspektivet i måling af kimtal anvendes ofte en måling af antallet af partikler over 0,5 μm; potentielle kimbærer. Kimtallet kan estimeres herud. Se tabel 2. Kontrolgrænse for antal partikler >0,5 μm pr. m³: Kontrolgrænsen refererer til kimtallet, da partikler på 0,5 μm er den mindste størrelse, hvorpå der teoretisk kan sidde kim/bakteriekolonier. Andelen af partikler over 0,5 μm der bærer kim antages at være konstant. Mindste volumenstrøm total: Den totale ventilerede luftmængde i lokalet, det vil sige udeluft + eventuelt recirkuleret luft. Denne parameter er relevant, da det er denne luftmængde der bliver filtreret, og dermed skal anvendes når partikel koncentrationen skal beregnes. Den ventilerede volumenstrøm skal altid dimensioneres ud fra den interne belastning (personer) og de krævede renhedskrav. 10

11 Mindste volumenstrøm udeluft: Den ventilerede luftmængde i lokalet, som erstattes med udeluft. Denne luftmængde er relevant i forbindelse med beregningen af koncentrationen af CO 2 og andre ikke filtrerbare gasser for at opretholde godt arbejdsklima. Anbefalet nettoareal af OP-stue: De anbefalede arealer tager højde for en fleksibel operationsstue. Arealerne kan godt være mindre, hvis stuens funktion specialiceres. Overtryk i forhold til mindre rene områder: Overtryk i OP stuerne i type 3, 4 og 5 skal etableres for, at sikre mod kontaminering ved lækage til tilstødende zoner. Overtrykket på Pa er angivet ved en stationær tilstand, hvor døre og sluser er lukkede. Dette relativt høje overtryk, i denne situation, skal sikre et konstant overtryk, ved de fluktuationer, der forekommer i differenstrykket under normal drift. Overtryk kan være uhensigtsmæssigt ved visse typer luftbåren smitte. Ved operation på patienter, hvor der er risiko for spredning af luftbåren smitte, beslutter klinikere og hygiejneorganisation, hvilken operationsstue/-afdeling operationen kan foregå på. Anbefalet slutfilter: I denne anbefaling, er der indarbejdet en vis sikkerhed, da renhedskravene ofte kan overholdes med en ringere filterklasse. Sikkerheden er indarbejdet i filteret, så mindre fejl i ventilationssystemet ikke øjeblikkeligt resulterer i et uacceptabelt højt kim tal, og dermed en potentiel farlig situation. Ventilationstekniske definitioner: Figur 1, Illustration og forklaring af forskellige ventilationstekniske termer. 11

12 Udeluft: Ventilationsluft på indblæsningssiden før ventilationsanlægget Afkastluft: Ventilationsluft på udsugningssiden efter ventilationsanlægget. Tilluft: Ventilationsluft der blæses ind i et rum. Fraluft: Ventilationsluft der suges ud fra et rum. Recirkulationsluft: Ventilationsluft, som tilføres samme rum som det er suget ud fra. Dette gøres for at filtrere og/eller temperaturregulere rumluften. Omluft: Ventilationsluft, som suges ud fra et rum, og tilføres et andet rum. Dette kan ske kontrolleret ved hjælp af et blandekammer i et centralt placeret ventilationsanlæg, eller ukontrolleret som lækage i et centralt placeret ventilationsanlæg. Primærluft: Den til rummet tilførte luftmængde eksklusiv eventuel recirkulationsluft. Infiltration: Ikke kontrolleret udeluft, som strømmer udefra ind igennem klimaskærmen. Eksfiltration: Ikke kontrolleret rumluft, som strømmer fra rummet ud igennem klimaskærmen. 3.2 LUFTSKIFTER De i tabel 1 angivne luftmængder er kun vejledende, og er ingen garanti for, at indeklima- og renhedskrav er overholdt. Under projekteringen bør det angives hvilken forureningsbelastning operationsstuen skal overholde kravene ved til henholdsvist type 3, 4 og 5. 12

13 3.3 ZONEOPDELING AF RUM Det kan i mange sammenhænge være fornuftigt at opdele rummet i zoner med forskellige renhedskrav afhængig af aktiviteten: Kritisk zone Support zone Zoneopdeling forudsætter, at der anvendes LAF-ventilation (Laminar Air Flow), da rummet ikke kan opdeles i forskellige ventilationszoner med almindelig opblandingsventilation. I den kritiske zone foregår den kritiske del af operationsprocessen hvor påvirkning af patienten kan få kritiske konsekvenser her vil normalt kun det nødvendige antal personer og sterilt udstyr være til stede. I support zonen må højere niveau af f.eks. bakterier forventes. Størrelsen af LAFet anlæg tilpasses den enkelte situation, og bør laves, så der kan anvendes standard filter størrelser. 3.4 OPRENSNING Filtreringen, luftskiftet og ventilationseffektiviteten skal sikre, at de opstillede krav til partikel og CFU koncentration overholdes. Oprensningstiden defineres som den tid det tager, at fortynde koncentrationen af partikler ned til et acceptabelt niveau. Acceptkriterierne for koncentrationen i rummene er normalt 10 % af start-koncentrationen ved type 3 rum og 1 % af startkoncetrationen ved type 4 og 5 rum. Dette kan eftervises ved beregning og måling, Den vejledende maksimale oprensningstid for en operationsstue i type 3, 4 og 5 bør maksimalt være 20 min. Oprensningstiden bør eftervises ved målinger. Ovenstående formel er afbilledet på figur 2 for både type 3, 4, 5 rum med forskellig ventilationseffektivitet. Heraf ses det, at ventilationseffektivitetens betydning for oprensningstiden er meget lille i forhold til den specifikke volumenstrøm. 13

14 Figur 2, Oprensningstid som funktion af specifik volumenstrøm i henhold til ovenstående formel. En god placering af indblæsningsarmaturerne er vigtigt for at opnå en god ventilationseffektivitet. Koordinering af indblæsningsarmaturernes placering i forhold til øvrigt udstyr er nødvendig, for at sikre en god opblanding i rummet. Efter udførelse skal måling af ventilationseffektivitet/oprensningstid eller røgforsøg udføres, for at eftervise, at det projekterede lever op til kravspecifikationen til oprensningstid. 3.5 FILTRERING Filterplacering skal vælges, så funktionen sikres. Samtidigt skal det sikres at kontrol og udskiftning let kan udføres. Yderligere informationer om filtre fremgår af bilag VENTILATIONSPRINCIPPER Opblandingsventilation: Luften tilføres ved loft (udenfor opholdszonen) med en relativ høj hastighed, typisk 4 m/s. Den høje hastighed medfører at der medrives rumluft, hvorved der sker en opblanding. Dermed opnår man en nogenlunde ensartet fordeling af forurening og temperatur i rummet. Udsugning sker normalt ved gulv og loft. Fortrængningsventilation (anvendes normalt ikke i denne type rum): Her tilføres luften ved gulv med lav hastighed, typisk 0,4 m/s, og en undertemperatur. Med udsugning placeret ved loft forstærkes de opadgående luftstrømme forårsaget af termisk påvirkning fra lamper, mennesker og andet. 14

15 UDF Uni Directional Flow også kaldet LAF (Laminar Air Flow): Her tilføres luften med lav hastighed over en stor flade typisk en del af loftet. Indblæsningshastigheden vil typisk være ca. 0,3-0,5 m/s. Den tilførte luft er HEPA-filtreret og dermed vil rumluften have en meget stor renhed så længe der ikke er tilført forurening til området. Ønsket er, at alle forureninger fanges af luftstrømmen og transporteres bort fra den kritiske zone, som holdes beskyttet af den rene luft. Den nødvendige hastighed af den tilførte luft vil være afhængig af mange faktorer: Afstand fra filter til det kritiske område Varmekilder i luftstrømmen Fysiske hindringer i luftens bane Lufttilførslen kan ske vertikal eller horisontalt. Typisk dog vertikal, da horisontalt flow kan være vanskelig at indarbejde i et lokale med mange personer. Det er afgørende. at der ikke er væsentlige hindringer i luftens bane eller tilførsel af forurening før luften når det område, som skal beskyttes. Der kan med fordel gennemføres CFD-simulering under projektering for at optimere forholdene. Den nødvendige lufthastighed skal verificeres f.eks, med røgstudier under simulerede operationer. Dokumentation af luftflow foretages i form af videooptagelser. Punktsug Der etableres punktsug på alle operationsstuer. Disse bør føres direkte til det fri, med afkast over tag, da luften kan indeholde skadelige partikler og gasser fra operationsprocesser. 3.7 VARMEGENVINDINGSMETODE Det skal sikres, at der ikke overføres smitte fra den udsugede luft til den indblæste. Ventilationen kan udføres fælles for flere operationsstuer eller et separat anlæg pr. operationsstue. Med et separat ventilationsanlæg pr. operationsstue, vil en eventuel tilbageførsel af en rest af smitte ikke være kritisk, da koncentrationen af samme smittekim er betydende større på operationsstuen. Derfor gælder nedenstående betragtninger i de tilfælde, hvor smitte kan tilføres et rum, hvorfra det ikke kom/ikke allerede findes. 15

16 Der findes mange varmegenvindingsmetoder, hvoraf de mest relevante er: 1. Roterende varmeveksler 2. Modstrømsveksler 3. Væskekoblede varme/køleflade Derudover findes der flere andre varianter og systemer som omtales til sidst i vejledningen Roterende varmevekslere og modstrømsvekslere er i stand til at opfylde Bygningsreglementets krav til varmegenvinding. Hvor de hygiejniske og personsikkerhedsmæssige forhold fordrer højst mulig sikkerhed, kan der anvendes væskekoblede varme/køleflader da Bygningsreglementets krav til energieffektivitet ikke gælder i dette tilfælde. Roterende veksler skal installeres og drives særligt omhyggeligt. Forkert installation kan give en stor grad af omluft; tilbageført udsugningsluft. Dette kan undgås ved, at der under alle driftsforhold er sikret undertryk i afkast og overtryk i indblæsning. Kræves der absolut sikkerhed bør der, som varmegenvinding, vælges en løsning med væskekoblede batterier. 3.8 TEMPERATUR OG FUGTFORHOLD Indblæsningstemperaturen bør styres efter rumlufttemperaturen, og denne kan måles i udsugningskanalen. Det anbefales, at gøre rumtemperatur brugerstyret, da temperaturkravene er varierende fra operation til operation. Temperaturkravet kan variere fra C. I tilfælde af LAF ventilation, kan der, med fordel, laves to temperaturzoner. Luftfugtigheden bør holdes under 70 % RH af hensyn til sterilvarer. 3.9 REGULERING; ANBEFALINGER VED DE FORSKEL- LIGE RUMTYPER Det anbefales at anvende en så simpel regulering som muligt. Herved reduceres fejlkilderne og fejlfindingen gøres så let som muligt. For anlæg som betjener type 3, 4 og 5 rum, bør der installeres kontrollamper, som er synlige i det rum ventilationsanlægget betjener. Disse kontrollamper kan anvendes som en del af personalets kontrol før og under operation. 16

17 3.10 LYD Der er ikke direkte bestemmelser for støjniveauet fra installationer i rum med invasive indgreb. Bygningsreglementet angiver, at der skal opstilles projektspecifikke krav for det akustiske indeklima i hvert enkelt tilfælde. Det anbefales, at lydtrykniveauet, som stammer fra ventilationsstøj, i rummet ikke overstiger 40 db(a) for traditionelle ventilationsanlæg, og 48 db(a) for LAF anlæg. Efterklangstiden bør ikke være længere end 0,9 s ENERGIFORBRUG Ventilationsanlæg i rum med invasive indgreb kan opdeles i henholdsvis komfortanlæg og procesanlæg. Komfortanlæg konditionerer rummene termisk og atmosfærisk, typisk så temperatur og CO2 krav overholdes. Dette svarer til mindste volumenstrøm udeluft i Tabel 1. Typiske ventilationssystemer som kategoriseres som procesanlæg vil være udsugning fra værktøj, stinkskab og punktudsugning. Rumventilation der har til formål at filtrere luften, så de kliniske renhedskrav kan overholdes defineres også som procesventilation. Denne luftmængde er i Tabel 1 defineret som forskellen mellem mindste volumenstrøm total og mindste volumenstrøm udeluft. Komfortventilation er underlagt energibestemmelserne i bygningsreglementet, ligesom det skal medregnes i energirammen på lige fod med alle andre komfortanlæg. Procesanlæggene skal ikke overholde kravene til SEL værdier, ligesom de heller ikke skal medregnes i energirammen. Både for energiforbrug og hygiejne anbefales det, at operationsstuer laves så tætte som muligt i forhold til omkringliggende rum. Dette gør, at der skal bruges mindre energi på at holde det vejledende overtryk i rummene. Tætheden af rummene kan kontrolleres ved en trykprøvning, hvor den vejledende lækage maksimalt bør være 1,5 l/s/m² ved 50 Pa differenstryk COMMISSIONING Et commissioning forløb gennemføres for at sikre kvaliteten i forbindelse med ombygninger og optimeringer af eksisterende anlæg og faciliteter. Commissioning er således en styret arbejdsproces, som tilsikrer at aflevering, overlevering og ibrugtagning finder sted som planlagt og forventet. Omfanget af commissioning afhænger bl.a. af projektets størrelse og kompleksitet. 17

18 Ideelt set, og for at få det bedste udbytte, bør commissioning processen følge hele projektets løbetid, fra idefasen til den endelige aflevering. Commissioning kan herved aflevere et gennemtestet projekt således, at sikker drift kan ske fra ibrugtagning. Derfor bør processen omkring commissioning forløbe fra start af projektering til afslutning af projektets gennemførelse forud for aflevering og ibrugtagning. Fase for fase og løbende i processen stilles spørgsmålet Hvad skal gøres i den aktuelle fase for at hindre, at noget går galt? Commissioning processen: I commissioning processen skal der fokuseres på alle relevante krav til præstationer, funktionalitet og effektivitet for at forebygge graverende fejl lige før aflevering. Således skabes der tryghed hos bygherren og bruger og dermed også rådgiver og entreprenør. Det betyder: Under programmeringen (i idefasen) tilsikrer commissioning processen, at krav og ønsker gøres målbare, og at omfanget af krav svarer til projektbasis. Det efterfølgende forløb planlægges. Under projektering forud for udbud sikrer commissioning processen, at sikre en grundig koordinering på tværs af fagområde. gennemgang af projektmaterialet med henblik på at sikre, at projektet opfylder brugernes og driftpersonalets krav herunder evt. opstille fremtidige driftsscenarier. 18

19 anskueliggøre hvordan driftssituationen bliver under de forskellige scenarier, med oplysning om muligheder for overstyring og ændring af driftstilstand, også uden for normal brug. Synliggøre driftpersonalets behov for dokumentation af driftsforholdene (kvalitetsopfølgning). Anskueliggøre fremtidig drift og vedligehold, herunder hyppighed, adgangsforhold, tilgængelighed, særlige omkostninger mv. ved drift og vedligehold såvel som særlige kompetencekrav til driftpersonale. Fastlægge referencesystem og evt. TAG-nummerering i sammenhæng med organisationens eksisterende system. Planlægge opgaver omkring indregulering og aflevering, herunder rollefordeling mellem entreprenør, projekterende enhed commissioningleder. Fastlægge omfang af indregulering som entreprenøren skal foretage. Opstille krav til dokumentation, herunder tegningsmateriale, så de opfylder driftpersonalets fremtidige behov. Herved fastlægges relevante krav med omfang af egenkontrol, hvor driftsperspektiver er inddraget ved driftspersonalets involvering. Samtidig er entreprenørernes ydelser i commissioning forløbet tydeliggjort og lister med krav og tilhørende udfaldskrkav er udarbejdet. I det endelige projekt er det tillige sikret, at de valgte løsninger er regulerbare og kan opfylde den ønskede funktion. Under udførelsen inddrages entreprenørerne i en løbende dialog med særlig fokus på, at de valgte løsninger kan driftes og serviceres, ligesom det bl.a. sikres at den nødvendige dokumentation bliver leveret så indregulering og test kan planlægges. Forud for aflevering og ibrugtagning sikres det, at udførelse af test, undervisning og afprøvning gennemføres som planlagt og med tilstrækkelig kvalitet. Det kan anbefales, at commisioning processen aftales som en selvstændig ydelse ved siden af det egentlige projektforløb. Commissioning processen ledes af en commissioningleder (CM), som refererer til projektets styregruppe. Commissioning teamet består af entreprenører, rådgivere, byggeleder, driftspersonale og evt. andre brugere. Commissioning teamet planlægger og sikrer enighed om afleveringsforløbet, herunder undervisning, test, dokumentation og indreguleringer. 19

20 Typisk rollefordeling: Commissioningleder (Commissioning manager): Leder teamet og varetager korrespondance med projektets øvrige interessenter. Rådgiver/projekterende: Udarbejder omfang af nødvendige test, undervisning mv. og indarbejder disse i lister og planer. Byggeleder: Indarbejder de nødvendige test og undervisningsforløb i projektets tidsplan samt sikrer opfølgning på fremdriften Entreprenøren: Indarbejder testplaner og procedure for de stillede krav i de relevante planer og lister fra den projekterende. Driftspersonale/brugere: Deltager i kravspecifikation ligesom de deltager i projektreviews og afleveringer. Et commissioning forløb anvendes til at sikre kvaliteten i forbindelse med ombygninger og optimeringer af eksisterende anlæg og faciliteter DRIFT OG VEDLIGEHOLD Der udarbejdes retningslinier og instrukser i henhold til standarderne i DDKM og med baggrund i drifts- og vedligeholdelsesmaterialet der afleveres som en del af entreprenørernes ydelse (DS447 bør være opfyldt). Heri bør bl.a. indgå: Egenkontrol (brugerne) (dagligt): Driftsstatus anlæg (kører anlægget lampeindikering el.lign) Trykforhold (differenstryksmålere) Driftsstatus rum (er rummet intakt?) Periodeservice/-kontrol (driftspersonale) (ugentligt/månedligt/årligt): Filterkontrol (visuel/differenstryk) Funktionsafprøvning Alarmafprøvning Partikelmåling Service (leverandør/specialist) (halvårligt/årligt): Filterskift Ydelseskontrol Optimering 20

21 BILAG 1: KOMPONENTER 4.1 ARMATURTYPER Typisk anvendte armaturer i OP-stuer med opblandingsventilation er: Diffusor med lukket eller perforeret bundplade Velegnet til indblæsning af kold/afkølet luft. Indblæsningsmønstret kan ændres til 1-, 2-, 3- eller 4-vejs indblæsning. Denne armaturtype kan kombineres med indbygning af HEPA-filter. Rotationsdiffusor På grund af hvirveldannelsen og opblandingen med rumluft omkring armaturet bliver kastelængden ret kort og armaturet er derfor velegnet til rum med store luftskifter. Denne armaturtype kan kombineres med indbygning af HEPA-filter Armatur med justerbar bundplade Velegnet til lokaler hvor der både skal blæses ind med over- eller undertemperatur. Omstilling skal typisk ske elektrisk. Denne armaturtype kan ikke kombineres med indbygning ag HEPA-filter. Udsugningsarmatur Det anbefales at forsyne lavtsiddende udsugningsarmaturer med fintmasket net for at forhindre papir mv. i at blive suget ind. 4.2 FILTRE Grundfiltre (G1 G4) Grundfiltre benyttes primært som forfilter, hvor der forekommer væsentlig forurening af luften. Nogle af de mest karakteristiske data ved grundfiltre er: grundfiltre fremstilles typisk af syntetiske fibre, glasfiber eller metalvæv. grundfiltre leveres ofte som planfiltre, men kan forekomme som korte posefiltre filtreringen er mest effektiv for grovere partikler større end 4-5 μm lufthastigheden gennem filtrets frontareal bør maks. være 2,5 m/s, idet udskilningsgraden reduceres kraftigt ved større hastigheder. 21

22 Medium-/Finfiltre (M5 - F9) Finfiltre benyttes i de fleste ventilationsanlæg både til filtrering af udeluften og til beskyttelse af enkelte komponenter i anlægget. Nogle af de mest karakteristiske data for finfiltre er: finfiltre fremstilles almindeligvis af glasfibre eller syntetiske fibre god filtrering af partikler større end 0,1 μm lufthastigheden gennem filtrets frontareal bør ikke være højere end 2-3 m/s af hensyn til tryktabet Mikrofiltre (E10 - U17) Mikrofiltre benævnes EPA (Efficiency Particulate Airfilter) HEPA (High Efficiency Particulate Airfilter) og ULPA (Ultra Low Penetration Airfilter) Mikrofiltre benyttes primært, hvor der er høje krav til luftens renhed eller, hvor en specifik forurening kræver det. Nogle af de vigtigste data for mikrofiltre er: Mikrofiltre fremstilles af glasfibermedie med separatorer af papir, plast eller aluminium Filtreringen er meget effektiv over for partikler større end 0,01 μm Mikrofiltre skal lækagetestes efter montage eller filterskift, da selv små utætheder kan medføre, at den tiltænkte filtrering udebliver. Mikrofiltre bør altid beskyttes af et effektivt forfilter. f.eks. F7 eller bedre. Tabel 3 Vejledende tryktab over filtre i ventilationsanlæg 22

23 4.3 VARMEGENVINDING Roterende varmeveklser Carry over (kortslutning af udsuget luft til indblæsning) skal være mindre end 1 % under alle driftsforhold af hensyn til hygiejenkrav. Eftervisning kan ske med sporgas som angivet i standarden DS/EN 308. Kravet medfører, 1. at der skal være en renblæsningszone - ofte i størrelsen at der skal være større tryk i indblæsningen end udsugningen på den varme side/rumsiden af rotoren ofte i størrelsen 150 [Pa]. 3. at rotorens omdrejningstal skal begrænses, så rotoren tømmes tilstrækkeligt for udsuget luft i renblæsningszonen ofte i størrelsen 10 omdr. pr. minut. 4. at rotorens maksimale omdrejningstal skal reduceres proportionalt med flowet i indblæsningen (reduceret omdrejningstal nedsætter kun temperaturvirkningsgraden relativt lidt: 6-8 omdr./ minut giver måske 98 % af 20 omdr./minut). 23

24 Disse størrelser påvirker hver for sig størrelsen af carry over, hvorfor andre kombinationer af parametre også vil sikre en carry over på under 1 %. Carry over må ikke forveksles med lækage, som er et udtryk for den roterende vekslers tæthed og hermed effektivitet. Følgende kursive afsnit inklusiv tabel er uddrag fra de Nationale Infektionshygiejniske Retningslinjer NIR. Krav til roterende veksler med henblik på at forhindre omluft Omluft er udsuget luft, der tilføres andet rum. Herved kan smittestof overføres fra et rum til et andet. Intallationen: 1. Ved forkert installation kan omluft overføres på den indvendige side af veksleren. Her skal være størst tryk i indblæsningen. 2. Dette overtryk skal løbende overvåges via bygningsautomatikken (CTS). Der skal være en relativ højt klassificeret alarm. 3. Renblæsningen af rotorhjulet for udsuget luft, inden zonen for indblæst nås, skal sikres. Renblæsningszonens størrelse (vinkel) skal være tilstrækkelig stor. 4. Rotorhjulets vinkelhastighed skal reduceres i tilfælde af reduceret flow (hastighed i indblæst luft). Bygningsautomtikken skal automatisk reducere den maksimale vinkelhastighed proportionalt med flowet. 5. Overfladebelægningen må ikke begunstige vækst af mikroorganismer. Det skal noteres, at temperatur- og lugt-tilstandendene er meget ustabile, hvilket skønnes at umuliggøre/minimere mikro-vækst betydeligt. Veksleren er skiftevis er varm og kold for hver 3 sekunder (afhænger af vinkelhastigheden). Når der er frit vand / kondens tilstede er veksleren tilsvarende skiftevis våd og tør for hver 3 sekunder. Der skal ligeledes bemærkes, at de særligt vandabsorberende overflader bindes vandet som luftmolekyler og ikke frit vand (igen minimering risiko for mikro-vækst. 6. Filtre på udeluften (tilluften) og fraluften skal tilbageholde partikler, omfang mindst som svarende filterklasse F7. 7. Der skal være tilstrækkelig plads (tomsektioner eller anden mulighed) så inspektion, rengøring og filterskift kan foregå regelmæssigt. 8. Områder, hvor indblæsningsluften ønskes renere, forsynes med ekstra filtre efter rotorveksleren. Dette filter bør lækagetestes efter hver udskiftning. 9. Samme filter kan være med kultilslag, der fjerner moderat lugtforurening. 10. Hvor der er særlig høj infektionsrisiko skal F7 filtret i indblæsningen efter veksleren kunne skiftes til et HEPA-filter. 24

25 Driften: 1. Regelmæssig inspektion af rotorhjulet og dets omgivelser samt rengøring ved behov. 2. Teknisk vedligehold: udskiftning af dele i overensstemmelse med drift og vedligehold-manual. 3. Test af filtre ved måling af partikeltal i indblæst luft, sammenholdt med partikeltallet i udeluften. 4. Test af alarm for overtryk og reduceret maksimal vinkelhastighed ved reduceret indblæsningsflow. 5. Ovenstående skal løbende registreres. 25

26 BILAG 2: PARTIKLERS FALDHASTIGHED Partikler i luften vil have en tendens til at sedimentere på grund af partiklernes faldhastighed. Faldhastigheden afhænger af partiklens størrelse, form og densitet. For partikler med en densitet på 1 ton/m3 er faldhastigheden således: Partikeltype Partikeldiameter, µm Faldhastighed cm/sek Tid for at falde 1 m Dråbe sekunder Hudpartikel 10 0,5 3 minutter Svampespore 1 0,04 7 timer Hovedparten af de kritiske partikler herunder hud- og sårbakterier har en størrelse så de generelt set sedimenterer. Men uanset hvilket ventilationsprincip man anvender, er det afgørende, at man har fokus på forholdet mellem opadgående termiske luftstrømme og de gravitationsmæssige effekter med partiklers faldhastighed 26

27 BILAG 3: KONTROL AFLEVERING, IBRUGTAGNING OG DRIFT I forbindelse med aflevering og ibrugtagning af ventilationsanlæg til OP-stuer skal der foretages en kontrol af anlæggenes funktion og ydeevne. Normalt vil der ved afleveringen foreligge en afleveringsrapport fra entreprenøren, hvor luftmængder, trykforhold, lydforhold mv. er dokumenteret. Som supplement til de traditionelle målinger anbefales for OP-stuer følgende supplerende tests, som alle kan udføres i henhold til ISO og vil normalt omfatte: Rumtryk måling Eftervisning af at OP-stuen, med lukkede døre, har det ønskede rumtryk Målingen kan foretages med f.eks. et håndholdt differenstrykmanometer Måling af oprensningstid Eftervisning af ventilationseffektiviteten Dosering af partikler til rummet i en hvilesituation og kontrol af, hvor hurtigt hviletilstanden igen er oprettet Lækagetest af HEPA-filtre Eftervisning af HEPA-filtrenes tæthed (ingen lækage) Filtrene påføres en belastning og den maksimale lækage kontrolleres Eftervisning af luftbevægelser i rum eller under LAF Eftervisning af luftbevægelser i rummet specielt i den kritiske zone Eftervisning af downflow et under eventuelt LAF-modulet Kontrol af lufthastigheder umiddelbart under LAF-modulet Kontrol af, at luftagtigheden er høj nok til at beskytte det kritiske område Eftervises ved hjælp af hastighedsmåler og evt. røg, som kan dokumentere luftbevægelserne Målinger bør foretages under simulerede driftsforhold, hvor personer og udstyr er i aktivitet 27

28 Partikelmålinger Eftervisning af renhed at rest og in operation Kontrol af partikeltal med hensyn renhedsklassifikation B, C eller D Eftervises ved hjælp af optisk partikeltæller Mikrobiologiske målinger Mikrobiologiske målinger foretages for at sikre, at kombinationen af ventilation, arbejdsdragt og adfærd bevirker, at kravene for luftkvalitet er opfyldt. Der måles i forbindelse med om- og nybygning ophobning af postoperative sårinfektioner væsentlige ændringer i adfærd, påklædning samt opstilling af afskærmning Måling foretages under igangværende aktivitet (operation, opdækning). Noter omstændighederne: Antal personer, hvilken type arbejdsdragt, der anvendes, samt antal døråbninger o.l. For aktiv måling gælder: Måling foretages med slitsampler 50 cm fra operationssåret/på instrumentbordet, ca. 1,2 m over gulvhøjde. Under opdækning foretages måling ved opdækningsbordet. For operationer: Så vidt muligt operationer med knivtid > 45 min., således at 3-4 målinger kan udføres under samme operation. Måleperioder 10 min, med flow 1 m3/10 min anbefales. Ved længere måleperiode er der risiko for udtørring af agarpladen. For passiv måling (sedimentation) gælder: Egnede agarplader (diameter 14 cm) placeres på strategiske steder i periferien af operationsstuen. Ved måling i rum med direkte forbindelse til stuer type 4 og 5, fx i korridor, placeres pladerne i områder med høj aktivitet. Sædvanligvis foretages ikke mikrobiologiske målinger på tom stue og/ eller ved ibrugtagning, hvis følgende er opfyldt: Tekniske parametre er tilfredsstillende. Installationskontrol og kontrol af indlækning er udført ved partikelmåling på tomt rum og viser tilfredsstillende resultater. Inden ibrugtagning er det dokumenteret, at ventilationssystemet er tilfredsstillende rengjort. 28

29 Eftervisning af den mikrobiologiske forurening i lokalet Kontrol af antallet af CFU (colony forming units) pr m3 rumluft Eftervises ved prøvetagning med slitsampler, som opsamler mikroorganismer på en agarplade Rutinemæssig driftskontrol For at eftervise at forholdene stadig er som ved ibrugtagningen bør der mindst en gang pr år foretages en kontrol at de væsentligste parametre. Kontrollen bør omfatte følgende emner: Rumtryk Lækagetest af HEPA-fitlre Partikelmålinger Følgende er en oversigt over relevante mikrobiologiske målinger på operationsstuer og tilstødende rum. 29

30 LITTERATURLISTE KILDE Department of Health Estates & Facilities Division, UK. Health Building Note 00-09: Infection control in the built environment.; Weber DJ, Rutala W a. Understanding and preventing transmission of healthcare-associated pathogens due to the contaminated hospital environment. Infection Control and Hospital Epidemiology. 2013;34(5): Zimring C, Denham ME, Jacob JT, et al. Evidence-based design of healthcare facilities: opportunities for research and practice in infection prevention. Infection Control and Hospital Epidemiology. 2013;34(5): Statens Serum Institut. Nationale Infektionshygiejniske Retningslinjer om håndhygiejne.; Department of Health Estates and Facilities Division. Health Building Note Part B : Walls and ceilings.; Tammelin A, Ljungqvist B, Reinmüller B. Single-use surgical clothing system for reduction of airborne bacteria in the operating room. Journal of Hospital Infection. 2013;84: NATIONALE INFEKTIONSHYGIEJNISKE RETNINGSLINJER Statens Serum Institut, Central Enhed for Infektionshygiejne, 1. udgave 2013 Tran K, Cimon K, Severn M, Pessoa-Silva CL, Conly J. Aerosol generating procedures and risk of transmission of acute respiratory infections to healthcare workers: A systematic review. PloS one. 2012;7(4):1 8. Sundhedsstyrelsen. Danske Lægemiddelstandarder ; 2012: Swedish Standards Institute. SIS-TS 39:2012 Mikrobiologisk renhet i operationsrum - Förebyggande av luftburen smitta - Vågledning och grundlåggande krav Mehtar S. IFIC Construction, Design and Renovation Interest Group. Ventilation to prevent airborne transmission of infection in a healthcare facility.; 2012:1 5. ÅRSTAL

31 IKAS. Den Danske Kvalitetsmodel for sygehuse.; 2012:Standard Macve JC, Weinbren MJ. Dirty utility room design and aerosolization of organisms. Journal of Hospital Infection. 2012;81(1):66 7. Gastmeier P, Breier A-C, Brandt C. Influence of laminar airflow on prosthetic joint infections: A systematic review. Journal of Hospital Infection. 2012;81: Statens Serum Institut. Nationale Infektionshygiejniske Retningslinjer om behandling af patienter med smitsomme sygdomme, herunder isolation.; Dansk Standard. DS Styring af infektionshygiejne i sundhedssektoren: Krav til rengøring.; Dansk Standard. DS Styring af infektionshygiejne i sundhedssektoren: Krav til vask og håndtering af tekstiler til flergangsbrug.; Chen C, Zhao B, Yang X, Li Y. Role of two-way airflow owing to temperature difference in severe acute respiratory syndrome transmission: Revisiting the largest nosocomial severe acute respiratory syndrome outbreak in Hong Kong. Journal of the Royal Society Interface. 2011;8: Sundhedsstyrelsen. Ventilation på operationsstuer - en medicinsk teknologivurdering.; MacCannell T, Umscheid C a, Agarwal RK, Lee I, Kuntz G, Stevenson KB. Guideline for the prevention and control of norovirus gastroenteritis outbreaks in healthcare settings. Infection Control and Hospital Epidemiology. 2011;32(10): Breier A-C, Brandt C, Sohr D, Geffers C, Gastmeier P. Laminar airflow ceiling size: No impact on infection rates following hip and knee prosthesis. Infection Control and Hospital Epidemiology. 2011;32(11): AIA. The American Institute of Architects: Guidelines for design and construction of hospital and health care facilities.; 2010 Svensk Förening för Vårdhygien. Byggenskap och Vårdhygien. Vårdhygieniska aspekter vid ny- och ombyggnation samt renovering av vårdlokaler. 2. upplaga.;

32 Wong BCK, Lee N, Li Y, et al. Possible role of aerosol transmission in a hospital outbreak of influenza. Clinical Infectious Diseases. 2010;51(10): Best EL, Fawley WN, Parnell P, Wilcox MH. The potential for airborne dispersal of Clostridium difficile from symptomatic patients. Clinical Infectious Diseases. 2010;50(11): Popp W, Bartley J, Ransjö U, Hoffman P. IFIC Construction, Design and Renovation Interest Group. Design of af surgery block.; Atkinson J, Chartier Y, Pessoa-silva CL, Jensen P, Li Y. Natural Ventilation for Infection Control in Health-Care Settings. World Health Organization; Dansk Standard. DS Styring af infektionshygiejne i sundhedssektoren Del 13 : Krav til genbehandling af steriliserbart medicinsk udstyr. Infection control in the health care sector Part 13 : Requirements for retreatment of sterilizable medical equipment DS Nielsen P V. Control of airborne infectious diseases in ventilated spaces Control of airborne infectious diseases in ventilated spaces. Journal of the Royal Society Interface. 2009;(September). Assadian O, Kuelpmann R, Zhumadilova A, Kobayashi H, Heidecke C-D, Kramer A. Protective effect of HEPA-filtered operating room air ventilation with or without laminar airflow on surgical site infections. Annals of Surgery. 2009;250(4):659. Erichsen & Horgen A/S, Forhold tilknyttet bruk av roterende gjenvinnere i skoler Brandt C, Hott U, Sohr D, Daschner F, Gastmeier P, Rüden H. Operating room ventilation with laminar airflow shows no protective effect on the surgical site infection rate in orthopedic and abdominal surgery. Annals of Surgery. 2008;248(5): National Collaborating Centre for Women s and Children s Health. Surgical site infection. Prevention and treatment of surgical site infection Nordenadler J. Skyddsventilation i operationsrum. Inblåsningssystem med parallelströmning

33 Yu IT, Xie ZH, Tsoi KK, et al. Why did outbreaks of severe acute respiratory syndrome occur in some hospital wards but not in others? Clinical Infectious Diseases. 2007;44: Department of Health Estates & Facilities Division. Heating and ventilation systems. Health Technical Memorandum 03-01: Specialised ventilation for healthcare premises. Part A: Design and validation.; Department of Health Estates & Facilities Division. Heating and ventilation systems. Health Technical Memorandum 03-01: Specialised ventilation for healthcare premises. Part B - Operational management.; Brady RR, Fraser SF, Dunlop MG, Paterson-Brown S, Gibb AP. Bacterial contamination of mobile communication devices in the operative environment. Journal of Hospital Infection. 2007;66(4): Christensen TE, Jørgensen JS, Kolmos HJ. Rengøringens betydning for forek... Ugeskrift for Læger. 2007;165(49): Sundhedsstyrelsen. Håndbog om sundhedsberedskab udgave.; Miller KM, ed. Planning, Design, And Construction of Health Care Facilities. Joint Commission Resources; Eckmanns T, Rüden H, Gastmeier P. The influence of high-efficiency particulate air filtration on mortality and fungal infection among highly immunosuppressed patients: a systematic review. Journal of Infectious Diseases. 2006;193(10): Fläktwoods (SEMCO incorporated), Results of Cross-Contamination Testing on Desiccants Centers for Disease Control and Prevention. Guidelines for preventing the transmission of Mycobacterium tuberculosis in health-care settings, Morbidity and Mortality Weekly Report. 2005;54(RR-17). Malvik B, Haugen EN, Mathisen HM. Roterende varmegjenvinnere i sykehus - overføring av forurensninger.; Barker J, Jones M V. The potential spread of infection caused by aerosol contamination of surfaces after flushing a domestic toilet. Journal of Applied Microbiology. 2005;99(2):

34 ROTERENDE VARMEGJENVINNERE I SYKEHUS - overføring av forurensninger, SINTEF Statens Serum Institut. Råd og anvisninger om desinfektion i sundhedssektoren. 7. udgave.; Yu ITS, Li Y, Wong TW, et al. Evidence of airborne transmission of the Severe Acute Respiratory Syndrome Virus. New England Journal of Medicine. 2004;350: Hassoun A, Velozzi E, Smith M. Colonization of personal digital assistants carried by healthcare professionals. Infection Control and Hospital Epidemiology. 2004;25: NHS Estates. HBN 26 Facilities for surgical procedures: Volume 1.; Beggs CB. The airborne transmission of infection in hospital buildings: Fact or fiction? Indoor and Built Environment. 2003;12(1-2):9 18. HICPAC/CDC. Guidelines for Environmental Infection control in Health- Care Facilities. Recommendations of CDC and Healthcare Infection Control Practices Advisory Committee (HICPAC), USA; Lutz BD, Jin J, Rinaldi MG, Wickes BL, Huycke MM. Outbreak of invasive Aspergillus infection in surgical patients, associated with a contaminated air-handling system Standards Australia/Standards New Zealand. AS/NZS 4187:2003 Cleaning, disinfecting and sterilizing reusable medical and surgical instruments and equipment, and maintenance of associated environments in health care facilities.; Dansk Standard. DS Styring af infektionshygiejne i sundhedssektoren: Krav til perioperativ profylakse.; Menzies D, Fanning A, Yuan L, FitzGerald JM, The Canadian Collaborative Group in Nosocomial Transmission of TB. Hospital ventilation and risk for tuberculous infection in Canadian health care workers. Annals of Internal Medicine. 2000;133: Kumari DNP, Haji TC, Keer V, Hawkey PM, Duncanson V, Flower E. Ventilation grilles as a potential source of methicillin-resistant Staphylococcus aureus causing an outbreak in an orthopaedic ward at a district general hospital. Journal of Hospital Infection. 1998;39:

35 FSD (Foreningen af Sygehusmaskinmestre i Danmark). Ventilation på operationsstuer Återföring av föroreningar i roterende väremväxlare en litteraturstudie/kunskapsöversikt, Svein Ruud, Sveriges Provnings- och Forskningsinstitut Whyte W, Hambraeus A, Laurell G, Hoborn J. The relative importance of the routes and sources of wound contamination during general surgery. II. Airborne. Journal of Hospital Infection. 1992;22(1): Whyte W, Hambraeus A, Laurell G, Hoborn J. The relative importance of routes and sources of wound contamination during general surgery. I. Non-airborne. Journal of Hospital Infection. 1991;18(2): Lidwell OM, Lowbury EJL, Whyte W, Blowers R, Stanley SJ, Lowe D. Effect of ultraclean air in operating rooms on deep sepsis in the joint after total hip or knee replacement: A randomized study. British Medical Journal. 1982;285:

Ventilation i rum med invasive indgreb, herunder OP-stuer Vejledende retningslinjer Høringsudgave, Fortryk 13.05.2014

Ventilation i rum med invasive indgreb, herunder OP-stuer Vejledende retningslinjer Høringsudgave, Fortryk 13.05.2014 Ventilation i rum med invasive indgreb, herunder OP-stuer Vejledende retningslinjer Høringsudgave, Fortryk 13.05.2014 Indhold 1 Forord... 3 2 Indledning... 5 2.1 Baggrund... 5 2.2 Udvalgte primære kilder

Læs mere

Metodebeskrivelse for Kontrol af operationsstuer i Vestsjællands Amt

Metodebeskrivelse for Kontrol af operationsstuer i Vestsjællands Amt Kontrol af operationsstuer Metodebeskrivelse for Kontrol af operationsstuer i Vestsjællands Amt Udført for: Region Sjælland Sygehus Vest Fælledvej 1 DK-4200 Slagelse Udgivelsesdato : 31. oktober 2007 Projekt

Læs mere

Aarhus Universitetshospital Skejby. Ventilation og CTS på højisolationsstuer. Bygning U P R O J E K T F O R S L A G. [Document type]

Aarhus Universitetshospital Skejby. Ventilation og CTS på højisolationsstuer. Bygning U P R O J E K T F O R S L A G. [Document type] P R O J E K T F O R S L A G Aarhus Universitetshospital Skejby Ventilation og CTS på højisolationsstuer Bygning U [Document type] 2016-12-19 Skanderborgvej 190 8260 Viby J Danmark Tlf.: +45 88 19 10 10

Læs mere

FSTA 2014 Ventilation af operationsstuer Recirkulation og rotorvekslere Hans Theil

FSTA 2014 Ventilation af operationsstuer Recirkulation og rotorvekslere Hans Theil Dias-nr.: 1 Præsentation Min baggrund er næsten 40 års arbejde som installationsingeniør på diverse hospitaler Mit speciale er ventilation og køle-/varmeforsyning Har været fagansvarlig for ventilation

Læs mere

Ventilation på operationsstuer/dagkirurgiske operationsstuer

Ventilation på operationsstuer/dagkirurgiske operationsstuer Ventilation på operationsstuer/dagkirurgiske operationsstuer # 1 Hans-Ulrik Rasmussen projektleder DNU/Skejby (På Skejby fra 2006) til og med 2014, herefter seniorkonsulent i DNU Arbejdet som rådgiver

Læs mere

Ventilation på operationsstuer Hvad bestemmer luftstrømningerne? Peter V. Nielsen, Aalborg University

Ventilation på operationsstuer Hvad bestemmer luftstrømningerne? Peter V. Nielsen, Aalborg University Ventilation på operationsstuer Hvad bestemmer luftstrømningerne? ø Peter V. Nielsen Aalborg Universitet 1 Temaet i dag Smittespredning på sengestuer (og operationsstuer) Luftmængde Luftfordelingssystem

Læs mere

Ventilation. Ventilation kan etableres på to forskellige måder:

Ventilation. Ventilation kan etableres på to forskellige måder: Rum, som benyttes af personer, skal ventileres så tilfredsstillende komfort og hygiejniske forhold opnås. Ventilationen bevirker, at fugt og forurening (partikler, CO 2, lugt mm.) fjernes fra opholdsrummene

Læs mere

SØREN JENSEN RÅDGIVENDE INGENIØRFIRMA A/S Havneparken Vejle Att.: Hans Theil Hansen

SØREN JENSEN RÅDGIVENDE INGENIØRFIRMA A/S Havneparken Vejle Att.: Hans Theil Hansen SØREN JENSEN RÅDGIVENDE INGENIØRFIRMA A/S Havneparken 4 7100 Vejle Att.: Hans Theil Hansen 6. kontor Postboks 1228 0900 København C Tlf. 70121288 Fax 72208585 at@at.dk www.at.dk CVR-nr. 21481815 Tilstrækkeligt

Læs mere

Afsnit 7 Teknisk standard Ventilation. Kolding og Fredericia Sygehuse 01-04-2011 - rev. 1

Afsnit 7 Teknisk standard Ventilation. Kolding og Fredericia Sygehuse 01-04-2011 - rev. 1 Afsnit 7 Teknisk standard Ventilation Kolding og Fredericia Sygehuse 01-04-2011 - rev. 1 Indholdsfortegnelse: 57.11 Komfortventilation Aggregater... 3 57.12 Komfortventilation Kanalsystemer og armaturer...

Læs mere

Tekniske standarder Afsnit 7 - bips nr. 57 Ventilation 10. udgave

Tekniske standarder Afsnit 7 - bips nr. 57 Ventilation 10. udgave OUH O D E N S E U N I V E R S I T E T S H O S P I T A L SVENDBORG SYGEHUS Afsnit 7 - bips nr. 57 Ventilation 10. udgave 10. januar 2014 Indholdsfortegnelse 57.11 Komfortventilation Aggregater... 2 57.12

Læs mere

Ventilation på faste arbejdssteder

Ventilation på faste arbejdssteder 1.6 Tjekliste om arbejdsstedets indretning og udførelse til koordinator P i program- og i projektgranskningsfasen Ventilation på faste arbejdssteder Krav om ventilation 1 Har arbejdsrum tilstrækkelig tilførsel

Læs mere

Afholdt d. 18. maj 2017

Afholdt d. 18. maj 2017 NIR SOM FUNDAMENT Elsebeth Tvenstrup Jensen Central Enhed for Infektionshygiejne Statens Serum Institut etj@ssi.dk NIR SOM FUNDAMENT FOR Retningsgivende instrukser Dialog-redskab med afdeling/hospital,

Læs mere

Styring af infektionshygiejne i sundhedssektoren Del 5: Krav til perioperativ infektionsprofylakse

Styring af infektionshygiejne i sundhedssektoren Del 5: Krav til perioperativ infektionsprofylakse Dansk Standard DS 2451-5 1. udgave 2001-08-21 Styring af infektionshygiejne i sundhedssektoren Del 5: Krav til perioperativ infektionsprofylakse Infection control in the health care sector Part 5: Requirements

Læs mere

Afholdt d. 22. maj 2015

Afholdt d. 22. maj 2015 NATIONALE INFEKTIONSHYGIEJNISKE RETNINGSLINJER - erfaringer fra processen Brian Kristensen Fagchef, overlæge Central Enhed for Infektionshygiejne NIR: EN STOR INDSATS FRA MANGE PARTER Retningslinje Antal

Læs mere

Funktionsafprøvning og BR18. - Niels Bruus Varming, TBST

Funktionsafprøvning og BR18. - Niels Bruus Varming, TBST Funktionsafprøvning og BR18 - Niels Bruus Varming, TBST BR18 OG CERTIFICERINGSORDNINGEN BAGGRUND FOR BR18 OG CERTIFICERINGSORDNINGEN BAGGRUND Initiativ i Vækst og udvikling i hele Danmark fra november

Læs mere

SEL-Værdi. Bachelorprojekt Andreas Jonassen

SEL-Værdi. Bachelorprojekt Andreas Jonassen SEL-Værdi Bachelorprojekt Andreas Jonassen Hvad og hvorfor SEL-værdi? Hvilke krav har jeg arbejdet med? Hvordan arbejder branchen med SELværdien? Hvordan kan branchen blive bedre? 2 22 Danmarks samlede

Læs mere

TEKNISK INFORMATION - HRV 501 Boligventilation med rotorveksler og fugtoverførsel

TEKNISK INFORMATION - HRV 501 Boligventilation med rotorveksler og fugtoverførsel TEKNISK INFORMATION - HRV 501 Boligventilation med rotorveksler og fugtoverførsel HRV 501 1 Generel beskrivelse 3 2 Tekniske data 5 3 Tilbehør 7 Forbehold for ændringer og trykfejl. September 2014. Generel

Læs mere

LAD NATUREN KOMME INDENFOR

LAD NATUREN KOMME INDENFOR LAD NATUREN KOMME INDENFOR JANUAR 2015 2 TX INDUSTRI Decentral ventilation med en kapacitet på 1400-3000 m³/h, kan anvendes følgende steder: autoværksteder produktionsvirksomheder idrætshaller byggemarkeder

Læs mere

INDHOLDSFORTEGNELSE VENTILATION 0 1. Ventilation 0 1

INDHOLDSFORTEGNELSE VENTILATION 0 1. Ventilation 0 1 INDHOLDSFORTEGNELSE VENTILATION 0 1 0 1 VENTILATION VENTILATION Registrering Registrering af ventilation omfatter: ventilationsform(er) areal af ventilerede lokaler driftstid luftskifte værdier virkningsgrad

Læs mere

INDHOLDSFORTEGNELSE VENTILATION 0 1. Ventilation 0 1

INDHOLDSFORTEGNELSE VENTILATION 0 1. Ventilation 0 1 INDHOLDSFORTEGNELSE VENTILATION 0 Ventilation 0 VENTILATION VENTILATION Registrering Registrering af ventilation omfatter: ventilationsform(er) areal af ventilerede lokaler driftstid luftskifte værdier

Læs mere

Appendiks 7. Solvarme. Klimatiske principper. appendiks

Appendiks 7. Solvarme. Klimatiske principper. appendiks appendiks Appendiks 7 Klimatiske principper Ved et adaptivt design skal der tages højde for de forskellige påvirkninger fra naturen ved de respektive placeringer. I forlængelse af ressourceforbrug under

Læs mere

LAD NATUREN KOMME INDENFOR

LAD NATUREN KOMME INDENFOR LAD NATUREN KOMME INDENFOR JUNI 2013 2 TX BOLIG Decentral ventilation med en kapacitet på 35 til 350 m³/h, kan eventuelt anvendes følgende steder: privatbolig kontorer mødelokaler undervisningslokaler

Læs mere

Fik vi svar på vores spørgsmål? - Debat og erfaringsudveksling v/deltagere og Planlægningsgruppen

Fik vi svar på vores spørgsmål? - Debat og erfaringsudveksling v/deltagere og Planlægningsgruppen Fik vi svar på vores spørgsmål? - Debat og erfaringsudveksling v/deltagere og Planlægningsgruppen Temadag for hygiejnesygeplejersker den 4. marts 2015 Den dagkirurgiske patient Phønix Fremtidens hus for

Læs mere

BRUGERVEJLEDNING CTS602 BY NILAN. Comfort CT150 med Basic panel

BRUGERVEJLEDNING CTS602 BY NILAN. Comfort CT150 med Basic panel BRUGERVEJLEDNING CTS602 BY NILAN Comfort CT150 med Basic panel Version 2.01-25.01.2017 INDHOLDSFORTEGNELSE Sikkerhed Strømforsyning... 3 Bortskaffelse... 3 Ventilationsanlæg... 3 Quick guide Betjeningspanel...4

Læs mere

FSTA Årsmøde OP-stuer vejledning & standard V/ Jan Mottlau, Niras a/s

FSTA Årsmøde OP-stuer vejledning & standard V/ Jan Mottlau, Niras a/s FSTA Årsmøde 2018 OP-stuer vejledning & standard 2018-10-23 V/ Jan Mottlau, Niras a/s Vejledning for OP stuer FSTA årsmøde 2018 - Hvor er vi nu Den gældende FSD/FSTA vejledning fokuserer næsten udelukkende

Læs mere

LAD NATUREN KOMME INDENFOR

LAD NATUREN KOMME INDENFOR LAD NATUREN KOMME INDENFOR OKTOBER 2012 2 TX KOMFORT Decentral ventilation med en kapacitet på 250 til 1000 m³/h, kan anvendes følgende steder: skoler kontorer mødelokaler kantiner institutioner pavilloner

Læs mere

ÅRSKONFERENCE FSTA 1. OKTOBER 2013 KOLDING

ÅRSKONFERENCE FSTA 1. OKTOBER 2013 KOLDING ÅRSKONFERENCE FSTA 1. OKTOBER 2013 KOLDING Kvalitetssikring på hospitaler i drift Hygiejnesygeplejerske Helle Amtsbiller SSI / Central Enhed for Infektionshygiejne SEMMELWEIS OG FLORENCE NIGHTINGALE FOREBYG

Læs mere

Vejledningen skal støtte de dagtilbud og kommuner i arbejdet med indeklima, herunder temperatur som en del af arbejdet for et godt børnemiljø.

Vejledningen skal støtte de dagtilbud og kommuner i arbejdet med indeklima, herunder temperatur som en del af arbejdet for et godt børnemiljø. Denne DCUM-vejledning handler om temperaturer i dagtilbud. en beskriver, hvilken betydning temperaturen i dagtilbud har, temperaturens påvirkning af børnenes trivsel, og hvordan børnene generelt bliver

Læs mere

BE KOMPAKT serie Ventilationsaggregat

BE KOMPAKT serie Ventilationsaggregat 1 serie Ventilationsaggregat Typer: 150 300 2 serien kan anvendes i lejligheder, boliger samt mindre erhvervsbygninger. De energivenlige ECmotorer og højeffektiv modstrømsveksler sikre en energibesparende

Læs mere

NORDISK R 3 -FORENING

NORDISK R 3 -FORENING NORDISK R 3 -FORENING Filterguide for Rene Rum i den farmaceutiske industri Februar 2000 Sag 99.0466 J.nr. 793-990417 Udarb. BRW Udg. 01 Kontrol HHO Dato 2000-02-01 Godk. HHO R A M B Ø L L B R E D E V

Læs mere

Kort informativ sammenfatning af projektets resultater og konklusioner

Kort informativ sammenfatning af projektets resultater og konklusioner Kort informativ sammenfatning af projektets resultater og konklusioner Indledning Passiv rygning på grund af luftoverføring mellem lejligheder, såkaldt naborøg, er en vigtig sag for mange beboere i etageboliger.

Læs mere

TX 3000. Turbovex. Turbovex A/S Industrivej 45 9600 Aars Tlf. 96 98 14 62 Fax 98 62 42 24 E-mail: info@turbovex.dk. Udvendig.

TX 3000. Turbovex. Turbovex A/S Industrivej 45 9600 Aars Tlf. 96 98 14 62 Fax 98 62 42 24 E-mail: info@turbovex.dk. Udvendig. Turbovex Decentral ventilation med varmegenvinding TX 3000 er et nyudviklet koncept for luftskifte I værksteder, industrihaller og lagerbygninger etc. Ventilationsaggregatet monteres gennem taget med kun

Læs mere

Prøvningsprogram og vurderingskriterier for luftrensere

Prøvningsprogram og vurderingskriterier for luftrensere Prøvningsprogram og vurderingskriterier for luftrensere Torben Eggert, Thomas Witterseh Byggeri September 2003, revideret september 2006 Principper Luftrensere, som kan prøves efter dette måleprogram,

Læs mere

BRUGERVEJLEDNING CTS602 BY NILAN. Comfort CT150 med Basic panel

BRUGERVEJLEDNING CTS602 BY NILAN. Comfort CT150 med Basic panel BRUGERVEJLEDNING CTS602 BY NILAN Comfort CT150 med Basic panel Version 2.10-03.04.2017 INDHOLDSFORTEGNELSE Sikkerhed Strømforsyning... 3 Bortskaffelse... 3 Ventilationsanlæg... 3 Quick guide Betjeningspanel...4

Læs mere

Nordisk R3-forening Revideret februar filterguide rene rum i den farmaceutiske industri

Nordisk R3-forening Revideret februar filterguide rene rum i den farmaceutiske industri Nordisk R3-forening Revideret februar 2012 filterguide rene rum i den farmaceutiske industri Denne filterguide udgivet som RAMBØLL Bulletin nr. 75 er udarbejdet med midler dels fra et R3-Stipendium tildelt

Læs mere

At-VEJLEDNING. Recirkulation. A.1.7 Februar 2002. Vejledning om tilbageførsel af udsuget forurenet luft til arbejdsrum eller andre lokaler

At-VEJLEDNING. Recirkulation. A.1.7 Februar 2002. Vejledning om tilbageførsel af udsuget forurenet luft til arbejdsrum eller andre lokaler At-VEJLEDNING A.1.7 Februar 2002 Recirkulation Vejledning om tilbageførsel af udsuget forurenet luft til arbejdsrum eller andre lokaler 2 Hvad er en At-vejledning? At-vejledninger vejleder om, hvordan

Læs mere

LAD NATUREN KOMME INDENFOR

LAD NATUREN KOMME INDENFOR LAD NATUREN KOMME INDENFOR AUGUST 2014 2 TX BOLIG Decentral ventilation med en kapacitet på 35 til 350 m³/h, kan eventuelt anvendes følgende steder: Privatbolig/lejligheder kontorer mødelokaler undervisningslokaler

Læs mere

Montage, drift og vedligeholdelsesvejledning TX 35A

Montage, drift og vedligeholdelsesvejledning TX 35A Montage, drift og vedligeholdelsesvejledning TX 35A Rev.04 april 2013 Side 1 af 18 1.0.0 Indhold MONTAGE, DRIFT OG...1 VEDLIGEHOLDELSESVEJLEDNING...1 1.0.0 INDHOLD...2 2.0.0 ILLUSTRATIONER...2 3.0.0 GENEREL

Læs mere

Vejledningen skal støtte de undervisningsmiljøansvarlige i arbejdet med ventilation som en del af arbejdet for et godt undervisningsmiljø.

Vejledningen skal støtte de undervisningsmiljøansvarlige i arbejdet med ventilation som en del af arbejdet for et godt undervisningsmiljø. Ventilation DDenne DCUM-vejledning handler om ventilation på uddannelsessteder. en beskriver, hvad man bruger ventilation til, og hvilken påvirkning dårlig luftkvalitet har både på helbredet og præstationsevnen.

Læs mere

BE VILLA serie Ventilationsaggregat

BE VILLA serie Ventilationsaggregat 1 BE VILLA serie Ventilationsaggregat Typer: BE VILLA 200 BE VILLA 350 BE VILLA 700 BE VILLA serien kan anvendes i lejligheder, boliger samt mindre erhvervsbygninger. De energivenlige EC-motorer og højeffektiv

Læs mere

Med 360 graders spredning kan indeklimaet rigtigt folde sig ud

Med 360 graders spredning kan indeklimaet rigtigt folde sig ud lindab ventilation Med 360 graders spredning kan indeklimaet rigtigt folde sig ud Plexus. Den fleksible løsning til både køling, varme og ventilation Designet er baseret på to unikke teknikker: 360 graders

Læs mere

Varme- og køleanlæg i bygninger

Varme- og køleanlæg i bygninger Dansk standard DS 469 2. udgave 2013-02-06 Varme- og køleanlæg i bygninger Heating and cooling systems in buildings DS 469 København DS projekt: M253996 ICS: 91.140.10 Første del af denne publikations

Læs mere

Boligventilation Nr.: 1.04

Boligventilation Nr.: 1.04 Side 1/5 Tema: Boligventilation Nr.: Boligventilation med VGV, etageejendomme Dato: May, 2004. Rev. maj 2012 Keywords: Residential ventilation, system layout, humidity control, heat recovery. Resume Der

Læs mere

Udvikling af mekanisk ventilation med lavt elforbrug

Udvikling af mekanisk ventilation med lavt elforbrug Udvikling af mekanisk ventilation med lavt elforbrug Søren Terkildsen Sektion for bygningsfysik og installationer Alectia seminar 20 September 2012. Introduktion 3 årigt Ph.d studie på DTU byg. Ny type

Læs mere

INDEKLIMA OG GLAS BR-krav

INDEKLIMA OG GLAS BR-krav INDEKLIMA OG GLAS BR-krav VEJLEDNING 1. Indledning Denne information giver en oversigt over vigtige emner, som indgår i beskrivelsen af valg af glas for at opnå et godt indeklima, primært i forbindelse

Læs mere

NYE RETNINGSLINJER, ET VÆRKTØJ TIL AT FASTHOLDE KVALITETEN VED GENBEHANDLING AF STERILISERBART MEDICINSK UDSTYR

NYE RETNINGSLINJER, ET VÆRKTØJ TIL AT FASTHOLDE KVALITETEN VED GENBEHANDLING AF STERILISERBART MEDICINSK UDSTYR NYE RETNINGSLINJER, ET VÆRKTØJ TIL AT FASTHOLDE KVALITETEN VED GENBEHANDLING AF STERILISERBART MEDICINSK UDSTYR HVORDAN KAN KVALITETEN I GENBEHANDLINGSENHEDEN FASTHOLDES OG ØGES UDEN DDKM? Elsebeth Tvenstrup

Læs mere

Ventilation med ECL Comfort 310

Ventilation med ECL Comfort 310 Ventilation med ECL Comfort 310 Én løsning til styring og overvågning Med ECL Comfort 310 kan I samle styring og overvågning af alle jeres anlæg ét sted. Udvid eksempelvis en eksisterende varme- og brugsvandsløsning

Læs mere

Afholdt d. 22. maj 2015

Afholdt d. 22. maj 2015 NYBYGNING AF SYGEHUSE - LÆRING OG ERFARINGER HOS CEI Elsebeth Tvenstrup Jensen Central Enhed for Infektionshygiejne Statens Serum Institut Fagligt Forum for Infektionshygiejne 22. maj 2015 OVERSIGT Historik

Læs mere

Kvalitetsordning for mikrobryggerier Good Manufacturing Practice (GMP)

Kvalitetsordning for mikrobryggerier Good Manufacturing Practice (GMP) 1 GENERELLE GMP OG DESIGNPRINCIPPER Dette dokument beskriver generelle principper, som gælder for flere procesområder og funktioner, specifikt design- og bygningsmæssige aspekter, der har indirekte indflydelse

Læs mere

Vejledningen skal støtte de undervisningsmiljøansvarlige i arbejdet med temperatur som en del af arbejdet for et godt undervisningsmiljø.

Vejledningen skal støtte de undervisningsmiljøansvarlige i arbejdet med temperatur som en del af arbejdet for et godt undervisningsmiljø. Temperatur Denne DCUM-vejledning handler om temperaturer på uddannelsessteder. en beskriver, hvilken betydning temperaturen i undervisningslokalet har, temperaturens påvirkning af præstationsevnen, og

Læs mere

BE TOP serie Ventilationsaggregat

BE TOP serie Ventilationsaggregat 1 serie Ventilationsaggregat Typer: 150 200 300 2 serien kan anvendes i lejligheder, boliger samt mindre erhvervsbygninger. De energivenlige EC-motorer og højeffektiv modstrømsveksler sikre en energibesparende

Læs mere

ITEK og DI's kølingsvejledning til serverrum

ITEK og DI's kølingsvejledning til serverrum ITEK og DI's kølingsvejledning til serverrum 1 Udgivet af: ITEK og DI Redaktion: Henning Mortensen ISBN: 87-7353-7353-712-8 0.4.08 2 Forord Varme i serverrum er blevet et stigende problem i mange virksomheder

Læs mere

Villavent fra Systemair

Villavent fra Systemair God luftkvalitet giver god livskvalitet Villavent fra Systemair Danvent-Systemair A/S www.systemair.dk Telefon Jylland: 8738 7500 Telefon Sjælland 4772 4772 Moderne boliger har ingen naturlig udluftning.

Læs mere

Afholdt d. 22. maj 2015

Afholdt d. 22. maj 2015 Nationale Infektionshygiejniske Retningslinjer (NIR) om behandling af patienter med smitsomme sygdomme, herunder isolation Anne Kjerulf Statens Serum Institut NIR OM BEHANDLING AF PATIENTER MED SMITSOMME

Læs mere

Norm for mekaniske ventilationsanlæg

Norm for mekaniske ventilationsanlæg Dansk standard DS 447 2. udgave 2005-06-15 Norm for mekaniske ventilationsanlæg Code of Practice for mechanical ventilation installations DS 447 København DS projekt: 48146 ICS: 91.140.30 Første del af

Læs mere

il laboratorier Beskyttelse mod tusindvis af kemiske stoffer, biologiske agenser, kræftfremkaldende stoffer, radioaktive isotoper etc.

il laboratorier Beskyttelse mod tusindvis af kemiske stoffer, biologiske agenser, kræftfremkaldende stoffer, radioaktive isotoper etc. DUA-møde 10. juni 2010 Procesventilation il laboratorier Beskyttelse mod tusindvis af kemiske stoffer, biologiske agenser, kræftfremkaldende stoffer, radioaktive isotoper etc. 1 Hvilke krav stiller myndigheder

Læs mere

LAD NATUREN KOMME INDENFOR

LAD NATUREN KOMME INDENFOR LAD NATUREN KOMME INDENFOR NOVEMBER 2015 2 TX INDUSTRI Decentral ventilation med en kapacitet på 1400-3000 m³/h, kan anvendes følgende steder: autoværksteder produktionsvirksomheder idrætshaller byggemarkeder

Læs mere

Erfaringsopsamling om indeklimaproblematikker

Erfaringsopsamling om indeklimaproblematikker Erfaringsopsamling om indeklimaproblematikker Dette appendiks præsenterer indeklimaudfordringer, som kan opstå, og som er observeret i nybyggeri og renoverede bygninger. Det er ikke formålet med appendikset

Læs mere

Performance tests før AB-aflevering Styring og regulering

Performance tests før AB-aflevering Styring og regulering Performance tests før AB-aflevering Styring og regulering Præcisering af ydelser for rådgiver (projektering, byggeledelse og fagtilsyn) vedr. performance tests: 1. Den projektspecifikke tilretning af performance

Læs mere

Løsninger til sundhedssektoren og laboratorier

Løsninger til sundhedssektoren og laboratorier Løsninger til sundhedssektoren og laboratorier Enabling wellbeing Wherever air qua we take care of eve Din partner i indendørs luftkvalitet Halton er din livstids partner, fra design af systemerne gennem

Læs mere

AFSNIT 8: VARME, VENTILATION OG INDEKLIMA

AFSNIT 8: VARME, VENTILATION OG INDEKLIMA AFSNIT 8: VARME, VENTILATION OG INDEKLIMA 01-11-2018 1 S i d e Termostaterne Opvarmning af lejligheden sker med henholdsvis gulvvarme i badeværelset og radiatorvarme i de resterende rum. I de enkelte rum

Læs mere

Hospitalsinfektioner - hvordan smittes man og hvorfor går det så ofte galt?

Hospitalsinfektioner - hvordan smittes man og hvorfor går det så ofte galt? HOSPITALS- HYGIEJNE 2014 Paneldebat - hvad har vi opnået de sidste 10 år og hvor skal de næste 10 år føre os hen? KONFERENCE DEN 26. og 27. februar 2014 - KØBENHAVN First Hotel Copenhagen Hør talere fra:

Læs mere

CENTER FOR KLINISKE RETNINGSLINJER - CLEARINGHOUSE

CENTER FOR KLINISKE RETNINGSLINJER - CLEARINGHOUSE Bilag 7: Resume Titel: Klinisk retningslinje for perioperativ desinfektion af øje og øjenomgivelser til patienter til øjenoperation Forfattergruppe: Birgith Jakobsen, Udviklings- og uddannelsesansvarlig

Læs mere

LAD NATUREN KOMME INDENFOR

LAD NATUREN KOMME INDENFOR LAD NATUREN KOMME INDENFOR TX 3100A DECEMBER 2016 TURBOVEX - frisk luft til alle 2 TX 3100A Decentral ventilation med en kapacitet på 1400-3000 m³/h, kan anvendes følgende steder: autoværksteder produktionsvirksomheder

Læs mere

ELFORSK PSO-F&U 2007

ELFORSK PSO-F&U 2007 ELFORSK PSO-F&U 2007 Grundvandsvarmepumper og køling med grundvandsmagasiner som sæsonlager BILAG 3 Ventilationssystemer med køling og vandbårne kølesystemer Hundsbæk & Henriksen A/S November 2008 1 Høj

Læs mere

ACTIVENT dysearmatur. Produktfakta. Standard dyse inddelinger: Produkt kode eksempel: Opad. Til siderne 1) Nedad. Cirkulært

ACTIVENT dysearmatur. Produktfakta. Standard dyse inddelinger: Produkt kode eksempel: Opad. Til siderne 1) Nedad. Cirkulært ACTIVENT dysearmatur Activent er et indblæsningssystem. Activent fungerer godt i både små og store lokaler. Systemet kan anvendes i mange typer lokaler, som. f. eks. kontorer, skoler, forretningslokaler,

Læs mere

Vejledningen er udarbejdet af følgende medarbejdere fra den farmaceutiske industri og sygehusapoteker:

Vejledningen er udarbejdet af følgende medarbejdere fra den farmaceutiske industri og sygehusapoteker: VEJLEDNING Hygiejnisk monitorering i ikke-steril lægemiddelproduktion Indholdsfortegnelse 1. INDLEDNING... 2 2. BAGGRUND... 2 2.1 Retningslinjer... 2 2.2 Status... 3 3. UDARBEJDELSE AF HYGIEJNEMONITORERINGSPROGRAM...

Læs mere

SWASH REFRESHING WIPES

SWASH REFRESHING WIPES SWASH REFRESHING WIPES Føl dig ren og frisk... på ethvert tidspunkt af dagen! www.swash.eu SWASH REFRESHING WIPES Swash Refreshing Wipes er bløde, vådservietter specielt designet til at forfriske sig ind

Læs mere

2.0.0 Illustrationer. 1.0.0 Indhold

2.0.0 Illustrationer. 1.0.0 Indhold Turbovex TX 30 2.0.0 Illustrationer 1.0.0 Indhold 3.0.0 Generel information 3.1.0 Forord Denne monterings- og driftsvejledning indeholder teknisk information, og informationer om installation og vedligeholdelse

Læs mere

Turbovex TX 250A Turbovex A/S

Turbovex TX 250A Turbovex A/S Turbovex TX 250A Side 1 af 17 1.0.0 Indhold 1.0.0 INDHOLD... 1 1.0.0 INDHOLD... 2 2.0.0 ILLUSTRATIONER... 2 3.0.0 GENEREL INFORMATION... 3 3.1.0 FORORD... 3 3.2.0 ANVENDELSESOMRÅDER... 3 3.3.0 FORKERT

Læs mere

MicroVent Home System

MicroVent Home System MicroVent Home System MicroVent Home system Beregningseksempel 2 l/s 2 l/s 5 l/s 5 l/s 2 l/s 15 l/s Emhætte 20 l/s Fig. 1 Grundventilation MicroVent i boliger Mikroventilation dimensioneres således at

Læs mere

Indeklimaundersøgelse i 100 danske folkeskoler

Indeklimaundersøgelse i 100 danske folkeskoler Indeklimaundersøgelse i 100 danske folkeskoler - Tilbagemelding til skolerne Udarbejdet af: Eva Maria Larsen & Henriette Ryssing Menå Danmarks Tekniske Universitet December 2009 Introduktion Tak, fordi

Læs mere

Lufttætning af bygninger - sådan..? Marianne Bender Energitjenesten, Nordjylland

Lufttætning af bygninger - sådan..? Marianne Bender Energitjenesten, Nordjylland Lufttætning af bygninger - sådan..? Marianne Bender Energitjenesten, Nordjylland Håndværkernes Energiforum Tlf.: 70 333 777 - en indsats baseret på lokale kontakter og et fagligt netværk - indsatsen er

Læs mere

Montage, drift og vedligeholdelsesvejledning TX 35A

Montage, drift og vedligeholdelsesvejledning TX 35A Montage, drift og vedligeholdelsesvejledning TX 35A Rev.15 Februar 2010 Side 1 af 23 1.0.0 Indhold MONTAGE, DRIFT OG...1 VEDLIGEHOLDELSESVEJLEDNING...1 1.0.0 INDHOLD...2 2.0.0 ILLUSTRATIONER...2 3.0.0

Læs mere

Hospitalsenheden Horsens. Teknisk afdeling. Tekniske Standarder. Bips nr. 57 Ventilation. Revision: 2014.07.01

Hospitalsenheden Horsens. Teknisk afdeling. Tekniske Standarder. Bips nr. 57 Ventilation. Revision: 2014.07.01 Hospitalsenheden Horsens Teknisk afdeling Tekniske Standarder Bips nr. 57 Ventilation Revision: 2014.07.01 Hospitalsenheden Horsens Tekniske standarder Bips nr. 57 Ventilation Indholdsfortegnelse 57.1

Læs mere

Sådan rengøres skydebaner

Sådan rengøres skydebaner Sådan rengøres skydebaner De Danske Skytteforeninger Vingstedvej 27 7182 Bredsten 1 Fokus på rengøring i ny pjece De Danske Skytteforeninger udgiver med denne skrivelse en pjece om, hvordan man rengør

Læs mere

Formål med ventilation

Formål med ventilation Formål med ventilation Sikre frisk luft Fjerne lugtgener Fjerne fugt Fjerne partikler Bygningsopvarmning M.m. = godt indeklima Simpelt ventilationsanlæg Rigtigt ventilationsanlæg sanlægtyper (komfortanlæg)

Læs mere

Princip beskrivelse. - mere end funktionel

Princip beskrivelse. - mere end funktionel Princip beskrivelse - mere end funktionel P e r p e t u a l E n e r g y A p S drager nytte af mange års erfaring såvel internt som hos vores samarbejdspartnere og leverandører af løs ninger til ventilationsbranchen.

Læs mere

Bygningsreglementet og funktionsafprøvning. Trafik-, Bygge- og Boligstyrelsen Center for Byggeri Installationskonferencen

Bygningsreglementet og funktionsafprøvning. Trafik-, Bygge- og Boligstyrelsen Center for Byggeri Installationskonferencen Bygningsreglementet og funktionsafprøvning Trafik-, Bygge- og Boligstyrelsen Center for Byggeri Installationskonferencen 2018 2018-09-25 Hvad skal vi snakke om? Bygningsreglement, vejledninger og standarder

Læs mere

Vejledning Energimærkning af nybyggeri

Vejledning Energimærkning af nybyggeri Vejledning Energimærkning af nybyggeri Energistyrelsen har udarbejdet en vejledning med et spørgsmål/svar-skema på baggrund af en række spørgsmål, som vi typisk modtager i forbindelse med energimærkning

Læs mere

Datablad Varmegenvindingsaggregat A06. ØLAND A06 Varmegenvindingsaggregat

Datablad Varmegenvindingsaggregat A06. ØLAND A06 Varmegenvindingsaggregat ØLAND A06 Varmegenvindingsaggregat A06 - Comfort Grå A06 - Comfort Hvid A06 - Grå A06 - Hvid Anvendelse Øland A06 varmegevindingsaggregat anvendes til enrums ventilation, hvor der ønskes et godt indeklima

Læs mere

BE KOMPAKT serie Ventilationsaggregat

BE KOMPAKT serie Ventilationsaggregat 1 serie Ventilationsaggregat Typer: 2 serien kan anvendes i lejligheder, boliger samt mindre erhvervsbygninger. De energivenlige EC-motorer og en højeffektiv modstrømsveksler sikrer en energibesparende

Læs mere

Decentral boligventilation Vi gør det enkelt. Du gør det effektivt!

Decentral boligventilation Vi gør det enkelt. Du gør det effektivt! lindab ventilation Decentral boligventilation Vi gør det enkelt. Du gør det effektivt! BR10 krav og løsninger Bygningsreglementet BR10, 2013 stiller følgende krav til ventilation: 6.3.1.2. Beboelsesbygninger

Læs mere

Indretning af stinkskabslaboratorium. August 2016

Indretning af stinkskabslaboratorium. August 2016 Indretning af stinkskabslaboratorium August 2016 Indholdsfortegnelse 1 Indledning... 2 2 Indblæsningsarmaturer... 2 2.1 Valg af indblæsningsarmatur... 2 2.2 Placering af indblæsningsarmatur... 2 3 Stinkskabe...

Læs mere

INDHOLDSFORTEGNELSE VARMEPRODUCERENDE ANLÆG 0 1. Varmepumper 0 1

INDHOLDSFORTEGNELSE VARMEPRODUCERENDE ANLÆG 0 1. Varmepumper 0 1 INDHOLDSFORTEGNELSE VARMEPRODUCERENDE ANLÆG 0 1 Varmepumper 0 1 VARMEPRODUCERENDE ANLÆG VARMEPUMPER Generelt Varmepumper kan i mange tilfælde reducere energiforbruget til opvarmning og/eller varmt brugsvand.

Læs mere

God luftkvalitet giver God livskvalitet!

God luftkvalitet giver God livskvalitet! Energi Effektiv Ventilation Nutidens byggerier er godt isoleret og er derfor meget varmeeffektive med en minimal luftlækage. Konsekvensen af dette er, at mekanisk ventilation er særdeles vigtig at få installeret,

Læs mere

Energibesparelser i ventilationsanlæg Teori og praksis v/carsten Tonn-Pedersen. KlimaKlar torsdag den 12. maj 2011

Energibesparelser i ventilationsanlæg Teori og praksis v/carsten Tonn-Pedersen. KlimaKlar torsdag den 12. maj 2011 Energibesparelser i ventilationsanlæg Teori og praksis v/carsten Tonn-Pedersen KlimaKlar torsdag den 12. maj 2011 Fokus-omr områder God og energirigtig ventilation opnås ved at fokusere på: 1. Ventilationsbehov

Læs mere

DUKA PLUS L180E. DUKA Ventilation. din tryghed for et sundt indeklima

DUKA PLUS L180E. DUKA Ventilation. din tryghed for et sundt indeklima DUKA PLUS L180E DUKA Ventilation din tryghed for et sundt indeklima DUKA PLUS L180E Beskrivelse DUKA PLUS L180E er et fuldautomatisk ventilation aggregat med varmegenvinding, der tilføjer frisk filtreret

Læs mere

Rumventilation i autoværksteder

Rumventilation i autoværksteder Rumventilation i autoværksteder Udbudsmateriale Bygherre: Navn Adresse By Rådgiver: Navn Adresse By Udbudet gælder følgende lokaler: Ventilationsanlægget har opvarmningsfunktion Mekanisk værksted dag nat

Læs mere

PERFORMANCETESTS FSTA ÅRSKONFERENCE OKTOBER

PERFORMANCETESTS FSTA ÅRSKONFERENCE OKTOBER PERFORMANCETESTS FSTA ÅRSKONFERENCE OKTOBER 2016 KORT PRÆSENTATION JOHANNES THUESEN, RAMBØLL Energi og installationer i samspil med arkitektur Lavenergibyggerier Energianalyser og energiprojekter Tilsyn

Læs mere

LAD NATUREN KOMME INDENFOR

LAD NATUREN KOMME INDENFOR LAD NATUREN KOMME INDENFOR DECEMBER 2014 2 TX KOMFORT Decentral ventilation med en kapacitet på 250 til 00 m³/h, kan anvendes følgende steder: skoler kontorer mødelokaler kantiner institutioner pavilloner

Læs mere

Commissioning-processen til bygninger Installationer i nybyggeri og større ombygninger

Commissioning-processen til bygninger Installationer i nybyggeri og større ombygninger Dansk standard DS 3090 1. udgave 2014-02-27 Commissioning-processen til bygninger Installationer i nybyggeri og større ombygninger The commissioning process in buildings Installation services in new buildings

Læs mere

ErP. Ecodesign i SystemairCAD. En quick-guide til Ecodesign

ErP. Ecodesign i SystemairCAD. En quick-guide til Ecodesign Ventilatorer Brand- og røgprodukter Ventilationsaggregater Luftfordeling Aircondition Tilbehør Systemløsninger Ecodesign i SystemairCAD En quick-guide til Ecodesign ErP 2018 Ecodesign i SystemairCAD Ecodesign

Læs mere

BRUGERVEJLEDNING CTS150 BY NILAN. Comfort CT150

BRUGERVEJLEDNING CTS150 BY NILAN. Comfort CT150 BRUGERVEJLEDNING CTS150 BY NILAN Comfort CT150 Version 2.10-03.04.2017 INDHOLDSFORTEGNELSE Sikkerhed Strømforsyning... 3 Bortskaffelse... 3 Ventilationsanlæg... 3 Quick guide Betjeningspanel...4 Funktioner...

Læs mere

Drifts- og vedligeholdelsesvejledning TX 64. Rev. 2015.10.09

Drifts- og vedligeholdelsesvejledning TX 64. Rev. 2015.10.09 Drifts- og vedligeholdelsesvejledning TX 64 Rev. 2015.10.09 0 1 Indhold 1. Systembeskrivelse... 3 1.1 Formål... 3 1.2 Forsyningsområde... 3 1.3 Virkemåde... 3 2. Komponentoversigt... 3 3. Styring... 4

Læs mere

CIP-optimering uden risiko for fødevaresikkerheden

CIP-optimering uden risiko for fødevaresikkerheden CIP-optimering uden risiko for fødevaresikkerheden LARS HOUBORG REGIONAL R&D/APPLICATION MANAGER 26. MAJ 2016 CIP optimering og fødevaresikkerhed Når man optimerer CIP-processen for at opnå besparelser,

Læs mere

Kontrolvilkår for absolutfiltre. Forslag til supplement til Luftvejledningen

Kontrolvilkår for absolutfiltre. Forslag til supplement til Luftvejledningen Rapport nr. 33-2005 Kontrolvilkår for absolutfiltre Forslag til supplement til Luftvejledningen Lars K. Gram 23. december 2005 Miljøstyrelsens Referencelaboratorium for måling af emissioner til luften

Læs mere

Anne-Marie Thye Hygiejnesygeplejerske anne-marie.thye.01@regionh.dk

Anne-Marie Thye Hygiejnesygeplejerske anne-marie.thye.01@regionh.dk * Anne-Marie Thye Hygiejnesygeplejerske anne-marie.thye.01@regionh.dk Agenda *Officielle Krav til Infektionshygiejne i lægepraksis *Den Danske Kvalitetsmodel og lægepraksis *Eksempler på Infektionshygiejnearbejde

Læs mere

BIM Universe CFD til design af bygningers performance. Lars Broder Nielsen

BIM Universe CFD til design af bygningers performance. Lars Broder Nielsen BIM Universe 2018 CFD til design af bygningers performance Lars Broder Nielsen MAJ 2018 SIDE 1 800+medarbejdere 100+ ejere 85+ års erfaring 6 kontorer i Danmark 1 datterselskab i Norge 1 datterselskab

Læs mere

Desinfektion - overordnet set

Desinfektion - overordnet set Desinfektion - overordnet set Temadag for Hygiejnekontaktpersoner 31. marts 2014 Bodil Forman Hygiejnesplejerske Stigende antibiotikaforbrug til mennesker og dyr her i landet har bevirket en stigende forekomst

Læs mere