Kortslutningsbeskyttelse af fejlstrømsafbrydere foransiddende: C60, C120, NG125 automatsikringer eller sikringer efterfølgende: fejlstrømsafbryder

Størrelse: px
Starte visningen fra side:

Download "Kortslutningsbeskyttelse af fejlstrømsafbrydere foransiddende: C60, C120, NG125 automatsikringer eller sikringer efterfølgende: fejlstrømsafbryder"

Transkript

1 Kortslutningsbeskyttelse af fejlstrømsafbrydere foransiddende: C60, C120, NG125 automatsikringer eller sikringer efterfølgende: fejlstrømsafbryder Installationsanvisninger Fejlstrømsafbryder En fejlstrømsafbryder har begrænset kortslutningsholdbarhed. Den skal derfor kortslutningsbeskyttes ved hjælp af et kortslutningsbeskyttelsesudstyr. Som kortslutningsbeskyttelsesudstyr for ID felstrømsafbrydere kan anvendes automatsikringer, maksimalafbrydere eller smeltesikringer type gg. Kortslutningsbeskyttelsesudstyret kan være placeret i strømkredsen foran fejlstrømsafbryderen eller i en eller flere strømkredse efter fejlstrømsafbryderen. Placeres kortslutningsbeskyttelsesudstyret i en eller flere strømkredse efter fejlstømsafbryderen skal denne være placeret i samme tavlesektion som kortslutningsbeskyttelsesudstyret. Endvidere skal lederne fra fejlstrømsafbryderens afgangsklemmer til og mellem efterfølgende beskyttelsesudstyr være oplagt på en sådan måde at kortslutning eller jordslutning kan anses for udelukket. Se nærmere herom i Stærkstrømsbekendtgørelse, Afsnit 439-1, Oplysninger om kortslutningsholdbarhed I nedenstående tabeller er anført betinget kortslutningsstrøm (Icc eller Icf) for ID fejlstrømsafbrydere beskyttet med automatsikringer, maksimalafbrydere og smeltesikringer. 2-polede fejlstrømsafbrydere har mærkespændingen 240 V, og anvendes derfor i almindelighed her i landet som beskyttelsesudstyr for 1-fasede (L+N) strømkredse. (De kan dog anvendes i 2-fasede strømkredse med en spænding mellem faselederne på max. 240 V). Den betingede kortslutningsstrøm kortslutningsholdbarhed for 2-polede fejstrømsafbrydere) kan derfor bestemmes i tabelkolonnerne for 230/240 V strømkredse. 4-polede fejlstrømsafbrydere har mærkespændingen 415 V, kan anvendes som beskyttelsesudstyr for eller i såvel 1-fasede (L+N) strømkredse som 2- eller 3-fasede stømkredse med eller uden N-leder Er en 4-polet fejlstrømsafbryder tilsluttet 230 V kan den betingede kortslutningsstrøm (kortslutningsholdbarhed) for den 4-polet fejlstrømsafbryder bestemmes i tabelkolonnerne for 230/240 V strømkredse. Tabelkolonnerne for 230/240 V strømkredse kan også anvendes i tilfælde, hvor der gennem en fejlstrømsafbryder, som er tilsluttet f.eks. 3 faseleder og N-leder, udelukkende forsynes 230 V strømkredse og hvor lederne fra afgangsklemmerne på fejlstrømsafbryderne til og mellem efterfølgende kortslutningsbeskyttelsesudstyr er oplagt på en sådan måde, at kortslutning og jordslutning kan anses for udelukket. Forsynes gennem en 4-polet fejlstrømsafbryder strømkredse for 2 eller 3 faseledere skal den betingede kortslutningsstrøm for fejlstrømsafbryderen bestemmes i tabelkolonnerne for 400/415 V strømkredse. kortslutningsbeskyttelse.eps Kortslutningsbeskyttelse med smeltesikring type gg betinget kortslutningsstrøm med sikring Icf [kaeff] for kombinationen smeltesikring og fejlstrømsafbryder fejlstrømsafbryder ID 230 V/240 V strømkredse 400 V/415 V strømkredse 2- eller 4-polede fejlstrømsafbrydere 4-polede fejlstrømsafbrydere In (A) smeltesekring mærkestrøm (A) type gg Kortslutningsbeskyttelse med automatsikring og maksimalafbryder betinget kortslutningsstrøm Icc [kaeff] for kombinationen automatsikring/maksimalafbryder og fejlstrømsafbryder fejlstrømsafbryder ID 230 V/240 V strømkredse 400 V/415 V strømkredse 2- eller 4-polede fejlstrømsafbrydere 4-polede fejlstrømsafbrydere In (A) aut. sikr./maks. afbryder DPN C60N C60H NG 125N NG125L C120H C120N

2 Beskyttelse mod lækstrøm til jord Overblik over produktudvalg til beskyttelse mod lækstrøm til jord Beskyttelse mod lækstrøm til jord Overblik over produktudvalg til beskyttelse mod lækstrøm til jord Udvælgelsesvejledning Type Fejlstrømsafbrydere iid K iid RCCB-ID 125 A RCCB-ID type B Ekstra fejlstrømsafbrydermoduler Fejlstrømsafbrydere RCBO Vigi ic60 Vigi C120 Vigi NG125 DPN N Vigi PB PB PB PB101616_SE-35 PB _SE N_SE-35 PB104341B-35 Standarder IEC/EN IEC/EN IEC/EN og VDE 0664 IEC/EN og VDE 0664 Antal poler 1P+N 2P 3P 4P Type AC A SI B Spænding (V) Ue 230/ / / /400 Impulsspænding (kv) Uimp Isoleringsspænding (V) Ui Mærkestrøm (A) In til til 125 Frekvens (Hz) 50/ Nominel brydeevne (A) Icn Nominel betinget Inc kortslutningsstrøm Nominel residualbryde- (IΔm) 10 In (500 A min.) In (500 A min.) og slutteevne (A) Kurve Følsomhed (ma) (IΔn) s 500 s s s Elektriske egenskaber Kurver B C D L K MA Få flere oplysninger se side 62, 72 og 370 se side 62, 176 og 370 se side 62, 176 og 370 se side 62, 176 og 370 Tilbehør se side 140 se side 74 se side 76 Hjælpeenheder se side 128 og 184 se side 74 se side 76 IEC/EN IEC/EN IEC/EN IEC/EN / / / til til til 40 50/60 50/60 50/ B, C Afhængigt af den anvendte kortslutningsudløser Afhængigt af den anvendte kortslutningsudløser Afhængigt af den anvendte kortslutningsudløser se side 62, 82 og 370 se side 62, 88 og 370 se side 62, 92 og 370 se side 62, 176 og 370 se side 140 se side 146 se side 148 se side 146 se side 128 og 176 se side 128 og 184 se side 189 se side 133, 153 og 184 Inc: nominel betinget kortslutningsstrøm Værdien af den prospektive vekselstrøm, som en fejlstrømsafbryder beskyttede ved hjælp af en relevant serieforbundet SCPD (short-circuit protective device), der kan modstå belastningen under de angivne brugsforhold. IΔc: nominel fejlstrøm Værdien af den prospektive fejlstrøm, som en fejlstrømsafbryder beskyttede ved hjælp af en relevant serieforbundet SCPD (short-circuit protective device), der kan modstå belastningen under de angivne brugsforhold. Im: nominel fejlstrøm- og slutteevne Værdien af den prospektive vekselstrøm, som en fejlstrømsafbryder kan oprette eller afbryde under de angivne brugsforhold. IΔm: nominel fejlstrøm- og slutteevne Værdien af den prospektive fejlstrøm, som en fejlstrømsafbryder kan oprette og fastholde inden for dens åbningstid og afbryde under de angivne brugsforhold og med den angivne virkemåde. SCPD Beskyttelsesenhed mod kortslutninger (en sikring i forhold til vores markeringer): dette er den maksimale sikring, der kan bruges til at klare værdien Inc = IΔc

3 Beskyttelse mod lækstrøm til jord iid-fejlstrømsafbrydere med to klemmer (A-type) IEC/EN PB PB iid-fejlstrømsafbrydere med to terminalklemmer giver: personbeskyttelse mod elektrisk stød ved direkte kontakt ( 30 ma), personbeskyttelse mod elektrisk stød ved indirekte kontakt ( 100 ma), beskyttelse af installationer mod brandfare (300 ma). DB Katalognumre iid fejlstrømsafbrydere med to klemmer Type A Modulbredde= Produkt iid 9 mm Hjælpeenheder Kan acceptere hjælpeenheder, se side 176 og 178 2P Følsomhed 10 ma 30 ma 100 ma 100 ma s 300 ma 300 ma s 500 ma Mærke 16 A A9Z A A9Z20225 A9Z A9Z A - A9Z21240 A9Z A9Z24240 A9Z A - A9Z21263 A9Z A9Z24263 A9Z A A9Z21280 A9Z A9Z44280 A9Z A - A9Z21291 A9Z A9Z24291 A9Z DB P Følsomhed 10 ma 30 ma 100 ma 100 ma s 300 ma 300 ma s 500 ma Mærke 25 A - A9Z A9Z A9Z A - A9Z21440 A9Z A9Z24440 A9Z25440 A9Z A - A9Z21463 A9Z A9Z24463 A9Z25463 A9Z A - A9Z21480 A9Z22480 A9Z24480 A9Z25480 A9Z A - A9Z21491 A9Z22491 A9Z24491 A9Z25491 A9Z26491 Mærkespænding (Ue) 2P V 4P V Driftsfrekvens 50/60 Hz Tilbehør se side 128 og

4 Beskyttelse mod lækstrøm til jord iid-fejlstrømsafbrydere med to klemmer (SI-type) IEC/EN PB PB iid-fejlstrømsafbrydere med to terminalklemmer giver: personbeskyttelse mod elektrisk stød ved direkte kontakt ( 30 ma), personbeskyttelse mod elektrisk stød ved indirekte kontakt ( 100 ma), beskyttelse af installationer mod brandfare (300 ma). Si-typen giver større immunitet over for elektrisk interferens og forurenede eller ætsende miljøer. DB Katalognumre iid fejlstrømsafbrydere med to klemmer Type Si Modulbredde= Produkt iid 9 mm Hjælpeenheder Kan acceptere hjælpeenheder, se side 176 og 178 2P Følsomhed 10 ma 30 ma 100 ma 100 ma s 300 ma s Mærke 25 A A9Z30225 A9Z A - A9Z31240 A9Z A9Z A - A9Z31263 A9Z A9Z A A9Z31280 A9Z A9Z A A9Z31291 A9Z A9Z35291 DB P Følsomhed 10 ma 30 ma 100 ma 100 ma s 300 ma s Mærke 25 A - A9Z A - A9Z31440 A9Z A9Z A - A9Z31463 A9Z A9Z A - A9Z31480 A9Z A9Z A - A9Z31491 A9Z A9Z35491 Mærkespænding (Ue) 2P V 4P V Driftsfrekvens 50/60 Hz Tilbehør se side 128 og

5 Beskyttelse mod lækstrøm til jord Fejlstrømsafbryder type B, AC/DC PB101616_SE-35 PB IEC/EN 61008, VDE 0664 RCCB-ID type B fejlstrømsafbryderne giver: personbeskyttelse mod elektrisk stød ved direkte kontakt (30 ma), personbeskyttelse mod elektrisk stød ved indirekte kontakt ( 300 ma), beskyttelse af installationer mod brandfare (300 eller 500 ma). B-type RCCB-ID-fejlstrømsafbrydere af B-typen giver: beskyttelse i tilfælde af en kontinuerlig fejlstrøm i trefasenetværk forårsaget af: Frekvensomformer og drev med variable hastighed, batteriladere og omformere, strømforsyninger med back-up De omfatter og garanterer også beskyttelse mod fejlstrømme: sinusformede vekselfejlstrømme (AC-typen), pulserende DC-fejlstrømme (A-typen). PB De kan tilpasses til alle de anvendelsesformer, der er defineret i IEC og EN standarden. Schneider Electric garanterer, at RCCB-ID af B-typen fungerer korrekt i kombination med drev med variable hastighed produceret af Schneider Electric. OFsp-hjælpekontakt Elektrisk indikation: for OFsp-hjælpekontakt monteret til venstre. Den har en dobbelt omskifter, der indikerer den åbne eller lukkede position af RCCB-IB-afbryderen af B-typen. Tilbehør 4P plomberbar skrueafdækning. Katalognumre RCCB-ID fejlstrømsafbrydere af B-typen Type B Modulbredde=9 mm. DB P Følsomhed 30 ma 300 ma 300 ma s 500 ma Mærke 25 A A A A A Mærkespænding (Ue) Driftsfrekvens 230/400 V 50 Hz Hjælpeenhed Type OFsp-kontakt Kontakt Spænding Modulbredde=9 mm. E A 110 V DC A 230 V AC (AC15) Tilbehør Type Antal poler Skrueafdækning (sæt à 10) til upstream eller downstream 4P

6 Beskyttelse mod lækstrøm til jord Fejlstrømsafbryder type B, AC/DC DB Forbindelse Med terminalklemmer til: 11 mm 6,5 mm Type Tilspændingsmoment Kobberkabler Fast Bøjeligt eller forskruning PZ2 DB DB RCCB-ID af B-typen 3 N.m 1 x 1,5 to 50 mm 2 1 x 1,5 to 35 mm 2 2 x 1,5 to 16 mm 2 2 x 1,5 to 16 mm 2 OFsp 0,8 N.m 1 til 1,5 mm 2 1 til 1,5 mm 2 DB OFsp-kontaktstatus, afhængigt af fejlstrømsafbryderens position Type RCCB-ID Lukket - - B-type Åben - - Udløst - - ved fejl Kontakt 22/21 Åben Lukket Lukket OF sp 12/11 14/11 Lukket Åben Åben Indikering af status for fejlstrømsafbryderen af B-typen via 3-positionsomskifteren og feltet på frontpanelet Lukket (rød felt) Udløst ved fejl (grøn felt) Åben (grøn felt). Tekniske specifikationer Elektriske egenskaber Isoleringsspænding (Ui) 400 V Forureningsgrad 3 Nominel impulsholdespænding (Uimp) 4 kv Ifølge IEC/EN Indkoblings- og brydeevne 25/40 A 500 A (Im/IΔm) 63/80 A 800 A 125 A A Overstrømsmodstand Ingen selektiv s 250 A (8/20 μs) uden udkobling Selektiv s 3 ka Betinget nominel kortslutningsstrøm Følsomhed Maks. sikring type gl eller gg (Inc/IΔc) 25 A 25 A 100 ka 40 A 40 A 80 ka 63 A 63 A 30 ka 80 A 80 A 20 ka 125 A 125 A 10 ka Kontakt: dk-ts@schneider-electric.com for yderligere info. Yderligere egenskaber Beskyttelsesgrad Kun enhed IP20 IP40 med skrueafdækning Enhed i modulær afdækning IP40 Isolationsklasse II Holdbarhed (O-C) Elektrisk > (O-C) Mekanisk > (O-C) Driftstemperatur -25 C til +40 C Opbevaringstemperatur -40 C til +85 C Vægt (g) Fejlstrømsafbrydere og hjælpeudstyr Type RCCB-ID af B-typen OFsp 4P Mål (mm) DB122838, , 2P RCCB-ID af B-typen 4P OFsp-kontakt 77

7 Beskyttelse mod lækstrøm til jord Kombiafbryder idpn Vigi PB PB IEC/EN idpn Vigi-fejlstrømsenheden yder fuld beskyttelse til slutkredsløb (imod overstrøm og isoleringsfejl): personbeskyttelse af brugere mod elektrisk stød ved direkte kontakt ( 30 ma), personbeskyttelse af brugere mod elektrisk stød ved indirekte kontakt (300 ma), beskyttelse af installationerne mod brandfare (300 ma). idpn N Vigi idpn H Vigi Si-sortimentet er beregnet til at opretholde et netværk med optimal sikkerhed og driftskontinuitet i installationer, der forstyrres af: ekstreme atmosfæriske forhold, harmonisk genererende belastninger, transiente driftsstrømme. DB DB DB idpn N Vigi 6000 Type A Si Modulbredde = 9 mm. Hjælpeenheder Ekstern indikation og udkobling, se side 128 og 176 1P+N B-kurve Følsomhed 10 ma 30 ma 100 ma 300 ma 30 ma 100 ma 300 ma N 1 Mærkeværdi 4 A - A9D56604 A9D60604 A9D A - A9D56606 A9D60606 A9D (In) 10 A A9D08610 A9D56610 A9D60610 A9D A - A9D56613 A9D60613 A9D A A9D08616 A9D56616 A9D60616 A9D R 20 A - A9D56620 A9D60620 A9D A - A9D56625 A9D60625 A9D A - A9D56632 A9D60632 A9D N 2 40 A - A9D56640 A9D60640 A9D P+N C-kurve Følsomhed 10 ma 30 ma 100 ma 300 ma 30 ma 100 ma 300 ma N 1 Mærkeværdi 6 A - A9D32606 A9D52606 A9D42606 A9D33606 A9D53606 A9D A A9D02610 A9D32610 A9D52610 A9D42610 A9D33610 A9D53610 A9D43610 (In) 13 A - A9D32613 A9D52613 A9D42613 A9D33613 A9D53613 A9D A A9D02616 A9D32616 A9D52616 A9D42616 A9D33616 A9D53616 A9D A - A9D32620 A9D52620 A9D42620 A9D33620 A9D53620 A9D43620 R 25 A - A9D32625 A9D52625 A9D42625 A9D33625 A9D53625 A9D A - A9D32632 A9D52632 A9D42632 A9D33632 A9D53632 A9D43632 N 2 40 A - A9D32640 A9D52640 A9D42640 A9D33640 A9D53640 A9D43640 Mærkespænding (Ue) 230 V AC Driftsfrekvens 50Hz Tilbehør se side 140, 152, 176 og 180 for hjælpekontakt idpn H Vigi Type A Si Modulbredde = 9 mm. Hjælpeenheder Ekstern indikation og udkobling, se side 133 og 176 1P+N B-kurve Følsomhed 30 ma 300 ma 30 ma 300 ma R N 1 Mærke (In) 6 A A9D A A9D A A9D A A9D A A9D A A9D DB N 2 1P+N C-kurve Følsomhed 30 ma 300 ma 30 ma 300 ma N 1 Mærke 6 A A9D37606 A9D47606 A9D38606 A9D (In) 10 A A9D37610 A9D47610 A9D38610 A9D A A9D37616 A9D47616 A9D38616 A9D A A9D37620 A9D47620 A9D38620 A9D A A9D37625 A9D47625 A9D38625 A9D48625 R 32 A A9D37632 A9D47632 A9D38632 A9D48632 N 2 Mærkespænding (Ue) Driftsfrekvens Tilbehør 230 V AC 50 Hz se side 140, 152, 176 og 180 for hjælpekontakt 97

8 PB eps Vigicompact NSX100 to 630 circuit breakers with earth-leakage protection Addition of the Vigi module does not alter circuit-breaker characteristics: bbcompliance with standards bbdegree of protection, class II front-face insulation bbpositive contact indication bbelectrical characteristics bbtrip-unit characteristics bbinstallation and connection modes bbindication, measurement and control auxiliaries bbinstallation and connection accessories. Dimensions and weights NSX100/160/250 NSX400/630 Dimensions 3 poles 105 x 236 x x 355 x 110 W x H x D (mm) 4 poles 140 x 236 x x 355 x 110 Weight (kg) 3 poles poles PB eps DB eps Sensitivity setting 2 Time-delay setting (for selective earth-leakage protection). 3 Lead-seal fixture for controlled access to settings. 4 Test button simulating an earth-fault for regular checks on the tripping function 5 Reset button (reset required after earth-fault tripping). 6 Rating plate 7 Housing for SDV auxiliary contact. Plug-in devices The Vigi module can be installed on a plug-in base. Special accessories are required (see catalogue number chapter). Vigi earth-leakage protection modules Compliance with standards bbiec , annex B. bbdecree dated 14 November 1988 (for France). bbiec 60755, class A, immunity to DC components up to 6 ma. bboperation down to -25 C as per VDE 664. Remote indications Vigi modules may be equipped with an auxiliary contact (SDV) to remotely signal tripping due to an earth fault. Use of 4-pole Vigi module with a 3-pole Compact NSX In a 3-phase installation with an uninterrupted neutral, an accessory makes it possible to use a 4-pole Vigi module with connection of the neutral cable. Power supply Vigi modules are self-supplied internally by the distribution-system voltage and therefore do not require any external source. They continue to function even when supplied by only two phases. Vigi module selection Type Vigi ME Vigi MH Vigi MB Number of poles 3, 4 (1) 3, 4 (1) 3, 4 (1) NSX100 b b - NXS160 b b - NSX250 - b - NSX b NSX b Protection characteristics Sensitivity fixed adjustable adjustable IDn (A) Time delay fixed adjustable adjustable Intentional delay < (2) (2) (2) (ms) Max. break time < 40 < 40 < 140 < 300 < 800 < 40 < 140 < 300 < 800 (ms) Rated voltage V AC 50/60 Hz (1) Vigi 3P modules may also be used on 3P circuit breakers used for two-phase protection. (2) If the sensitivity is set to 30 ma, there is no time delay, whatever the time-delay setting. Operating safety The Vigi module is a user safety device. It must be tested at regular intervals (every 6 months) via test button. A-47

9 Vejledning til valg af materiel med fejlstrømsbeskyttelse 10kA Følgende komponenter kan benyttes: A B C Un: V/ V TT og TN systemer Brydere Relæ In Kombination NG125N Termomagnetisk A A/B/C* ( 63A iid) NG125L Termomagnetisk 10-80A A/B/C* ( 80A iid) NG160E/N/H Termomagnetisk A A/B NSX100 TM/Micrologic A A/B NSX160 TM/Micrologic A A/B NSX250 TM/Micrologic A A/B Kombiafbrydere Poler In Kombination idpn N Vigi (Clario) 1P+N/3P+N 1-40A A idpn N Vigi 1P+N 1-40A A DCP N 3P+N 1-32A A ic60n/h/l Vigi 1P+N/3P+N 0,5-63A A Fejlstrømsafbrydere Poler In Kombination iid fejlstrømsafbryder 2/ A B/C* Automatsikringer Poler In Kombination idpn N (Clario) 1P+N/3P+N 1-40A B idpn N 1P+N 1-40A B ic60n/h/l 1+N 4P 0,5-63A B/C* ( 63A iid) Forbindelser mellem niveau 2 og 3 fra afgangsklemmer på fejlstrømsafbryder til efterfølgende automatsikringer skal oplægges således, at kortslutning og jordslutning kan anses for udelukket. * For kombination C kan bryderen placeres enten i niveau 1 eller 3. Er den placeret i niveau 1, behøver forbindelsen mellem niveau 1 og 2 ikke at være udført som ovennævnte.

10 Vejledning til valg af materiel med fejlstrømsbeskyttelse 16kA Følgende komponenter kan benyttes: A B C Un: V/ V TT og TN systemer Brydere Relæ In Kombination NG125N Termomagnetisk A A/B/C* ( 40A iid) NG125L Termomagnetisk 10-80A A/B/C* ( 40A iid) NG160E/N/H Termomagnetisk A A/B NSX100 TM/Micrologic A A/B NSX160 TM/Micrologic A A/B NSX250 TM/Micrologic A A/B Kombiafbrydere Poler In Kombination idpn N Vigi (Clario) 1P+N/3P+N 1-40A A idpn N Vigi 1P+N 1-40A A DCP N 3P+N 1-16A A ic60n/h/l Vigi 1P+N/3P+N 0,5-63A A Fejlstrømsafbrydere Poler In Kombination iid fejlstrømsafbryder 2/ A B/C* Automatsikringer Poler In Kombination idpn N (Clario) 1P+N / 3P+N 1-16A B idpn N 1P+N 1-16A B ic60n 1P+N 4P 0,5-63A B ic60h/l 1P+N 4P 0,5-63A B/C* ( 63A iid) Forbindelser mellem niveau 2 og 3 fra afgangsklemmer på fejlstrømsafbryder til efterfølgende automatsikringer skal oplægges således, at kortslutning og jordslutning kan anses for udelukket. * For kombination C kan bryderen placeres enten i niveau 1 eller 3. Er den placeret i niveau 1, behøver forbindelsen mellem niveau 1 og 2 ikke at være udført som ovennævnte.

11 Vejledning til valg af materiel med fejlstrømsbeskyttelse 20kA Følgende komponenter kan benyttes: A B C Un: V/ V TT og TN systemer Brydere Relæ In Kombination NG125N Termomagnetisk A A/B NG125L Termomagnetisk 10-80A A/B/C * ( 40A iid) NG160N/H Termomagnetisk A A/B NSX100 TM/Micrologic A A/B NSX160 TM/Micrologic A A/B NSX250 TM/Micrologic A A/B Kombiafbrydere Poler In Kombination idpn N Vigi (Clario) 1P+N/3P+N 1-16A A idpn N Vigi (Clario) 1P+N/3P+N 20-40A A (kun med NG125L) idpn N Vigi 1P+N 1-16A A idpn N Vigi 1P+N 20-40A A (kun med NG125L) DCP N 3P + N 1-16A A (kun med NG125L) ic60n/h/l Vigi 1P+N/3P+N 0,5-63A A Fejlstrømsafbrydere Poler In Kombination iid fejlstrømsafbryder 2/ A B/C* Automatsikringer Poler In Kombination ic60n/h 1P+N 4P 0,5-40A B ic60l 1P+N 4P 0,5-40A B/C* ( 40A iid) Forbindelser mellem niveau 2 og 3 fra afgangsklemmer på fejlstrømsafbryder til efterfølgende automatsikringer skal oplægges således, at kortslutning og jordslutning kan anses for udelukket. * For kombination C kan bryderen placeres enten i niveau 1 eller 3. Er den placeret i niveau 1, behøver forbindelsen mellem niveau 1 og 2 ikke at være udført som ovennævnte.

12 Vejledning til valg af materiel med fejlstrømsbeskyttelse 25kA Følgende komponenter kan benyttes: A B C Un: V/ V TT og TN systemer Brydere Relæ In Kombination NG125N Termomagnetisk A A/B NG125L Termomagnetisk 10-80A A/B/C*( 25A iid) NG160N/H Termomagnetisk A A/B NSX100 TM/Micrologic A A/B NSX160 TM/Micrologic A A/B NSX250 TM/Micrologic A A Kombiafbrydere Poler In Kombination idpn N Vigi (Clario) 1P+N/3P+N 1-40A A (kun med NG125L) idpn N Vigi 1P+N 1-40A A (kun med NG125L) ic60n Vigi 1P+N/3P+N 0,5-63A A** ic60h/l Vigi 1P+N/3P+N 0,5-63A A Fejlstrømsafbrydere Poler In Kombination iid fejlstrømsafbryder 2/ A B/C* Automatsikringer Poler In Kombination ic60n/h 1P+N 4P 0,5-40A B ic60l 1P+N 4P 0,5-40A B/C* ( 25A iid) Forbindelser mellem niveau 2 og 3 fra afgangsklemmer på fejlstrømsafbryder til efterfølgende automatsikringer skal oplægges således, at kortslutning og jordslutning kan anses for udelukket. * For kombination C kan bryderen placeres enten i niveau 1 eller 3. Er den placeret i niveau 1, behøver forbindelsen mellem niveau 1 og 2 ikke at være udført som ovennævnte. ** Gælder ikke for NSX100/160/250B og NG160N.

13 Back-up tabeller Kombination A: RCBO Bryder NG125N NG125L NG160E NG160N/H In NS(X)100B/ F/N NS(X)160B/ F/N NS(X)250B/ F/N idpnn Vigi 1-16A idpnn Vigi 20-40A idpnn Vigi 1-16A idpnn Vigi 20-40A DCP N 1-16A DCP N 20-32A ic60n Vigi 0,5-63A /25 20/25/30 20/25/30 20/25/25 ic60h Vigi 0,5-63A ic60l Vigi 0,5-25A ic60l Vigi 32-40A ic60l Vigi 50-63A Kombination B & C: Foransiddende bryder Eftersiddende bryder Mærkestrøm Back-up NG125N/L idpn N/DPN N 1-16A 16 NG125N/L idpn N/DPN N 20-40A 10 NG160E/N/H idpn N/DPN N 1-16A 16 NG160E/N/H idpn N/DPN N 20-40A 10 NS(X)100/160/250 idpn N/DPN N 1-16A 16 NS(X)100/160/250 idpn N/DPN N 20-40A 10 NG125N/L ic60n/h/l 0,5-40A 25 NG125N/L ic60n/h/l 50-63A 16 NG160E ic60n/h/l 0,5-63A 16 NG160N/H ic60n/h/l 0,5-40A 25 NG160N/H ic60n/h/l 50-63A 16 NS(X)100/160 ic60n/h/l 0,5-40A 25 NS(X)100/160 ic60n/h/l 50-63A 16 NS(X)250 ic60n/h/l 0,5-40A 20 NS(X)250 ic60n/h/l 50-63A 16 - ic60n 0,5-63A 10 - ic60h 0,5-63A 16 - ic60l 0,5-63A 25(25A iid) 20(40A iid) 16(63A iid) NG125N (10-63A) (25-40A iid) 10(63A iid) NG125L (25A iid) 20(40A iid) 10(63-80A iid) NG160E/N/H NSX100/ Gælder for fejlstrømsafbrydere (iid) med en mærkestrøm på A, hvis andet ikke er angivet i tabellen. Schneider Electric Danmark A/S Industriparken Ballerup Tlf.: Bemærk at belastningsstrømmen igennem fejlstrømsafbryderen ikke må være større end dens mærkestrøm. Da standarder og produkter er under kontinuerlig udvikling, vil oplysninger i denne brochure ændres løbende. Schneider Electric/Lauritz Knudsen by Schneider Electric tager forbehold for disse ændringer samt trykfejl og mangler i øvrigt Kvik-fejlstrømsafbryder25kA Schneider Electric Danmark A/S - All rights reserved

14 Complementary technical information Earth leakage protection Routine operating checks Residual current devices are vital for the safety of people. That is why: b the electrical installation operation and maintenance standards require these protection devices to be tested at regular intervals, b the product standards IEC and IEC require such devices to be fitted with a test button (marked "T") on the front panel. The user can therefore check and be certain that the device is working correctly. The test button provides reliable information about how the device is working: tripping as soon as the button is pressed guarantees that the protection is working properly. If the device fails to trip, it must be examined to determine the cause of this malfunction. Example iid Example Vigi ic60 Test frequency The residual current devices must be tested as frequently as required by the installation regulations and/or the safety regulations currently in force. In the absence of any regulations, Schneider Electric recommends the test to be carried out: b after initial connection and any subsequent reconnection, b every years, for devices recently installed in good environmental conditions (no dust, corrosion, humidity, etc.), b every 3 months, for devices that have been in use for seven years or more in good environmental conditions, b every months, for devices used in corrosive or harsh environmental conditions or highly exposed to lightning strikes. The residual current device is powered on and the loads are connected. Procedure press the test button marked "T" on the front panel. Pressing the test button too long can seriously damage the device. The residual current device should trip instantly. If it fails to trip, the additional checks described below should be performed. residual current device back into service. CA908012E Version : /01/

15 Complementary technical information Earth leakage protection Routine operating checks Failure to trip during the test Failure to trip during the test is often due to a cause that is external to the residual current device. The table below shows the possible causes, the additional checks and tests to be carried out and the corrective actions to be taken, depending on the results. After a corrective action has been performed, repeat the test until a correct result is obtained. Cause of the malfunction Network frequency Network voltage Connection (three-pole or four-pole device) Additional test Check that the network frequency is the same as the frequency read on the device. Check that the mains voltage is the same as that indicated on the front face of the device. Measure the voltage between terminals: b 3 and 6 for iid b 4 and 6 for Vigi ic60. This voltage must be between 85 % and 110 % of the voltage indicated on the device. Load leakage currents Disconnect the loads and press the test button again A iid Vigi ic60 Incorrect test result If the network frequency is different, the Corrective actions The device must be checked by an external device (see below). b If the voltage measured is less than 85 % of that indicated on the device, the test button may not work, although the protection device will continue to function. b If the voltage measured is more than 110 % of the voltage indicated on the device there is a risk that the device will be destroyed. If the voltage measured is different from the rated voltage of the mains, look for the problem on the power supply or on the downstream circuits (lines, loads): b if the rated voltage of the mains is lower than that indicated on the device it must be replaced by a device with a suitable rated voltage the next time it is shut down b if the rated voltage of the mains is higher than the voltage indicated on the device it must immediately be replaced by a device with a suitable rated voltage. The incorrect voltage may be due to a connection error (e.g. phase/neutral inversion/missing phase, etc.). The Acti 9 three-pole and four-pole residual current devices cannot be used on single-phase circuits. The Acti 9 four-pole residual current devices can be used normally on three-phase circuits without neutral. Modify the connection to obtain the rated voltage (phase-phase) between terminals. If the device trips, the earth leakage protection is working correctly. Measure the permanent leakage current of each load. b in the event of abnormal load leakage, correct the insulation fault. b otherwise, separate the circuits to reduce the permanent leakage currents seen by each residual current device. If none of the additional tests indicate a fault, the residual current device is faulty. Checking with an external device (see below) will show whether or not it has to be replaced urgently. Test result Positive Negative Diagnosis b the earth leakage protection device is working Earth leakage protection is not working properly b the test circuit is faulty Corrective actions The residual current device must be replaced quickly (as soon as it is no longer being used). The residual current device must be replaced immediately 796 Version : /01/2017 CA908012E

16 Complementary technical information Earth leakage protection Routine operating checks Some tertiary and industrial installation safety regulations require residual current devices to be checked with a specific device. For the tests performed to be valid, these devices must comply with IEC These devices are used to check: b the operating voltage b device b pages CT6-1 and CT6-4. Procedure b power outlets). b Connect the test device to the downstream terminals of the residual current device or to a downstream power outlet. CA908012E Version : /01/

17 Complementary technical information Earth leakage protection Response time of high-sensitivity residual current devices 30 ma All the high-sensitivity residual current devices (30 ma) in the Acti 9 range conform to the IEC/EN and IEC/EN standards. The response times defined by these standards guarantee their effectiveness in protecting people against direct contacts. Response time The response time of a residual current device is the time between the appearance of a dangerous leakage current and circuit power down. Types AC, A, Si Fault current (ma) 15 ma No tripping 30 ma 300 ms 60 ma 150 ms 150 ma 40 ms Type B, DC leakage current Fault current (ma) 15 ma No tripping 60 ma 300 ms 120 ma 150 ms 300 ma 40 ms Maximum response time (ms) Maximum response time (ms) IEC/EN and IEC/EN (DC leakage current) standards. Residual current device They guarantee protection of people against direct contacts for the following reasons : b when a person comes into direct contact with a live conductor, the current passes directly through the human body, b this current, with the same magnitude, is detected by the residual current device. Zones AC-1 to -3 No danger Zone AC-4 Danger (IEC 60479) Response time maxi residual current devices 30 ma (IEC 61008/61009) C1 b The IEC technical report studies the sensitivity of the human body to the the current causes injury to a person. b Superimposing the two curves shows that the above response times protects the users. Measuring the response time If the user wishes to check the response time of his residual current devices, he b establish a leakage current of calibrated magnitude, b measure the exact response time. Procedure The measuring instruments must conform to IEC/EN Carry out the operations in the following order according to the safety instructions: b disconnect the loads, b install the measuring instrument downstream of the residual current device to be tested (for example on a power outlet), b perform the measurement. 798 Version : /01/2017 CA908013E

18 Complementary technical information Earth leakage protection Response time of medium-sensitivity residual current devices 100 ma ma Response time of ic60 Vigi and iid residual current devices The medium-sensitivity residual current devices ( ma) in the Acti 9 range conform to IEC/EN 61008, IEC/EN and IEC/EN (DC leakage current): b their response time guarantees personal protection against indirect contacts and b in the case of selective versions (S), a "non-tripping time" guarantees discrimination with the residual current devices installed downstream. Types AC, A, Si Residual current device Fault current (ma) Instantaneous residual current devices Sensitivity (I n) 100 ma 300 ma 500 ma I n/ No tripping Max. response time I n ms 2 x I n ms 5 x I n ms 500 A 40 ms Residual current device Selective (S) and time-delayed (R) residual current devices Sensitivity (I n) Type 100 ma 300 ma 500 ma 1000 ma Selective (S) Time-delayed (R) Fault I n/ No tripping No tripping current (ma) Non-tripping time Response time Non-tripping time Response time I n ms 500 ms 300 ms 1000 ms 2 x I n ms 200 ms 150 ms 500 ms 5 x I n ms 150 ms 150 ms 300 ms 500 A 40 ms 150 ms 150 ms 300 ms Type B, DC leakage current Residual current device Fault current (ma) Instantaneous residual current devices Sensitivity (I n) 300 ma 500 ma I n/ No tripping Max. response time 2 x I n ms 4 x I n ms 10 x I n ms 5 A A 40 ms Residual current device Fault current (ma) Selective (S) residual current devices Sensitivity (I n) 300 ma I n/2 150 No tripping Non-tripping time Response time 2 x I n ms 500 ms 4 x I n ms 200 ms 10 x I n ms 150 ms 5 A A 40 ms 150 ms Response time Time between the appearance of a hazardous leakage current and circuit power down. Non-tripping time For selective and time-delayed devices, the non-tripping time is the time between the appearance of a hazardous leakage current and the device tripping. If the leakage current disappears before this time, the device does not trip. This fast disappearance of the leakage current can be due to: b the transient nature of the fault (e.g. the current generated by a switching surge), b the interruption of the fault current by another faster residual current device situated downstream. Selective and time-delayed devices therefore afford the user: b better immunity against nuisance tripping, b total discrimination between residual current devices. CA908018E Version : /01/

19 Complementary technical information Earth leakage protection Response time of medium-sensitivity residual current devices 100 ma ma DB Uc Protection against indirect contacts The response times of residual current devices guarantee personal protection against indirect contacts, in conformance with the requirements of the installation standards (IEC or equivalent). Indirect contacts A person who comes into contact with an accidentally live frame caused by an insulation fault experiences an indirect contact: the contact voltage Uc creates a current that passes through the human body. Maximum breaking time The maximum breaking time required by the installation standards, in the event of an insulation fault, depends on: b the network voltage, b the earthing system. Maximum breaking time for terminating circuits (ms) Earthing Network phase/neutral voltage system V V V > 400 V TN or IT TT Note: a breaking time of no more than 5 s is permitted for distribution circuits to ensure discrimination with the devices installed on the terminating circuits. This time should be reduced to the essential minimum. DB L1 L2 L3 N PE These times are based on the maximum prospective values of the contact voltage Uc and on the contact times authorised by technical report IEC Example On a three-phase phase/neutral voltage network Uo = 230 V in a TT system: b b In the event of an insulation fault, the leakage current Id is equal to: Uo/ (RA + Rn) Rn = 10 Ω UA = 20 Ω Uc Protection sensitivity The residual current device must trip as soon as the leakage current corresponds to a hazardous situation, i.e. a contact voltage of 50 V (in a dry atmosphere). Neutral earth connection Operating frame earth connection Maximum breaking time For a 230 V phase/neutral voltage network in a TT system, the IEC standard requires a maximum breaking time of 200 ms. For the 2.1 A leakage current: v an instantaneous residual current device with a sensitivity of 300 ma will power down the circuit in less than 40 ms, v an instantaneous residual current device with a sensitivity of 500 ma will power down the circuit in less than 60 ms. Note: For well-designed and regularly maintained electrical installations, the resistance of Use of the time-delayed residual current devices In accordance with the breaking times required by the installation standards (above), the selective and time-delayed residual current devices can be used in the following cases: Circuit Terminating circuit Network voltage Residual current device (phase/neutral) Instantaneous I Selective S Time-delayed R y 230 V b b (1) > 230 V b Sub-distribution or general b b b (1) Only in a TN system for a phase/neutral voltage < 120 V. 800 Version : /01/2017 CA908018E

20 Complementary technical information Earth leakage protection Response time of medium-sensitivity residual current devices 100 ma ma DB Origin of the fire arcs in building materials, in the presence of moisture, dust, pollution, etc. These arcs appear and develop due to the wear and tear or ageing of the insulating milliamps for a few seconds. For fault currents of this magnitude, residual current devices with a sensitivity of 300 or 500 ma trip in less than a second, whether they be instantaneous, selective or time-delayed. Id < 300 ma Wet dust The response times of residual current devices with a sensitivity of 300 ma guarantee protection against fires generated by leakage currents IEC (subclause ) states that it is mandatory to install a residual current device with a sensitivity less than or equal to 500 ma: b on premises with a risk of explosion (BE3), b b in agricultural and horticultural buildings, b for circuits supplying fair, exhibition and entertainment equipment, b on temporary outdoor leisure facilities. In certain countries, the installation rules and/or local safety regulations require a sensitivity of 300 ma. CA908018E Version : /01/

21 Complementary technical information Earth leakage protection Response time of medium-sensitivity residual current devices 100 ma ma Discrimination of residual current devices The non-tripping times of type (S) and (R) residual current devices ensure discrimination with the residual current devices located downstream. Combination rules To ensure discrimination between two cascading residual current devices, the following two conditions must be met simultaneously: b the sensitivity of the upstream device must be at least 3 times the sensitivity of the downstream residual current device, b the upstream residual current device must be one of the following types: v Selective (S) if the downstream residual current device is instantaneous, v Time-delayed (R) if the downstream residual current device is selective (S). discrimination on three levels: whatever the value of the fault current, it will be interrupted by the device situated immediately upstream of the fault and only by this device. DB Time-delayed residual current device (R) 1000 ma Selective residual current device (S) 300 ma Instantaneous Selective (S) Time-delayed (R) Feeder 2 Feeder 1 Instantaneous residual current device 30 ma Example: In the above diagram for a fault current of 1000 ma: b if the fault occurs downstream of the 30 ma residual current device, the latter will interrupt the current in less than 40 ms, whereas type S and R devices "wait" for 80 ms and 200 ms respectively. Therefore, neither of the two devices trips, b if the fault occurs downstream of the type S residual current device, the latter will interrupt the current in less than 175 ms, whereas the type R device "wait" for 200 ms and therefore does not trip. If these cascading combination rules are complied with, the level of continuity of service provided to the user depends on the way in which the "horizontal discrimination" is implemented: the terminal feeders must be divided into as many circuits as necessary, each protected by a residual current device. 802 Version : /01/2017 CA908018E

22 Complementary technical information Electrical and electromagnetic interference Operation of earth leakage protection devices Some types of electrical and electromagnetic interference caused by the network or its environment may affect the operation of earth leakage protection devices and result in: b Nuisance tripping (tripping in a non-dangerous situation). Such tripping is often repetitive, which is highly detrimental to satisfying the user s energy requirements. b Risk of non-tripping in dangerous situations. This risk must be carefully of earth leakage protection devices according to their ability to control these types of situation. b The risk of interference must be taken into account when selecting earth leakage protection devices (see module CA902000), according to the loads supplied and the environment. b The explanations given below specify the main types of interference, their origin and how Schneider Electric s earth leakage protection devices respond, according to their type. DB Nuisance tripping This type of tripping is caused by the combination of two factors: b A transient or continuous high-frequency voltage that is superimposed on the normal network voltage (50 Hz). b The presence of capacitors between the electrical network and the earth (or frames). As these capacitors are exposed to a high-frequency voltage, a current The causes, duration and frequency spectra of such interference, which is often DB khz High-frequency harmonics The current absorbed by non-linear loads such as IT equipment power supplies, frequency converters, variable speed drive motor controls, electronic ballast lights, etc. includes high-order harmonics. and earth, or between the live parts of the devices and their frames), earth leakage protection devices may be tripped, although no danger is present. This risk of nuisance tripping is all the more likely to occur when a large number of identical loads are supplied in parallel and protected by the same earth leakage protection device. Low-frequency continuous leakage currents supply stage of electronic devices. Depending on the number of devices protected by the same earth leakage protection device, these leakage currents may: b Increase the risk of tripping in the event of high-frequency interference. b Cause frequent tripping To guarantee satisfactory operation, these continuous leakage currents must not the number of interfering loads protected by the same earth leakage protection device. b If more accurate data is unavailable, the leakage current can be estimated on the following basis, for a 230 V, 50 Hz network: v v fax, printer: 1 ma, v PC, workstation: 2 ma, v photocopier: 1.5 ma. If long cables are installed downstream of the earth leakage protection devices, it may be necessary to take the natural capacitance formed by the cable/earth pair into account (order of magnitude: at 230 V, approximately 1.5 ma for 100 m). CA908015E Version : /01/

23 Back-up table for residual current devices with fuses Un: 230/400V TT and TN earthing systems Upstream Fuses, type gg Downstream In(A) Combined breaking capacity (ka) idpnn Vigi (Clario) & idpnn Vigi idpnn Vigi (Clario) & idpnn Vigi idpnn Vigi (Clario) & idpnn Vigi idpnn Vigi (Clario) & idpnn Vigi idpnn Vigi (Clario) & idpnn Vigi idpnn Vigi (Clario) & idpnn Vigi DCPN Vigi ID 2 & 4-pole ID 2 & 4-pole The fuse can be placed either upstream or downstream of the residual current device. If it is placed downstream the connection between the residual current device and the fuse must be installed so that a short-circuit or earth fault can be ruled out. Please note that the RCCB s have to be protected against overload situation. Schneider Electric Danmark A/S Industriparken Ballerup Phone: As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein Kvik-Back-up for residual current devices with fuses_eng Schneider Electric Danmark A/S - All rights reserved

Vejledning til valg af materiel med fejlstrømsbeskyttelse 10kA

Vejledning til valg af materiel med fejlstrømsbeskyttelse 10kA Vejledning til valg af materiel med fejlstrømsbeskyttelse 0kA Un: 0-40V/80-45V TT og TN systemer NG5N Termomagnetisk 0-5A A/B/* ( 6A ID) NG5L Termomagnetisk 0-80A A/B/* ( 80A ID) NG60E/N/H Termomagnetisk

Læs mere

Kortslutningsbeskyttelse af fejlstrømsafbrydere foransiddende: C60, C120, NG125 automatsikringer eller sikringer efterfølgende: fejlstrømsafbryder

Kortslutningsbeskyttelse af fejlstrømsafbrydere foransiddende: C60, C120, NG125 automatsikringer eller sikringer efterfølgende: fejlstrømsafbryder Kortslutningsbeskyttelse af fejlstrømsafbrydere foransiddende: C60, C120, NG125 automatsikringer eller sikringer efterfølgende: fejlstrømsafbryder Installationsanvisninger Fejlstrømsafbryder En fejlstrømsafbryder

Læs mere

Acti 9. Hovedkatalog 2012. Fejlstrømsafbrydere

Acti 9. Hovedkatalog 2012. Fejlstrømsafbrydere Acti 9 Hovedkatalog 2012 Fejlstrømsafbrydere Beskyttelse mod lækstrøm til jord Valg af fejlstrømsafbrydere Valg af følsomhed Følsomheden på fejlstrømsafbryderen afhænger hovedsageligt af funktionen den

Læs mere

Acti 9. Hovedkatalog 2012. Automatsikringer

Acti 9. Hovedkatalog 2012. Automatsikringer Acti 9 Hovedkatalog 0 Automatsikringer Valg af beskyttelsesenheder til kredsløb Kortslutningsudløsere kan: - beskytte imod ildebrand, der kan forårsages af et fejlbehæftet elektrisk kredsløb (kortslutning,

Læs mere

TDC 4 Indoor voltage transformers

TDC 4 Indoor voltage transformers Medium Voltage Product TDC 4 Indoor voltage transformers Highest voltage for equipment [kv] 3.6-12 Power frequency test voltage, 1 min. [kv] 10 - Lightning impulse test voltage [kv] Max. rated burden,

Læs mere

50 (0,5 til 4 A) 50 (0,5 til 4 A) 70 (0,5 til 4 A) 50 (0,5 til 4 A) 10 (6 til 63 A) 50 (0,5 til 4 A) 10 (6 til 63 A) 25 (0,5 til 4 A) 6 (6 til 63 A)

50 (0,5 til 4 A) 50 (0,5 til 4 A) 70 (0,5 til 4 A) 50 (0,5 til 4 A) 10 (6 til 63 A) 50 (0,5 til 4 A) 10 (6 til 63 A) 25 (0,5 til 4 A) 6 (6 til 63 A) Oversigt over er Beskyttelse med Oversigt over er Udvælgelsesvejledning Automatsikringer Type idpn N ik0n ic0n ic0h ic0l Standard IEC/EN 09- IEC/EN 09- Kvalitetsmærke International standard International

Læs mere

Fremtiden inden for boligtavler i hjemmet. Resi9, den forbundne el-tavle til dit hjem. lk.dk/resi9 eller schneider-electric.

Fremtiden inden for boligtavler i hjemmet. Resi9, den forbundne el-tavle til dit hjem. lk.dk/resi9 eller schneider-electric. Fremtiden inden for boligtavler i hjemmet Resi9, den forbundne el-tavle til dit hjem lk.dk/resi9 eller schneider-electric.dk/resi9 Ny serie tavlekomponenter udviklet specielt til boliger Schneider Electric

Læs mere

Acti 9. Hovedkatalog 2012. Lastadskillere

Acti 9. Hovedkatalog 2012. Lastadskillere Acti 9 Hovedkatalog 01 Lastadskillere Lokal kontrol isw-omskiftere DB1818 PB10566-40 Indikation af positionskontakt Egnethed til industriel isolering ifølge IEC/EN 60947-3-standarden. Det grønne felt garanterer

Læs mere

WIO200A Water in oil sensor

WIO200A Water in oil sensor WIO200A Water in oil sensor Datasheet 111688-900 Rev. 1.03 Dato: 2012-06-01 03-01-0501-CRJ-04 Side 1 af 13 Technical Sensor Data Order Order number A01-110-0101-01 Output Analogue output 4 20 ma (galvanic

Læs mere

Acti 9 Hovedkatalog 2012. Transient beskyttelse

Acti 9 Hovedkatalog 2012. Transient beskyttelse Acti 9 Hovedkatalog 2012 Transient beskyttelse iprf1 12,5r/PRF1 Master/ PRD1 25r/PRD1 Master Type 1 og 2 LV overspændingsbeskyttere Type 1-sortimentet af overspændingsbeskyttere overholder den normerede

Læs mere

Varenr.: 553925 90 højre 553926 90 venstre 554027 90º højre med coating 554028 90º venstre med coating

Varenr.: 553925 90 højre 553926 90 venstre 554027 90º højre med coating 554028 90º venstre med coating DK GH Skiftespor Varenr.: 55395 90 højre 55396 90 venstre 55407 90º højre med coating 55408 90º venstre med coating 553991 60º højre 553995 60º venstre 551058 60º højre med coating 551059 60º venstre med

Læs mere

Acti 9. Den effektivitet, du fortjener. Hovedkatalog 2012

Acti 9. Den effektivitet, du fortjener. Hovedkatalog 2012 Acti 9 Den effektivitet, du fortjener Hovedkatalog 2012 Indholdsfortegnelse Princip for katalognumre... 5 Valg af beskyttelsesenheder til kredsløb... 6 Oversigt over kortslutningsudløsere... 8 idpn-kortslutningsudløsere

Læs mere

Bilag 8. TDC technical requirements for approval of splitterfilters and inline filters intended for shared access (ADSL or VDSL over POTS).

Bilag 8. TDC technical requirements for approval of splitterfilters and inline filters intended for shared access (ADSL or VDSL over POTS). Bilag 8. TDC technical requirements for approval of splitters and inline s intended for shared access (ADSL or VDSL over POTS). Dette bilag udgør bilag 8 til det mellem parterne tiltrådte Produkttillæg

Læs mere

H07RN-F CPR BESKRIVELSE STANDARDER. Kontakter Installation Tlf.: Support:

H07RN-F CPR BESKRIVELSE STANDARDER. Kontakter Installation Tlf.: Support: Industrial flexible rubber cable range with an insulation and sheath in elastomers. Cables for heavy duty uses, Oil resistant and Flame retardancy according to IEC/EN 60332-1-2 standard. BESKRIVELSE Application

Læs mere

UNISONIC TECHNOLOGIES CO.,

UNISONIC TECHNOLOGIES CO., UNISONIC TECHNOLOGIES CO., 3 TERMINAL 1A NEGATIVE VOLTAGE REGULATOR DESCRIPTION 1 TO-263 The UTC series of three-terminal negative regulators are available in TO-263 package and with several fixed output

Læs mere

Constant Terminal Voltage. Industry Workshop 1 st November 2013

Constant Terminal Voltage. Industry Workshop 1 st November 2013 Constant Terminal Voltage Industry Workshop 1 st November 2013 Covering; Reactive Power & Voltage Requirements for Synchronous Generators and how the requirements are delivered Other countries - A different

Læs mere

ATEX direktivet. Vedligeholdelse af ATEX certifikater mv. Steen Christensen stec@teknologisk.dk www.atexdirektivet.

ATEX direktivet. Vedligeholdelse af ATEX certifikater mv. Steen Christensen stec@teknologisk.dk www.atexdirektivet. ATEX direktivet Vedligeholdelse af ATEX certifikater mv. Steen Christensen stec@teknologisk.dk www.atexdirektivet.dk tlf: 7220 2693 Vedligeholdelse af Certifikater / tekniske dossier / overensstemmelseserklæringen.

Læs mere

R9H R9H R9H R9H R9H R9H R9H13303

R9H R9H R9H R9H R9H R9H R9H13303 Resi9 en da R9H84 - R9H84 - R9H84 - R9H844 - R9H0 - R9H0 - R9H0 IP0 NVE5695 http://tv.schneider-electric.com This service guide must be kept for future use. PLEASE NOTE bbthis equipment should be installed,

Læs mere

MS-H280-Pro Magnetic Stirrer

MS-H280-Pro Magnetic Stirrer MS-H280-Pro Magnetic Stirrer www..com Copyright: No part of this manual may be reproduced or transmitted without prior written permission of. VERSION201407 CONTENTS Chapter 1: Working Principle... 3 1

Læs mere

Bilag 1 GPS dataudskrifter fra Stena Carisma ved passage af målefelt

Bilag 1 GPS dataudskrifter fra Stena Carisma ved passage af målefelt Bilag 1 GPS dataudskrifter fra Stena Carisma ved passage af målefelt Passage 1 Passage 2 Passage 3 Passage 4 Passage 5 27 Bilag 2 Engelsk beskrivelse af S4-måleren InterOcean S4 Current Meter The S4 Electromagnetic

Læs mere

Portal Registration. Check Junk Mail for activation . 1 Click the hyperlink to take you back to the portal to confirm your registration

Portal Registration. Check Junk Mail for activation  . 1 Click the hyperlink to take you back to the portal to confirm your registration Portal Registration Step 1 Provide the necessary information to create your user. Note: First Name, Last Name and Email have to match exactly to your profile in the Membership system. Step 2 Click on the

Læs mere

Technical Specifications

Technical Specifications Technical Specifications Pressure measuring range (bar) 0.1... 0.5, (1) > 0.5... 2 > 2... 25 Overpressure 3 bar 3 x FS ( 3 bar) 3 x FS Burst pressure > 200 bar > 200 bar > 200 bar Accuracy, (5), (± % FS)

Læs mere

ME6212. High Speed LDO Regulators, High PSRR, Low noise, ME6212 Series. General Description. Typical Application. Package

ME6212. High Speed LDO Regulators, High PSRR, Low noise, ME6212 Series. General Description. Typical Application. Package High Speed LDO Regulators, High PSRR, Low noise, Series General Description The series are highly accurate, low noise, CMOS LDO Voltage Regulators. Offering low output noise, high ripple rejection ratio,

Læs mere

Project Step 7. Behavioral modeling of a dual ported register set. 1/8/ L11 Project Step 5 Copyright Joanne DeGroat, ECE, OSU 1

Project Step 7. Behavioral modeling of a dual ported register set. 1/8/ L11 Project Step 5 Copyright Joanne DeGroat, ECE, OSU 1 Project Step 7 Behavioral modeling of a dual ported register set. Copyright 2006 - Joanne DeGroat, ECE, OSU 1 The register set Register set specifications 16 dual ported registers each with 16- bit words

Læs mere

Davo-Meg 1002 & 1002B Dansk manual Side 3-5 English user manual Page 6-8

Davo-Meg 1002 & 1002B Dansk manual Side 3-5 English user manual Page 6-8 Davo-Meg 1002 & 1002B Dansk manual Side 3-5 English user manual Page 6-8 DK: Davo-Meg 1002: 87 98 301 819 Davo-Meg 1002B: 87 98 301 822 EAN: Davo-Meg 1002: 5703534100059 Davo-Meg 1002B: 5703534100202 Indhold

Læs mere

ELECTRONIC CONTROL BOX 20-0344

ELECTRONIC CONTROL BOX 20-0344 ELECTRONIC CONTROL BOX 20-0344 Specifications Rated voltage: Rated power: Rated current: Pump load: Blower (aux) load: Light load: Heater load: 400V, 50 Hz 11000 W 3 x 16 A Max. 3 x 3000 W Total sum of

Læs mere

WIO200A INSTALLATIONS MANUAL Rev Dato:

WIO200A INSTALLATIONS MANUAL Rev Dato: WIO200A INSTALLATIONS MANUAL 111686-903 Rev. 1.01 Dato: 10.01.2013 Side 1 af 14 Contents Contents... 2 Introduction... 3 Pin assignment of the terminal box connector for customer... 4 Pin assignment of

Læs mere

TM4 Central Station. User Manual / brugervejledning K2070-EU. Tel Fax

TM4 Central Station. User Manual / brugervejledning K2070-EU. Tel Fax TM4 Central Station User Manual / brugervejledning K2070-EU STT Condigi A/S Niels Bohrs Vej 42, Stilling 8660 Skanderborg Denmark Tel. +45 87 93 50 00 Fax. +45 87 93 50 10 info@sttcondigi.com www.sttcondigi.com

Læs mere

DIVAR VIGTIGT! / IMPORTANT! MÅL / DIMENSIONS. The DIVAR wall lamp comes standard. with 2.4 m braided cord and a plug in power supply (EU or UK).

DIVAR VIGTIGT! / IMPORTANT! MÅL / DIMENSIONS. The DIVAR wall lamp comes standard. with 2.4 m braided cord and a plug in power supply (EU or UK). DIVAR VIGTIGT! / IMPORTANT! VIGTIGT læs vores anvisninger før du bruger produktet. Har du problemer med den elektriske installation, skal du kontakte en elektriker. Sørg for at altid slukke for strømmen

Læs mere

Programmable pressure transmitters PTM

Programmable pressure transmitters PTM Programmable pressure transmitters PTM Version: 07.01.2016 Technical Specifications Pressure measuring range (bar) 0.1... 0.5 > 0.5... 2 > 2... 25 Overpressure 3 bar 3 x FS ( 3 bar) 3 x FS Burst pressure

Læs mere

Clear aim to ensure safety of all people involved in optical links project Scope

Clear aim to ensure safety of all people involved in optical links project Scope Laser Safety Outline Clear aim to ensure safety of all people involved in optical links project Scope Hazard classification of CMS Tracker readout link system Requirements Note: Safety requirements here

Læs mere

Elektriske apparater til husholdningsbrug o.l. Sikkerhed Del 1: Generelle krav

Elektriske apparater til husholdningsbrug o.l. Sikkerhed Del 1: Generelle krav Dansk standard Tillæg DS/IEC 60335-1/A1:2013 + Corr 1:2014 1. udgave 2014-05-08 Elektriske apparater til husholdningsbrug o.l. Sikkerhed Del 1: Generelle krav Household and similar electrical appliances

Læs mere

BRUGERVEJLEDNING TIL REVOLTA TRANSFORMER 2-WAY VOLTAGE TRANSFORMER USER MANUAL RV-2400

BRUGERVEJLEDNING TIL REVOLTA TRANSFORMER 2-WAY VOLTAGE TRANSFORMER USER MANUAL RV-2400 BRUGERVEJLEDNING TIL REVOLTA TRANSFORMER 2-WAY VOLTAGE TRANSFORMER USER MANUAL RV-2400 BETJENINGSVEJLEDNING 1. Vigtigt: Før du tilslutter spændingstransformerne til stikkontakten i dit hjem, skal du sørge

Læs mere

RE7TP13BU ZELIO tidsrelæ justerbar forsinket indkobling - 0,05..1 sek V AC/DC - 2OC

RE7TP13BU ZELIO tidsrelæ justerbar forsinket indkobling - 0,05..1 sek V AC/DC - 2OC Produkt datablad Karakteristika RE7TP13BU ZELIO tidsrelæ justerbar forsinket indkobling - 0,05..1 sek. - 24 V AC/DC - 2OC Primær Produktsortiment Zelio Time Produkttype Industrial timing relay Kontaktype

Læs mere

22.00 AutomAtiske Afbrydere og AUTOMATISKE AFBRYDERE/ KOBLINGSMATERIEL. koblingssmateriel BENEDICT MAKSIMALAFBRYDERE M4

22.00 AutomAtiske Afbrydere og AUTOMATISKE AFBRYDERE/ KOBLINGSMATERIEL. koblingssmateriel BENEDICT MAKSIMALAFBRYDERE M4 22.00 AUTOMATISKE AFBRYDERE/ KOBLINGSMATERIEL BENEDICT MAKSIMALAFBRYDERE M4 BENEDICT MAKSIMALAFBRYDERE M4 22.00 AutomAtiske Afbrydere og koblingssmateriel 1 Motorværnindsatse Varenr. M4-32T Indsatse EAN-nr.

Læs mere

United Nations Secretariat Procurement Division

United Nations Secretariat Procurement Division United Nations Secretariat Procurement Division Vendor Registration Overview Higher Standards, Better Solutions The United Nations Global Marketplace (UNGM) Why Register? On-line registration Free of charge

Læs mere

EASYLINE CV 48 V. LED Drivers CV. EasyLine 48 V C-L , Typical Applications Shop lighting for 48 V systems Furniture lighting

EASYLINE CV 48 V. LED Drivers CV. EasyLine 48 V C-L , Typical Applications Shop lighting for 48 V systems Furniture lighting LED Drivers CV EASYLINE CV 48 V EasyLine 48 V C-L 186691, 186692 Typical Applications Shop lighting for 48 V systems Furniture lighting EasyLine 48 V C-L VERY COMPACT SHAPE VERY LOW RIPPLE CURRENT POWER

Læs mere

Help / Hjælp

Help / Hjælp Home page Lisa & Petur www.lisapetur.dk Help / Hjælp Help / Hjælp General The purpose of our Homepage is to allow external access to pictures and videos taken/made by the Gunnarsson family. The Association

Læs mere

Engelsk. Niveau D. De Merkantile Erhvervsuddannelser September Casebaseret eksamen. og

Engelsk. Niveau D. De Merkantile Erhvervsuddannelser September Casebaseret eksamen.  og 052431_EngelskD 08/09/05 13:29 Side 1 De Merkantile Erhvervsuddannelser September 2005 Side 1 af 4 sider Casebaseret eksamen Engelsk Niveau D www.jysk.dk og www.jysk.com Indhold: Opgave 1 Presentation

Læs mere

Aktivering af Survey funktionalitet

Aktivering af Survey funktionalitet Surveys i REDCap REDCap gør det muligt at eksponere ét eller flere instrumenter som et survey (spørgeskema) som derefter kan udfyldes direkte af patienten eller forsøgspersonen over internettet. Dette

Læs mere

LED STAR PIN G4 BASIC INFORMATION: Series circuit. Parallel circuit. www.osram.com 1. HOW CAN I UNDERSTAND THE FOLLOWING SHEETS?

LED STAR PIN G4 BASIC INFORMATION: Series circuit. Parallel circuit. www.osram.com 1. HOW CAN I UNDERSTAND THE FOLLOWING SHEETS? BASIC INFORMATION: 1. HOW CAN I UNDERSTAND THE FOLLOWING SHES? Compatibility to OSRAM s: -Series Circuit... Page 2 -Parallel Circuit... Page 3 Compatibility to OTHER s : -Series Circuit... Page 4 -Parallel

Læs mere

Hi-Res Audio/DNC Headset MDR-NC750

Hi-Res Audio/DNC Headset MDR-NC750 Brugervejledning Hi-Res Audio/DNC Headset MDR-NC750 Indholdsfortegnelse Introduktion... 3 Introduktion...3 Oversigt... 3 De grundlæggende funktioner... 4 Sådan bærer du headsettet... 4 Tilslutning af dit

Læs mere

MultiProgrammer Manual

MultiProgrammer Manual MultiProgrammer Manual MultiProgrammeren bruges til at læse og skrive værdier til ModBus register i LS Controls frekvensomformer E 1045. Dansk Version side 2 til 4 The MultiProgrammer is used for the writing

Læs mere

SmartDock for Xperia ion Brugervejledning

SmartDock for Xperia ion Brugervejledning SmartDock for Xperia ion Brugervejledning Indholdsfortegnelse Indledning...3 Oversigt over SmartDock...3 Opladning med SmartDock...3 Kom godt i gang...5 LiveWare -administration...5 Opgradering af LiveWare

Læs mere

Sikkerhedsvejledning

Sikkerhedsvejledning 11-01-2018 2 Sikkerhedsvejledning VIGTIGT! Venligst læs disse instruktioner inden sengen samles og tages i brug Tjek at alle dele og komponenter er til stede som angivet i vejledningen Fjern alle beslagsdele

Læs mere

frame bracket Ford & Dodge

frame bracket Ford & Dodge , Rev 3 02/19 frame bracket 8552005 Ford & Dodge ITEM PART # QTY DESCRIPTION 1 00083 8 NUT,.50NC HEX 2 00084 8 WASHER,.50 LOCK 3 14189-76 2 FRAME BRACKET 4 14194-76 1 411AL FRAME BRACKET PASSENGER SIDE

Læs mere

Brugervejledning. MHL to HDMI Adapter IM750

Brugervejledning. MHL to HDMI Adapter IM750 Brugervejledning MHL to HDMI Adapter IM750 Indholdsfortegnelse Indledning...3 Oversigt over MHL to HDMI Adapter...3 Kom godt i gang...4 Smart Connect...4 Opgradering af Smart Connect...4 Brug af MHL to

Læs mere

DIVAR VIGTIGT! / IMPORTANT! MÅL / DIMENSIONS

DIVAR VIGTIGT! / IMPORTANT! MÅL / DIMENSIONS DIVAR VIGTIGT! / IMPORTANT! VIGTIGT læs vores anvisninger før du bruger produktet. Har du problemer med den elektriske installation, skal du kontakte en elektriker. Sørg for at altid slukke for strømmen

Læs mere

Lithium-Ion Jump-Starters / Jumper Cables

Lithium-Ion Jump-Starters / Jumper Cables AUTOMOTIVE Lithium-Ion Jump-Starters / Jumper Cables Lithium-Ion Jump-Starter 1300: Part No. DRLJS130 1300 4 6 8 cylinder (6 liter gas 3 liter diesel) SafeJump technology prevents sparking and protects

Læs mere

ELECTRONIC CONTROL BOX 20-0313

ELECTRONIC CONTROL BOX 20-0313 ELECTRONIC CONTROL BOX 20-0313 Specifications Rated voltage: Rated power: Rated current: Output A: Output B: Output C: 230VAC, 50Hz, single phase 2300W 10 A Max. 900W The total sum of the loads must not

Læs mere

Date of issue Fremstillingsdato. Machine no , Maskinnr. ALSCO SAN DIEGO

Date of issue Fremstillingsdato. Machine no , Maskinnr. ALSCO SAN DIEGO JENSEN CLASSIC FOLDER JENSEN MAX STACKER MANUAL MANUAL Date of issue 2005.11.04 Fremstillingsdato Machine no. 760790, 492147 Maskinnr. Distributor / Forhandler Project Manufacturer / Fabrikant JENSEN USA

Læs mere

GV3P18 TeSys GV3 motorværn A

GV3P18 TeSys GV3 motorværn A Produkt datablad Karakteristika GV3P18 TeSys GV3 motorværn - 12 18A Primær Sortiment Produktnavn Enhedens korte navn Produkttype Enhedens anvendelse Udløserteknologi TeSys TeSys GV3 GV3P Maksimalafbryder

Læs mere

DANSK INSTALLATIONSVEJLEDNING VLMT500 ADVARSEL!

DANSK INSTALLATIONSVEJLEDNING VLMT500 ADVARSEL! DANSK INSTALLATIONSVEJLEDNING VLMT500 Udpakningsinstruktioner Åben indpakningen forsigtigt og læg indholdet på et stykke pap eller en anden beskyttende overflade for at undgå beskadigelse. Kontroller at

Læs mere

RE7RL13BU ZELIO tidsrelæ forsinket frafald - 0,05..1 sek V AC/DC - 2OC

RE7RL13BU ZELIO tidsrelæ forsinket frafald - 0,05..1 sek V AC/DC - 2OC Produkt datablad Karakteristika RE7RL13BU ZELIO tidsrelæ forsinket frafald - 0,05..1 sek. - 24 V AC/DC - 2OC Primær Produktsortiment Zelio Time Produkttype Industrial timing relay Kontaktype og sammensætning

Læs mere

Screened electronic cable LiYCY

Screened electronic cable LiYCY Screened electronic cable LiYCY Conductor material: copper, bare Conductor class: class 5 = fine stranded Insulation: PVC Screen: copper braid, tinned Screen coverage: 70 % Sheathing material: PVC Flame-retardant:

Læs mere

Slot diffusers. Slot diffusers LD-17, LD-18

Slot diffusers. Slot diffusers LD-17, LD-18 LD-17, LD-18 Application LD-17 and LD-18 are designed for supply of cold or warm air in rooms with a height between. m and 4 m. They allow easy setting of air deflectors for different modes of operation

Læs mere

Brugervejledning. Xperia P TV Dock DK21

Brugervejledning. Xperia P TV Dock DK21 Brugervejledning Xperia P TV Dock DK21 Indholdsfortegnelse Indledning...3 Bagside oversigt over TV Dock...3 Kom godt i gang...4 Håndtering af LiveWare...4 Opgradering af Håndtering af LiveWare...4 Brug

Læs mere

Xperia TX TV Dock DK22 Xperia T TV Dock DK23

Xperia TX TV Dock DK22 Xperia T TV Dock DK23 Brugervejledning Xperia TX TV Dock DK22 Xperia T TV Dock DK23 Indholdsfortegnelse Indledning...3 Oversigt over TV Dock...3 Kom godt i gang...4 Smart Connect...4 Opgradering af Smart Connect...4 Brug af

Læs mere

Unitel EDI MT940 June 2010. Based on: SWIFT Standards - Category 9 MT940 Customer Statement Message (January 2004)

Unitel EDI MT940 June 2010. Based on: SWIFT Standards - Category 9 MT940 Customer Statement Message (January 2004) Unitel EDI MT940 June 2010 Based on: SWIFT Standards - Category 9 MT940 Customer Statement Message (January 2004) Contents 1. Introduction...3 2. General...3 3. Description of the MT940 message...3 3.1.

Læs mere

RAVE. The New Radar Motion Sensor Rated IP67: Optimized for Harsh Outdoor Applications

RAVE. The New Radar Motion Sensor Rated IP67: Optimized for Harsh Outdoor Applications RAVE The New Radar Motion Sensor Rated IP67: Optimized for Harsh Outdoor Applications Product Presentation RAVE radar motion sensor In addition to the RaDec and RMS product families, the new RAVE radar

Læs mere

Acti 9 Hovedkatalog 2012. Funktions tilbehør

Acti 9 Hovedkatalog 2012. Funktions tilbehør Acti 9 Hovedkatalog 2012 Funktions tilbehør Relæer Transmittering af tidsforsinkelser anvendes i servicesektoren og industribygninger til små automatiske kontrolsystemer: ventilation, opvarmning, animering,

Læs mere

Filtering on Wires Cable Ferrites, Usage & Comparison Alex Snijder Field Application Engineer Wurth Elektronik Nederland B.V.

Filtering on Wires Cable Ferrites, Usage & Comparison Alex Snijder Field Application Engineer Wurth Elektronik Nederland B.V. Filtering on Wires Cable Ferrites, Usage & Comparison Alex Snijder Field Application Engineer Wurth Elektronik Nederland B.V. Agenda Electromagnetic Compatibility (EMC) Application of Cable Ferrites Impedance

Læs mere

Product. Information. A. u. K. Müller. 2/2-way Drain Valve NC, DN 40. Series Characteristics. Possible approvals

Product. Information. A. u. K. Müller. 2/2-way Drain Valve NC, DN 40. Series Characteristics. Possible approvals Solenoid valves Control valves Special valves and systems GmbH & Co. KG Dresdener Str. 162 D-40595 Düsseldorf/Germany Tel.: +49(0)1-73-0 Fax: +49(0)1-73-281 e-mail: info@akmueller.de Internet: www.akmueller.de

Læs mere

RE7ML11BU ZELIO tidsrelæ forsinket med 6 funktioner - 0,05..1 sek V AC/DC - 1OC

RE7ML11BU ZELIO tidsrelæ forsinket med 6 funktioner - 0,05..1 sek V AC/DC - 1OC Produkt datablad Karakteristika RE7ML11BU ZELIO tidsrelæ forsinket med 6 funktioner - 0,05..1 sek. - 24 V AC/DC - 1OC Primær Produktsortiment Produkttype Type nr. Tidsforsinkelsestype Tidsforsinkelsesområde

Læs mere

Wander TDEV Measurements for Inexpensive Oscillator

Wander TDEV Measurements for Inexpensive Oscillator Wander TDEV Measurements for Inexpensive Oscillator Lee Cosart Symmetricom Lcosart@symmetricom.com Geoffrey M. Garner SAMSUNG Electronics (Consultant) gmgarner@comcast.net IEEE 802.1 AVB TG 2009.11.02

Læs mere

Privat-, statslig- eller regional institution m.v. Andet Added Bekaempelsesudfoerende: string No Label: Bekæmpelsesudførende

Privat-, statslig- eller regional institution m.v. Andet Added Bekaempelsesudfoerende: string No Label: Bekæmpelsesudførende Changes for Rottedatabasen Web Service The coming version of Rottedatabasen Web Service will have several changes some of them breaking for the exposed methods. These changes and the business logic behind

Læs mere

PARALLELIZATION OF ATTILA SIMULATOR WITH OPENMP MIGUEL ÁNGEL MARTÍNEZ DEL AMOR MINIPROJECT OF TDT24 NTNU

PARALLELIZATION OF ATTILA SIMULATOR WITH OPENMP MIGUEL ÁNGEL MARTÍNEZ DEL AMOR MINIPROJECT OF TDT24 NTNU PARALLELIZATION OF ATTILA SIMULATOR WITH OPENMP MIGUEL ÁNGEL MARTÍNEZ DEL AMOR MINIPROJECT OF TDT24 NTNU OUTLINE INEFFICIENCY OF ATTILA WAYS TO PARALLELIZE LOW COMPATIBILITY IN THE COMPILATION A SOLUTION

Læs mere

JENSEN EXTREME FEEDER

JENSEN EXTREME FEEDER JENSEN EXTREME FEEDER MANUAL MANUAL Date of issue 2005.06.03 Fremstillingsdato Machine no. 870272 Maskinnr. Distributor / Forhandler Project / Projekt Manufacturer / Fabrikant JENSEN USA INC. 4211 Pleasant

Læs mere

XXL-Rehab Stok XXL-Rehab Walking Cane

XXL-Rehab Stok XXL-Rehab Walking Cane XXL-Rehab Stok XXL-Rehab Walking Cane Anvendelse Use Max 270 kg Brugsanvisning User manual DK Bruges til: - Bariatriske brugere. UK For use by: - Bariatric users. Brugsanvisning for XXL-Rehab Stok ADVARSEL

Læs mere

Specifikationer: Producer: Unitron a/s Kokmose 6, 6000 Kolding. Tlf Fax

Specifikationer: Producer: Unitron a/s Kokmose 6, 6000 Kolding. Tlf Fax DK MANUAL TIL SMÅGRISE Number: 1212-1201 Number: 1212-1202 Number: 1212-1203 HOLDER TIL Number: 1212-1205 MIXERHJUL TIL Number: 1212-1210 Specifikationer: UniFeeder monteres på siden af skillevæg i faresti,

Læs mere

E-PAD Bluetooth hængelås E-PAD Bluetooth padlock E-PAD Bluetooth Vorhängeschloss

E-PAD Bluetooth hængelås E-PAD Bluetooth padlock E-PAD Bluetooth Vorhängeschloss E-PAD Bluetooth hængelås E-PAD Bluetooth padlock E-PAD Bluetooth Vorhängeschloss Brugervejledning (side 2-6) Userguide (page 7-11) Bedienungsanleitung 1 - Hvordan forbinder du din E-PAD hængelås med din

Læs mere

Læs venligst Beboer information om projekt vandskade - sikring i 2015/2016

Læs venligst Beboer information om projekt vandskade - sikring i 2015/2016 Læs venligst Beboer information om projekt vandskade - sikring i 2015/2016 Vi er nødsaget til at få adgang til din lejlighed!! Hvis Kridahl (VVS firma) har bedt om adgang til din/jeres lejlighed og nøgler,

Læs mere

IPTV Box (MAG250/254) Bruger Manual

IPTV Box (MAG250/254) Bruger Manual IPTV Box (MAG250/254) Bruger Manual Når din STB (Set top Box) starter op, bliver der vist en pop up boks på skærmen, hvor du kan åbne EPG ved at trykke på F2 (Nogle bokse kan fortælle at den har brug for

Læs mere

RE7TM11BU ZELIO tidsrelæ forsinket indkobling - 0,05..1 sek V AC/DC - 1OC

RE7TM11BU ZELIO tidsrelæ forsinket indkobling - 0,05..1 sek V AC/DC - 1OC Produkt datablad Karakteristika RE7TM11BU ZELIO tidsrelæ forsinket indkobling - 0,05..1 sek. - 24 V AC/DC - 1OC Primær Produktsortiment Produkttype Type nr. Tidsforsinkelsestype Time delay range Zelio

Læs mere

IBM Network Station Manager. esuite 1.5 / NSM Integration. IBM Network Computer Division. tdc - 02/08/99 lotusnsm.prz Page 1

IBM Network Station Manager. esuite 1.5 / NSM Integration. IBM Network Computer Division. tdc - 02/08/99 lotusnsm.prz Page 1 IBM Network Station Manager esuite 1.5 / NSM Integration IBM Network Computer Division tdc - 02/08/99 lotusnsm.prz Page 1 New esuite Settings in NSM The Lotus esuite Workplace administration option is

Læs mere

Tekniske bestemmelser mv. for transformere for 50-60/10-20 kv netspænding og med mærkeeffekt 6,3-25 MVA. 5. udgave, december 2015.

Tekniske bestemmelser mv. for transformere for 50-60/10-20 kv netspænding og med mærkeeffekt 6,3-25 MVA. 5. udgave, december 2015. Rekommandation 1 Tekniske bestemmelser mv. for transformere for 50-60/10-20 kv netspænding og med mærkeeffekt 6,3-25 MVA. 5. udgave, december 2015. Recommendation 1 Technical terms and conditions of transformers

Læs mere

Control cable YSLY-JZ/-JB/-OZ/-OB

Control cable YSLY-JZ/-JB/-OZ/-OB Control cable YSLY-JZ/-JB/-OZ/-OB CPR-performance: Eca Conductor material: copper, bare Conductor class: class 5 = fine stranded Insulation: PVC TI1 Sheathing material: PVC YM2 Colour outer sheath: grey

Læs mere

Fundamentals of HVAC Control Systems

Fundamentals of HVAC Control Systems ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 4 Sensors and Auxiliary Devices 2007 ASHRAE Hong

Læs mere

RPW This app is optimized for: For a full list of compatible phones please visit radiation. result.

RPW This app is optimized for: For a full list of compatible phones please visit   radiation. result. TM TM RPW-1000 Laser Distance Measurer This app is optimized for: For a full list of compatible phones please visit www.ryobitools.eu/phoneworks IMPORTANT SAFETY S READ AND UNDERSTAND ALL INSTRUCTIONS.

Læs mere

PARATHOM / PARATHOM PRO MR16 Electric Transformer Compatibility

PARATHOM / PARATHOM PRO MR16 Electric Transformer Compatibility / PRO MR16 Electric Transformer Compatibility BASIC INFORMATION: 1. HOW CAN I UNDERSTAND THE FOLLOWING SHES? Compatibility to OSRAM s: -Series Circuit... Page 2 -Parallel Circuit... Page 3 Compatibility

Læs mere

RoE timestamp and presentation time in past

RoE timestamp and presentation time in past RoE timestamp and presentation time in past Jouni Korhonen Broadcom Ltd. 5/26/2016 9 June 2016 IEEE 1904 Access Networks Working Group, Hørsholm, Denmark 1 Background RoE 2:24:6 timestamp was recently

Læs mere

Ergonomisk løft. Specials. www.certex.dk. Højdestabler kasser High stacking boxes. Rulle løfter med 90º tilt Roll handling with 90º tilt

Ergonomisk løft. Specials. www.certex.dk. Højdestabler kasser High stacking boxes. Rulle løfter med 90º tilt Roll handling with 90º tilt Ergonomisk løft Højdestabler kasser High stacking boxes Rulle løfter med 90º tilt Roll handling with 90º tilt Kuffert løfter Baggage handling Håndtering af postpakker Handling of parcels Rudehåndtering

Læs mere

Engelsk. Niveau C. De Merkantile Erhvervsuddannelser September 2005. Casebaseret eksamen. www.jysk.dk og www.jysk.com.

Engelsk. Niveau C. De Merkantile Erhvervsuddannelser September 2005. Casebaseret eksamen. www.jysk.dk og www.jysk.com. 052430_EngelskC 08/09/05 13:29 Side 1 De Merkantile Erhvervsuddannelser September 2005 Side 1 af 4 sider Casebaseret eksamen Engelsk Niveau C www.jysk.dk og www.jysk.com Indhold: Opgave 1 Presentation

Læs mere

Basic statistics for experimental medical researchers

Basic statistics for experimental medical researchers Basic statistics for experimental medical researchers Sample size calculations September 15th 2016 Christian Pipper Department of public health (IFSV) Faculty of Health and Medicinal Science (SUND) E-mail:

Læs mere

1. Basic safety information 3 2. Proper use 3

1. Basic safety information 3 2. Proper use 3 307346 EN Motion detector LUXA 103-100 U WH 1030040 LUXA 103-100 UA WH 1030045 1. Basic safety information 3 2. Proper use 3 Disposal 3 3. Device description 4 4. Installation and connection 4 Installing

Læs mere

ELECTRONIC CONTROL BOX

ELECTRONIC CONTROL BOX ELECTRONIC CONTROL BOX 20-0314 Specifications Rated voltage: Rated power: Rated current: Blower load (A): Pump load (B): Light load (C): Aux (D): Heater load: 400V, 50Hz, 3 phase 11000 W 3 x 16 A Max.

Læs mere

XXL-Rehab 4-punkt Stok XXL-Rehab 4-point Cane

XXL-Rehab 4-punkt Stok XXL-Rehab 4-point Cane XXL-Rehab 4-punkt Stok XXL-Rehab 4-point Cane Anvendelse Use Max 270 kg Brugsanvisning User manual DK Bruges til: - Bariatriske brugere. UK For use by: - Bariatric users. Brugsanvisning for XXL-Rehab 4-punkt

Læs mere

Vina Nguyen HSSP July 13, 2008

Vina Nguyen HSSP July 13, 2008 Vina Nguyen HSSP July 13, 2008 1 What does it mean if sets A, B, C are a partition of set D? 2 How do you calculate P(A B) using the formula for conditional probability? 3 What is the difference between

Læs mere

Metal Oxide Varistor:TVM-B Series

Metal Oxide Varistor:TVM-B Series Features 1. RoHS compliant 2. High surge suppress capability 3. EIA size 0402 ~ 2220 4. Operating voltage: 5.5 ~ 85 Vdc 5. Bidirectional and symmetrical V/I characteristics 6. Multilayer ceramic construction

Læs mere

Betjenings vejledning I Operator manual Tekniske data I Technical data El-tegninger I Electrical drawings. QVEX Clima. Revideret 12-10-2011 /JLK

Betjenings vejledning I Operator manual Tekniske data I Technical data El-tegninger I Electrical drawings. QVEX Clima. Revideret 12-10-2011 /JLK Betjenings vejledning I Operator manual Tekniske data I Technical data El-tegninger I Electrical drawings QVEX Clima Revideret 12-10-2011 /JLK mit: JLK CC: Dato: 12-10-2011 Indhoidsfortegnelse I Table

Læs mere

Brug sømbrættet til at lave sjove figurer. Lav fx: Få de andre til at gætte, hvad du har lavet. Use the nail board to make funny shapes.

Brug sømbrættet til at lave sjove figurer. Lav fx: Få de andre til at gætte, hvad du har lavet. Use the nail board to make funny shapes. Brug sømbrættet til at lave sjove figurer. Lav f: Et dannebrogsflag Et hus med tag, vinduer og dør En fugl En bil En blomst Få de andre til at gætte, hvad du har lavet. Use the nail board to make funn

Læs mere

Special VFR. - ved flyvning til mindre flyveplads uden tårnkontrol som ligger indenfor en kontrolzone

Special VFR. - ved flyvning til mindre flyveplads uden tårnkontrol som ligger indenfor en kontrolzone Special VFR - ved flyvning til mindre flyveplads uden tårnkontrol som ligger indenfor en kontrolzone SERA.5005 Visual flight rules (a) Except when operating as a special VFR flight, VFR flights shall be

Læs mere

WI180C-PB. Online-datablad

WI180C-PB. Online-datablad Online-datablad A B C D E F H I J K L M N O P Q R S T Oversigt over tekniske data Tekniske data Tilbehørsfamilie Henvisning Kapslingsklasse Dimensioner (B x H x L) Beskrivelse Klassifikationer Bestillingsoplysninger

Læs mere

Opera Ins. Model: MI5722 Product Name: Pure Sine Wave Inverter 1000W 12VDC/230 30A Solar Regulator

Opera Ins. Model: MI5722 Product Name: Pure Sine Wave Inverter 1000W 12VDC/230 30A Solar Regulator Opera Ins Model: MI5722 Product Name: Pure Sine Wave Inverter 1000W 12VDC/230 30A Solar Regulator I.Precautions 1. Keep the product away from children to avoid children playing it as a toy and resultinginpersonalinjury.

Læs mere

User Manual for LTC IGNOU

User Manual for LTC IGNOU User Manual for LTC IGNOU 1 LTC (Leave Travel Concession) Navigation: Portal Launch HCM Application Self Service LTC Self Service 1. LTC Advance/Intimation Navigation: Launch HCM Application Self Service

Læs mere

Small Autonomous Devices in civil Engineering. Uses and requirements. By Peter H. Møller Rambøll

Small Autonomous Devices in civil Engineering. Uses and requirements. By Peter H. Møller Rambøll Small Autonomous Devices in civil Engineering Uses and requirements By Peter H. Møller Rambøll BACKGROUND My Background 20+ years within evaluation of condition and renovation of concrete structures Last

Læs mere

YDEEVNEDEKLARATION. Nr DA

YDEEVNEDEKLARATION. Nr DA YDEEVNEDEKLARATION Nr. 0003 DA 1. Varetypens unikke identifikationskode: fischer slaganker EA II 2. Tilsigtet anvendelse: Produkt Metalanker til brug i beton (let befæstigelse) Anvendelsesområde/r Anvendes

Læs mere

Elma DT 802D CO2 logger. Dansk/Norsk 2 English 4 EAN:

Elma DT 802D CO2 logger. Dansk/Norsk 2 English 4 EAN: Elma DT 802D CO2 logger Dansk/Norsk 2 English 4 EAN: 5706445840366 Elma DT_802D CO2 logger 2 Brugervejledning Sikkerhed Læs venligst denne brugermanual grundigt igennem og anvend udelukkende instrumentet

Læs mere

* _0817* Drivteknik \ Drivautomatisering \ Systemintegration \ Services. Rettelse. MOVIMOT MM..D med vekselstrømsmotor DT/DV

* _0817* Drivteknik \ Drivautomatisering \ Systemintegration \ Services. Rettelse. MOVIMOT MM..D med vekselstrømsmotor DT/DV Drivteknik \ Drivautomatisering \ Systemintegration \ Services *23582529_0817* Rettelse MOVIMOT MM..D med vekselstrømsmotor DT/DV Udgave 08/2017 23582529/DA SEW-EURODRIVE Driving the world Supplerende

Læs mere

XXL-Rehab 4-punkt Stok XXL-Rehab 4-point Cane

XXL-Rehab 4-punkt Stok XXL-Rehab 4-point Cane XXL-Rehab 4-punkt Stok XXL-Rehab 4-point Cane Anvendelse Use Max 270 kg Brugsanvisning User manual DK Kan med fordel anvendes til: - Bariatriske brugere. UK Ideal use for: - Bariatric users. Brugsanvisning

Læs mere