Lite Integreret Alarmovervågning og Adgangskontrol HARDWARE MANUAL IRC-2000-2 En ny generation af bygningssikkerhed
Copyright Notice Copyright 1995-2001 by RBH Access Technologies Inc. All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant to an agreement containing restrictions on its use. No part of this book may be copied or distributed, transmitted, stored in a retrieval system, or translated into any human or computer language, in any form or by any means, electronic, mechanical, magnetic, manual or otherwise, or disclosed to third parties without the express written consent of RBH Access Technologies Inc., Mississauga, Ontario, Canada. Trademark Integra32 is the trademark of RBH Access Technologies Inc. Windows is a trademark of Microsoft Corporation. All other product names mentioned herein are the property of their respective owners. Use of a term in this book should not be regarded as affecting the validity of any trademark or service mark. Disclaimer This book is provided as is, without warranty of any kind, either express or implied, including but not limited to performance, merchantability, or fitness for any particular purpose. Neither RBH Access Technologies Inc. nor its dealers or distributors shall be liable to any person or entity with respect to any liability, loss, or damage, caused or alleged to have been caused directly or indirectly by this information. Further RBH Access Technologies Inc. reserves the right to revise this publication, and to make changes to the content hereof from time to time, without the obligation of RBH Access Technologies Inc. to notify any person or organization of such revision or changes. RBH ACCESS TECHNOLOGIES INC. 5775 Atlantic Drive, Suite 14 Mississauga, Ontario CANADA L4W 4P3 Tel: (905) 670-1100 Fax: (905) 670-0022 Email: info@rbh-access.com www: www.rbh-access.com Printing Date 3 November, 2004
Indhold KAPITEL 1 PRÆSENTATION AF AXIOMLITE...3 AXIOMLITE SYSTEM DIAGRAM...4 KAPITEL 2 INTELLIGENT TERMINAL...5 Spænding...6 PC/ Modem Interface...6 Input...6 Output...6 Læsere...6 Jord...6 DIP Switch indstillinger...8 TABEL 1 DIP SWITCH...8 Terminal-adressering...9 TABEL 2 TERMINALADRESSE...9 Direkte tilslutning/modem...9 TABEL 3 DIREKTE/MODEM...9 Computer/Modem Port Baud Rate...10 TABEL 4 BAUD RATE...10 PC TILSLUTNING...10 RS232 TILSLUTNING...10 TABEL 5 RS232 TILSLUTNING...10 PC TIL IRC-2000 - RS232 INTERFACE KABLING...11 Kabelspecifikation...11 Maximum kabellængde...11 MODEM TILSLUTNING...12 Kabelspecifikation...12 Maximum kabellængde...12 TCP/IP TILSLUTNING...12 RS485 TILSLUTNING...13 PC TIL IRC-2000 TILSLUTNING 2-LEDERS RS485 INTERFACE-KABLING...13 Kabelspecifikation...13 Maximum kabellængde...13 TERMINALNETVÆRK...14 TERMINALNETVÆRK TILSLUTNINGSDIAGRAM...14 STATUS LED'S...14 Computer/Modem Port...14 Run LED...14 Buzzer LED...14 SIKRINGER...15 JUMPERE...15 KAPITEL 3 INPUT- & OUTPUTTILSLUTNINGER...16 INPUT...16 RTE (UD-tryk)...16 DC (Dørsensor)...16 i
INPUT - KREDSLØBSTYPER...16 TABEL 6 NORMALT LUKKET, INGEN MODSTAND...16 TABEL 7 NORMALT ÅBEN, INGEN MODSTAND...17 TABEL 8 NORMALT LUKKET, 1 MODSTAND...17 TABEL 9 NORMALT LUKKET, 2 MODSTANDE...18 TABEL 10 NORMALT ÅBEN, 1 MODSTAND...18 TABEL 11 NORMALT ÅBEN, 2 MODSTANDE...19 TABEL 12 NORMALT ÅBEN OG NORMALT LUKKET, 1 MODSTAND...19 OUTPUT...20 Låse Output...20 Handicap Output...20 ELEKTRONISK OUTPUT - TILSLUTNINGSDIAGRAM...20 Aktivering af Induktive enheder (Låse, klokker, m.v.)...21 RELÆ OUTPUT OPERATION...21 Låse Output...21 MAGNETISK LÅS - TILSLUTNINGSDIAGRAM...21 DØRLÅS - TILSLUTNINGSDIAGRAM...22 HANDICAP OUTPUT - TILSLUTNINGSDIAGRAM...22 ADGANGSPUNKTS OPERATIONSTILSTANDE...23 Høj sikkerhed...23 Oplåst...23 Dør-holdt-åben-advarsel...23 Dør-holdt-åben-alarm...23 Tastatur/læser-kombination...23 Adgang godkendt...23 Adgang nægtet...23 LÆSERTILSLUTNING...24 IRC-2000-2 TIL ALFAPROX-LÆSER TILSLUTNINGSDIAGRAM...24 Kabelspecifikation...24 Maximum kabellængde...24 IRC-2000 SPECIFIKATION...26 KABELSPECIFIKATION...27 PC til terminal...27 IRC-2000 til læser:...27 Input / Output kredsløbssløjfe:...27 ii
Kapitel 1 Præsentation af AxiomLite Kapitel 1 Præsentation af AxiomLite AxiomLite systemet fra RBH Access Technologies Inc. repræsenterer det nyeste indenfor adgangsteknologi specifikt designet til mindre applikationer. Dets intuitive grafiske interface tillader brugerne at udnytte styrken i AxiomLite med minimal oplæring. De nye IRC-2000 Intelligente terminaler indeholder flash firmware for nem opgradering. IRC-2000- terminalerne anvender fuld distribueret intelligens til off-line-operationer. Foruden at understøtte 2 kortlæsere, har hver IRC-2000-terminal også 8 fuldt overvågede alarminput samt 8 output. PC en anvendes til indtastning af data, opsætning af databasen og overvågning af aktivitet I systemet. Når databasen først er downloaded til terminalerne, er PC en ikke længere nødvendig til systemoperation. Bliver PC en lukket ned, vil IRC-2000-terminalen udføre al kontrol af adgang og andre funktioner, inklusiv logging af op til 1.400 events. Når forbindelsen bliver genetableret, vil loggen blive rapporteret til PC en. AxiomLite Sikkerhedsmanagement-software kører på Windows 98, Windows NT 4.0 eller Windows 2000 og er Y2K-kompatibelt. Op til 16 IRC-2000 ere kan sammenkobles med en maksimal kapacitet på 32 læsere. Systemet understøtter maksimalt 2.000 kortholdere. Tilslutning til PC en kan være RS232 (ved enkelt-terminal-systemer) eller RS485 (maksimal total kabel-distance er 1.300 meter) i systemer med flere terminaler. Andre funktioner inkluderer 40 feriedage, 128 tidszoner samt handicap-adgang for pr. kortholder. Høj sikkerhed og lås/åben-funktion understøttes også. Hver terminal kan have op til 64 input/output-link, og systemet er i stand til at indeholde 255 forud-programmerede operatør-kommandoer. Både lokal og tidsstyret Antipassback understøttes også. 3
Kapitel 1 Præsentation af AxiomLite AxiomLite System Diagram Maksimalt 16 IRC-2000 og 32 kortlæsere med/uden tastatur 4
Kapitel 2 Intelligent terminal Kapitel 2 Intelligent terminal AxiomLite32 adgangskontrolsystem består af een eller flere terminaler (IRC-2000). Al information, som terminalen kræver, bliver downloaded fra PC en og gemt lokalt i flash-hukommelsen. Denne information inkluderer konfigurationsdata, kortholder-poster, adgangsniveauer, skemaer og alle andre poster, der er nødvendig for systemoperationen. Terminalen opererer uafhængigt af PC en og al beslutningstagning bliver udført lokalt; selv i tilfælde af totalt strømsvigt. IRC-2000 eren indeholder en kraftfuld flash micro-controller og er en af de mest kraftfulde og alsidige terminaler, der i øjeblikket er tilgængelig. 5
Kapitel 2 Intelligent terminal Tilslutningdetaljer Spænding IRC-2000 kræver 9 til 14 volt DC og trækker ca. 250 ma. PC/ Modem Interface PC/Modem interfacet forbinder IRC-2000 eren til en PC eller et modem via en RS232, TCP/IP Ethernet eller et RS485 (2 ledninger) interface. Input Der er en fælles terminal for hvert sæt af 2 input (én for input 1 og 2, én for input 3 og 4, én for input 5 og 6 og en anden for input 7 og 8). 7 forskellige inputtyper er understøttet (inklusiv normalt åben, normalt lukket, een modstand og to modstande). Output 4 af de 8 programmerbare output er potentialefri relæer (output 5A @ 12V DC). Disse er tildelt som output 1 og 2 samt 5 og 6. De andre 4 output er elektroniske omskiftere (åben kollektor til stel 100mA) og har numrene 3 og 4 samt 7 og 8. Læsere Læsere bliver tilsluttet til ikke-programmerbare output BUZ, RED, & GRN, samt datainput D0 og D1. Begge læsere har deres egne tilslutningsterminaler, læser A på venstre side og læser B på højre side. Jord Terminalen indeholder adskillige lag af beskyttelse mod induceret høj spænding transient fra statisk afladning, lyn og spændingsudsving. For at gøre denne beskyttelse fuldt effektiv, er det vigtigt med en god jording. Forbind denne tilslutning til et koldt-vandsrør af metal eller lignende. Forbind ikke direkte til jord på AC. Brug 1,5 mm² eller kraftigere kabel og hold længden så kort som mulig (mindre en 15 meter). 6
Kapitel 2 Intelligent terminal Relæer: #1, 2, 5, 6 form C Relæer #3, 4, 7, 8 åben collector til minus Læser A: Grøn LED (Rød LED) Buzzer Data 0 Data 1 (Tamper) Spænding Læser B: Grøn LED (Rød LED) Buzzer Data 0 Data 1 (Tamper) Spænding Input 1-4 Input 5-8 RS485 tilslutning PC/Modem Interface 9-14 vdc @ 250ma 7
Kapitel 2 Intelligent terminal DIP Switch indstillinger IRC-2000 erens DIP switches kontrollerer en række operations-parametre inklusiv terminal- adressen og serielportens baud rate. Terminalen skal slukkes for at acceptere ændringer i DIP-switchindstillingerne. Brug DIP-switches 1 til 5 for at sætte terminal-adressen. Switch 6 og 7 sætter kommunikationens baud rate, og switch 8 anvendes for at sætte tilslutningstypen (modem eller direkte). DIP Switch DIP Switch Funktion 1-5 Terminal-adresse 6,7 Baud Rate 8 Modem/Direkte PC tilslutning Tabel 1 DIP Switch 8
Kapitel 2 Intelligent terminal Terminal-adressering Brug DIP-switches 1, 2, 3, 4 og 5 for at vælge terminaladresse. Adressen er binært kodet og switch-indstillingerne for alle 16 mulige adresser er givet herunder. Terminal-adressering Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Adresse On Off Off Off Off 1 Off On Off Off Off 2 On On Off Off Off 3 Off Off On Off Off 4 On Off On Off Off 5 Off On On Off Off 6 On On On Off Off 7 Off Off Off On Off 8 On Off Off On Off 9 Off On Off On Off 10 On On Off On Off 11 Off Off On On Off 12 On Off On On Off 13 Off On On On Off 14 On On On On Off 15 Off Off Off Off On 16 Direkte tilslutning/modem Tabel 2 Terminaladresse DIP-switch 8 specificerer om IRC-2000 er tilsluttet direkte til en seriel port på PC en eller kommunikerer med PC en over et modem. Kontact ARAS Security for information om den mulige TCP/IP Ethernet-tilslutning. Direkte tilslutning / Modem DIP Switch 8 Interface Type OFF Direkte tilslutning til PC ON Modem Tabel 3 Direkte/Modem 9
Kapitel 2 Intelligent terminal Computer/Modem Port Baud Rate Terminalens serielle port baud rate sættes med DIP-switches 6 og 7. Denne indstilling bestemmer hastigheden brugt til kommunikation med modemet eller PC ens serielle port. Hvis terminalen er tilsluttet direkte til PC en, skal terminalens baud rate være sat til det samme som PC ens port. Default PC baud rate er 9600. Terminalens Baud Rate DIP Switch 6 DIP Switch 7 Baud Rate OFF OFF 9,600 OFF ON 56,000 ON OFF 38,400 ON ON 28,800 Tabel 4 Baud Rate PC tilslutning PC ens serielle port, som anvendes for tilslutning til IRC-2000-2 tildeles under Communication Port Setup i AxiomLite softwaren. Baud raten er som default sat til 9600 for direkte tilslutning til PC en ved brug af standard RS232 interface. RS232 interface anvendes kun til kommunikation med den første terminal i netværket. Afstanden mellem PC en og terminalen kan ikke være større end 50 meter eller 10 meter, hvis baud raten forøges til 38.400. Ved afstande over 50 meter skal der bruges et RS485 interface. RS485 er indbygget i IRC-2000- terminalen, men er ikke en del af en standard-pc. PC en skal enten udstyres med et RS485 serielt kort eller en ekstern RS232 til RS485 seriel port converter. Den/de næste terminaler tilsluttes terminal 1 via terminalstik P9 RS485. RS232 tilslutning Terminal til PC (RS232) Terminal DB9 Connector DB25 Connector GND Pin 5 Pin 7 TX/A Pin 2 Pin 3 RX/B Pin 3 Pin 2 Tabel 5 RS232 tilslutning 10
Kapitel 2 Intelligent terminal PC til IRC-2000 - RS232 Interface kabling Jumper JP1 sættes i den øverste position ved RS232. Kabelspecifikation 3 eller 4 ledere skærmet, 0,35 0,8 mm² Maximum kabellængde 9600 baud 50 meter 38400 baud 10 meter 11
Kapitel 2 Intelligent terminal Modem tilslutning IRC-2000 kan tilsluttes PC en via et modem. Modemtilslutningen svarer til RS232- tilslutningen, men inkluderer DCD terminalen. Hvis der anvendes flere terminaler, skal RS485-konnectoren anvendes for tilslutning af yderligere terminaler. Jumper JP1 sættes i den øverste position ved RS232. Kabelspecifikation 4 ledere skærmet, 0,35 0,8 mm² Maximum kabellængde 9600 baud 50 meter 38400 baud 10 meter TCP/IP tilslutning Ved TCP/IP-tilslutning, forbindes TCP/IP interfacet som til en PC, med en direkte RS232-tilslutning. Yderligere terminaler kan tilsluttes via RS485 terminalen. 12
Kapitel 2 Intelligent terminal RS485 tilslutning IRC-2000-terminalen understøtter en 2-leders RS485-tilslutning. Jumper JP1 skal sættes på de 2 nederste pinde. RS485 interfacet tillader at afstanden mellem terminalen og PC en øges til 1200 meter. RS485 kræver et snoet par med skærm. Den sidste terminal skal have sin terminator -jumper anbragt. Sørg også for at PC en er ordentligt termineret. Hvis det ikke kan gøres på boardet, kan man sætte en 130- ohms modstand over A/B-tilslutningen i PC-enden. PC til IRC-2000 tilslutning 2-leders RS485 Interface-kabling Jumper JP1 sættes i den nederste position ved RS485. Tilslutning til yderligere termninaler. Kabelspecifikation Enkelt snoet par, skærmet, 0,35 0,8 mm² Maximum kabellængde 1300 meter 13
Kapitel 2 Intelligent terminal Terminalnetværk Op til 16 IRC-2000-terminaler kan forbindes med hinanden og tilsluttes en enkelt COM-port på PC en. RS485-interfacet skal anvendes, når der tilsluttes flere terminaler. Tilslut TX/A på én terminal til TX/A på den næste terminal, og tilslut RX/B til RX/B. Terminer den sidste terminal med jumper JP3. Terminalnetværk tilslutningsdiagram Status LED's Computer/Modem Port Computer/modem-porten har 2 LEDs, der viser flowet af data mellem IRC-2000-terminalen og PC eller modem. Den røde RX LED (LED 3) blinker, når terminalen modtager data. Den grønne TX LED (LED 4) blinker, når terminalen sender data. Hvis terminalen er tilsluttet direkte til PC en, blinker status LED's kontinuerligt. Run LED Run LED en (LED 2) blinker for at indikere, at terminalen ikke kommunikerer. Hvis den lyser konstant, kører den normalt, og når den er slukket, mangler der spænding eller sikringen er sprunget.. Buzzer LED Denne LED (LED 1) vil lyse, hvis enten læser A s eller læser B s buzzer er aktiv. 14
Kapitel 2 Intelligent terminal Sikringer Der findes 2 stk. 1.25 amp. sikringer på IRC-2000-printpladen. F1 er tilsluttet læserspændingen og F2 er tilsluttet hovedspændingen til printet.. Læser spænding Hovedspænding Jumpere JP1 I øverste position for RS232 og i nederste position for RS485. JP2 Bias Lav RS485 tuning JP3 Termination RS485 tuning JP4 Bias Høj RS485 tuning Jumperne JP2 og JP4 bør kun ændres efter aftale med ARAS. 15
Kapitel 3 Input & Output tilslutninger Kapitel 3 Input- & outputtilslutninger Input IRC-2000 eren har 8 fuldt overvågede input, 2 sæt af 4, hvert sæt med 2 fælles common. Alle input kan programmeres individuelt fra PC en. IRC-2000 eren har digital filtrering for at eliminere effekten af interference på input-sløjferne og verificerer alle sløjfeændringer før de bliver rapporteret til terminalen. Hvert input kan rapportere op til 4 tilstande; Åben, Lukket, Unormal og Normal. F.eks. hvis kredsløbstypen er programmeret som 2 modstande normalt lukket, vil 1Kohm repræsentere en normal tilstand og 2Kohm repræsentere en unormal tilstand. Nul ohm er lukket og meget høj modstand er åben. RTE (UD-tryk) Input programmeret som RTE vil blive tilsluttet en trykknap monteret ved døren eller en bevægelsesføler nær døren. Aktivering af RTE-inputtet vil oplåse døren. UDtrykket kan deaktiveres af en tidszone. Flere input kan programmeres som UD-tryk for den samme dør. DC (Dørsensor) Input programmeret som dørsensor overvåger dørens status. Tvangsåbning, Dørholdt-åben-alarm og Dør-holdt-åben-advarsel kræver overvågning af dørens status. Input - kredsløbstyper IRC-2000 eren understøtter 7 forskellige input-kredsløbstyper gående fra ingen modstand ved lav sikkerhed til 2-modstande-normalt-lukket-kredsløb, hvor den højeste sikkerhed kræves. Normalt lukket, ingen modstand Sløjfemodstand Status Lukket Genopret Åbent kredsløb Alarm Tabel 6 Normalt lukket, ingen modstand 16
Kapitel 3 Input & Output tilslutninger Normalt åben, ingen modstand Sløjfemodstand Status Lukket Alarm Åbent kredsløb Genopret Tabel 7 Normalt åben, ingen modstand Normalt lukket, 1 modstand Sløjfemodstand Status Lukket Problem 1Kohm Genopret Åbent kredsløb Alarm Tabel 8 Normalt lukket, 1 modstand 17
Kapitel 3 Input & Output tilslutninger Normalt lukket, 2 modstande Sløjfemodstand Status Lukket Problem 1Kohm Genopret 2Kohm Alarm Åbent kredsløb Problem Tabel 9 Normalt lukket, 2 modstande Dette kredsløb giver en høj grad af overvågning og detekterer både lukkede og åbne kredsløbsfejl. Brug dette kredsløb i applikationer med høj sikkerhed. Normalt åben, 1 modstand Sløjfemodstand Status Lukket Alarm 1Kohm Genopret Åbent kredsløb Problem Tabel 10 Normalt åben, 1 modstand 18
Kapitel 3 Input & Output tilslutninger Normalt åben, 2 modstande Sløjfemodstand Status Lukket Problem 1Kohm Alarm 2Kohm Genopret Åbent kredsløb Problem Tabel 11 Normalt åben, 2 modstande Normalt åben og Normalt lukket, 1 modstand Sløjfemodstand Lukket 1Kohm Åbent kredsløb Status Alarm Genopret Alarm Tabel 12 Normalt åben og Normalt lukket, 1 modstand Dette kredsløb bruges, hvor der anvendes normalt åben og lukket i den samme sløjfe. 19
Output Kapitel 3 Input & Output tilslutninger IRC-2000 eren har 8 output, 4 relæoutput og 4 solid state output. Output 1, 2, 5 og 6 er potentialefri relæer, der kan belastes med 5 Amp @ 12 VDC. Output 3, 4, 7 og 8 bruger elektroniske drivere og kan belastes op til 100mA. Alle output er programmerbare fra PC en som On State energized eller On State de-energized. On State de-energized output anvendes til fejlsikker operation, hvor det er vigtigt, at outputtet returnerer til en sikker tilstand, når systemet går ned på grund af strømsvigt, kommunikationsfejl eller brand. Elektroniske output skifter til negativ, hvilket betyder, at de skifter spændingen til negativ på terminaltilslutningen. Når outputtet er FRA, bliver outputtet elektronisk frakoblet. Output kan programmeres til låse eller handicap-operation (som beskrevet herunder), eller de kan anvendes som output til generel brug. Låse Output Låse-outputtet anvendes til at aktivere eller deaktivere låseenheden på døren. Det kan tilføre spænding til låse eller fjerne spænding fra magnetlåse. Handicap Output Dette output anvendes til at drive dørautomatik. Det aktiveres 1 sekund efter låseoutputtet og forbliver aktivt indtil låseoutputtet slår fra. Kun særligt tildelte kortholdere vil aktivere dette output. Elektronisk Output - tilslutningsdiagram 20
Kapitel 3 Input & Output tilslutninger Aktivering af Induktive enheder (Låse, klokker, m.v.) Vær forsigtig ved tilslutning af induktive enheder. Induktive enheder inkluderer eksterne relæer, klokker og dørlåse. Alle disse enheder genererer ekstremt høje spændingsudsving (adskillige 1000 volt), når spænding tilføres og fjernes. Resultatet kan blive ødelæggelse af operationen, hvis denne interference kommer ind på det elektroniske board. Denne interference kan undertrykkes ved at man placerer en diode (1N4004 eller lignende) over låsen ellen anden induktiv enhed der bliver brugt. Tilslut diodens katode (enden med hvidt bånd) til den positive terminal og den anden til den negative terminal. Dioden skal placeres ved enheden og ikke på boardet. Relæ Output Operation Låse Output Ethvert output kan bruges til styring af en magnetisk lås eller dørlås. Flere output kan sættes til den samme funktion (output 1 og 2 kan begge være låseoutput for læser A). Magnetisk Lås - tilslutningsdiagram Ved brug af magnetisk lås, bør relæet konfigureres fra PC en som On State deenergized for fejlsikker operation. Hvis strømmen forsvinder (AC og batteri), vil spændingen til den magnetiske lås fjernes og døren åbnet. 21
Kapitel 3 Input & Output tilslutninger Dørlås - tilslutningsdiagram Handicap Output - tilslutningsdiagram 22
Kapitel 3 Input & Output tilslutninger Adgangspunkts operationstilstande Høj sikkerhed I høj sikkerhed, bliver kun kortholder med privilegiet Supervisor givet adgang. Oplåst Den grønne LED tænder og indikerer at døren er oplåst. Dør-holdt-åben-advarsel Buzzeren beeper langsomt. Dør-holdt-åben-alarm Buzzeren beeper vedvarende. Tastatur/læser-kombination Buzzeren udsender en serie af korte beep hvert sekund efter at et kort er blevet præsenteret, indtil PIN-koden indtastes. Adgang godkendt Buzzeren udsender eet langt beep og den grønne LED tænder i den tid, døren er oplåst. Adgang nægtet Buzzeren udsender 2 korte beep og den røde LED blinker 2 gange. 23
Læsertilslutning IRC-2000 eren understøtter enhver læser, der bruger Wiegand-format Kapitel 3 Input & Output tilslutninger IRC-2000-2 til ALFAPROX-læser tilslutningsdiagram Læser A Læser B Grøn LED Buzzer Data 0 Data 1 0 volt +12 volt Grøn LED Buzzer Data 0 Data 1 0 volt +12 volt Ledningsfarver for Alfaprox-læsere Rød 5-12 Vdc Sort GND Grøn D0 Hvid D1 Brun GRN (grøn LED) Gul buz (buzzer) Kabelspecifikation 6 ledere, skærmet, (ikke snoet), 0,25 0,50 mm² Maximum kabellængde 0,25 mm² kabel: 75 meter 0,50 mm² kabel: 150 meter 24
Appendix 1 Specifikationer Specifikationer 25
Appendix 1 Specifikationer IRC-2000 Specifikation Terminal - spændingskrav: 9 14V DC Strømforbrug: 250 ma Processor: 14-bit Microcontroller Flash ROM: Download firmware-opgradering fra PC en til IRC-2000 Hukommelse: Flash RAM Systemkapacitit: IRC-2000 ere per Netværk Maximum 16 Læsere per IRC-2000 2 Kortholdere Maximum 2.000 Eventlog per IRC-2000 Maximum 1.400 Netværkstilslutning: Type RS-232 eller RS-485 Seriel Port hastighed 9600, 28800, 38400 eller 56000 Real Time ur: Dallas DS1999 med batteri-backup Kabinetdimensioner: H?cm x B?cm x D?cm Operationstemperatur: 0 til 70 C Operatingsfugtighed: 20 til 80% RH (ikke-kondenserende) 26
Appendix 1 Specifikationer Kabelspecifikation PC til terminal RS232: 2-leder RS485: 3 eller 4 ledere skærmet, 0,35 0,80 mm² Maximum kabellængde 9600 baud 50 meter 38400 baud 10 meter Enkelt snoet par, skærmet 0,35 0,80 mm² Maximum kabellængde 1200 meter IRC-2000 til læser: 0,35 0,50 mm², 6 eller 8 ledere, skærmet (ikke snoet) Maximum kabellængde 0,35 mm² kabel 75 meter 0,50 mm² kabel 150 meter Input / Output kredsløbssløjfe: 2 ledere, 0,35 0,50 mm² Maximum kabellængde 300 meter 27