REDUKTION AF OVERFØRSEL AF FORURENINGER MELLEM LEJLIGHEDER, FASE 2

Størrelse: px
Starte visningen fra side:

Download "REDUKTION AF OVERFØRSEL AF FORURENINGER MELLEM LEJLIGHEDER, FASE 2"

Transkript

1 REDUKTION AF OVERFØRSEL AF FORURENINGER MELLEM LEJLIGHEDER, FASE 2 UNDERSØGELSE AF METODER TIL TÆTNING OG REDUKTION AF OVERFØRSEL AF FORURENINGER FRA TOBAKSRØG MELLEM LEJLIGHEDER I ÆLDRE ETAGEBOLIGER SBI 2017:05

2

3 Reduktion af overførsel af forureninger mellem lejligheder, Fase 2 Undersøgelse af metoder til tætning og reduktion af overførsel af forureninger fra tobaksrøg mellem lejligheder i ældre etageboliger Alireza Afshari Niels Christian Bergsøe Ahsan Iqbal SBi 2017:05 Statens Byggeforskningsinstitut, Aalborg Universitet 2017

4 Titel Reduktion af overførsel af forureninger mellem lejligheder, Fase 2 Undertitel Undersøgelse af metoder til tætning og reduktion af overførsel af forureninger fra tobaksrøg mellem lejligheder i ældre etageboliger Serietitel SBi 2017:05 Udgave 1. udgave Udgivelsesår 2017 Forfatter Alireza Afshari, Niels Christian Bergsøe, Ahsan Iqbal Sidetal 61 Litteraturhenvisninger Emneord Side Naborøg, partikelforurening, gasser, ultrafine partikler ISBN Udgiver Statens Byggeforskningsinstitut, Aalborg Universitet, A.C. Meyers Vænge 15, 2450 København SV E-post sbi@sbi.aau.dk Der gøres opmærksom på, at denne publikation er omfattet af ophavsretsloven

5 Indhold Forord... 4 Materiale... 6 Fremgangsmåde... 7 Beregningsmetoder... 9 Resultater Før tætning Efter tætning Supplerende undersøgelser i laboratoriet Diskussion Konklusion Litteratur Bilag 1... A Bilag 2... B Bilag 3... C 3

6 Forord I etageejendomme kan beboere blive udsat for luftforureninger, som stammer fra aktiviteter i de omkringliggende lejligheder. Aktiviteterne kan for eksempel være madlavning og tobaksrygning. I ældre etageboliger kan der være utætheder for eksempel ved rørgennemføringer og langs vægge, hvor gasser og partikler kan bliver overført fra en lejlighed til en anden. Tobaksrøg er en særlig udfordring, da gasser, partikler og lugte fra tobaksrygning af mange anses som en særlig gene. I en rapport fra SBi (Gunner, et al. 2012) blev overførslen af ultrafine partikler og sporgas mellem to etageadskilte lejligheder målt før og efter tætning af etageadskillelsen. I den nederste af lejlighederne blev der anvendt tændte cigaretter til generering af partikler og sporgas til måling af luftoverførsel. Tætning af etageadskillelsen, som blev udført i den øverste lejlighed, omfattede en membran af polyethylen, tagklæber og fugemasse. Før tætning af gulvet blev ca. 4 % af de ultrafine partikler og ca. 14 % af den anvendte sporgas overført. Efter tætningen blev overførslen af ultrafine partikler og gasser reduceret med en faktor 3 til henholdsvis ca. 1,6 % og ca. 5 %. Forsøget blev udført i en etageejendom fra slutningen af tallet. I Sverige er der udviklet en membran, som kan adsorbere gasser og partikler, og i Danmark er der udviklet en membran, som er omtrent uigennemtrængelig for gasser og partikler. Der er behov for at undersøge de to membraner og udførelsesmetoder under både laboratorieforhold og i praksis i etageboliger. Projektet blev gennemført i to faser. I fase 1 er to membraner, ctrap fra Lunds Universitets InnovationsSystem (LUIS), Sverige og Ico-Vario fra Icopal, Danmark, afprøvet og analyseret under kontrollerede forhold i laboratoriet med henblik på bestemmelse af membranernes evne til at reducere indeluftens indhold af gasser og ultrafine partikler. På grundlag af undersøgelsen i fase 1 konkluderes at: membraner er i stand til at reducere overførslen af ultrafine partikler fra cigaretrøg og stearinlys membraner er i stand til at reducere overførslen af kemiske stoffer (VOC) ctrap har en lav vanddamp-diffusionsmodstand fra to sider, mens IcoVario har en lav vanddampdiffusionsmodstand fra én side. Der er behov for at afprøve, måle og evaluere membranerne i eksisterende etageboliger der er også behov for at analysere langtidsydeevnen af membranerne i eksisterende etageboliger Denne afrapportering vedrører fase 2, som har til formål i praksis at afprøve, måle og evaluere metoder til tætning og reduktion af overførsel af forureninger fra tobaksrøg mellem lejligheder i ældre etageboliger. Metoderne omfattede anvendelse af de to membraner - eventuelt i kombination med tætning ved hjælp af fugemasse og tape. Projektets formål i fase 2 var at afprøve, måle og evaluere i praksis metoder til tætning og reduktion af overførsel af forureninger fra tobaksrøg mellem lejligheder i ældre etageboliger. Metoderne omfattede anvendelse af de to membraner - eventuelt i kombination med tætning ved hjælp af fugemasse og tape. 4

7 Statens Byggeforskningsinstitut, Aalborg Universitet Forskningsafdelingen for Energieffektivitet, Indeklima og bæredygtighed April 2017 Søren Aggerholm Forskningschef 5

8 Materiale Den ene af to membraner er ctrap, som er udviklet ved Lunds universitets innovationssystem (LUIS, Lund, Sverige), se figur 1. ctrap består af fire lag: Et indre og et ydre beskyttende lag, et adsorberende lag og en semipermeabel barriere. ctrap har en indvendig side (ru side) og en udvendig side (glat side), og adsorberer kun de gasser og partikler, der kommer indefra. Membranen kan blandt andet adsorbere flygtige organiske forbindelser (VOC), mens vanddamp kan trænge igennem. ctrap er oprindelig udviklet til at fungere som spærre for VOC i forbindelse med fugtskader i konstruktioner, se bilag 2. Den anden membran er IcoVario fra Icopal, se figur 2. Membranen er fugtadaptiv, og den tillader, at fugt i tag-, loft- og vægkonstruktioner kan afgives indad til rummet i forbindelse med udtørring af konstruktionen. Fugttransporten foregår ved vanddampdiffusion gennem en aktiv film, hvorimod VOC tilbageholdes, se bilag 3. På grundlag af undersøgelsen i fase 1 konkluderes, at ctrap har en lav vanddamp-diffusionsmodstand fra to sider, mens IcoVario har en lav vanddampdiffusionsmodstand fra én side. Det blev besluttet at afprøve, måle og evaluere ctrap i eksisterende etageboliger. ctrap Figur 1. ctrap (ctrap 2015). IcoVario Figur 2. IcoVario fra Icopal (Icopal, 2015). 6

9 Fremgangsmåde Formålet med undersøgelsen var at kvantificere overførslen af ultrafine partikler (UFP) fra tobaksrøg og sporgas (N 2 O) gennem membranen ctrap. I samarbejde med et firma, som er specialist i fugning og tætning, blev der udvalgt to lejligheder til at undersøge membranen. Undersøgelsen blev gennemført i to lejligheder i to ældre etageboligbyggerier fra 1900 og Eksponeringslejligheden lå umiddelbart over kildelejligheden. Undersøgelsen blev gennemført i forskellige måneder i Under målingerne fandt ingen indendørsaktiviteter sted, som kunne indebære generering partikler, fx madlavning og rengøring. Lejlighederne består af en entré, en stue, der vender mod en trafikeret vej, et værelse og et køkken, der begge vender mod gården, samt toilet og bad placeret centralt i lejligheden. Under hvert vindue i stue og værelse er der radiator med varmerør, der er ført gennem gulvet ved lysning. Der er naturligt aftræk fra toilet/badeværelse. For at opnå et overtryk i kildelejligheden i forhold til eksponeringslejligheden blev der etableret en højere rumtemperatur i kildelejligheden. Dette blev sikret ved at holde temperaturen i kildelejligheden ca. 2-5 C højere end i eksponeringslejligheden. Kilde til generering af partikler bestod af fire tændte cigaretter i kildelejligheden, to i stuen og to i værelset. Koncentrationen af ultrafine partikler blev målt ved hjælp af partikeltællere af fabrikatet P-Trak ultrafine particle counter og to Condensation Particle Counter (CPC) model 3007 fra TSI Incorporated. Partikeltællerne målte simultant i hver af lejlighederne (CPC 3007) og udenfor (P-Trak). Desuden blev lejlighedernes luftskifte og luftoverførslen mellem de to lejligheder målt ved hjælp af Multi-Gas-monitorer, type 1302 fra Brüel & Kjær, der var placeret én i hver lejlighed. Endvidere blev der anvendt passiv sporgasteknik (PFT) til at måle den gennemsnitlige luftoverføring mellem lejlighederne. Temperatur og relativ luftfugtighed blev målt ved hjælp af dataloggere TinyTag type TGU-4500 fra Gemini. Under partikelgenereringen blev der opnået fuld opblanding ved brug af ventilatorer i rummet. Alle udeluftventiler var åbne, og aftrækskanalen på toilettet var lukket. I eksponeringslejligheden var alle vinduer, yderdøre og udeluftventiler lukkede, og aftrækskanalen på toilettet var åben. Første del af undersøgelsen blev udført før tætning af gulvet i eksponeringslejligheden. Anden del af undersøgelsen blev udført efter tætning af gulvet. Forud for anden del af undersøgelsen blev gulvet i eksponeringslejligheden tætnet. Fodlister og fejelister blev demonteret, og gulvet blev overalt dækket af membranen ctrap. Tætningen blev udført af et fagkyndigt firma. Membranen ctrap blev ført ca. 10 cm op ad væggene, hvor den blev tætnet med byggefugemasse og klemt med fodlister og fejelister, som blev genmonteret. Rørgennemføringer ved radiatorerne blev tætnet med tape og ctrap. 7

10 Lejlighed 1, Irmingersgade 9, 2100 København Ø Lejlighed 2, Hørsholmgade 26, 2200 København N Figur 3. Facadefotos og plantegninger af lejlighederne. Figur 3 viser facadefotos og plantegninger af lejlighederne. Eksponeringslejlighed og kildelejlighed er opbygget ens. Lejlighed 1 har et areal 37,3 m 2 og en rumhøjde på 2,72 meter. Voluminet er således ca. 102 m 3. Lejlighed 2 har et areal på 60,1 m 2. Rumhøjden er 2,5 meter og voluminet er således ca. 150 m 3. I denne rapport præsenteres udvalgte resultater fra målinger i lejlighed 1. 8

11 Beregningsmetoder Til at bestemme overførslen af ultrafine partikler og gasser er beregningsmetoden (1) anvendt, se bilag 1: VC o V leakcs V V leakcs V + Vγ Cr{ t} = + + Co Cr e i V V V V V V + V V + γ + γ + γ V + Vγ t V (1) Hvor C r {t} er koncentration af forureninger på ethvert øjeblik i eksponeringslejligheden {forurening/m 3 }. C ri baggrundskoncentration af forureninger i eksponeringslejligheden {forurening/m 3 }. C s er koncentrationen af forureningen i kildelejligheden {forurening/m 3 }. C 0 er koncentrationen af udenfor forureninger {forurening/m 3 } γ er fjernelse af forureninger i eksponeringslejligheden (for gasser ignoreres) {1/h} V er luftstrøm {m 3 /h} V er eksponeringslejlighedens volumen {m 3 } er lækage gennem gulvet i eksponeringslejligheden {m 3 /h} V leak Luftskiftet i de to lejligheder er bestemt ved brug af sporgasteknik og henfaldsmetoden. Princippet er, at en kendt og målbar luftart (sporgas) doseres. Sporgassen fordeles, så fuldstændig opblanding sikres. Derefter afbrydes doseringen af sporgas, og sporgaskoncentrationen registreres over tid. Af henfaldskurven bestemmes luftskiftet således (2): CC{tt} = CC oo ee nnnn (2) Hvor C 0 er startkoncentrationen i ppm C{t} er koncentrationen i ppm efter t t er tiden i timer [h] n er luftskiftet i gange pr. time [h -1 ] 9

12 Resultater Før tætning Undersøgelsen blev gennemført i to lejligheder i to ældre etageboligbyggerier. Her præsenteres udvalgte resultater fra lejlighed 1. Detaljerede resultater fremgår af bilagene. Figur 4 viser de målte koncentrationsforløb for cigaretrøg i kildelejlighed og eksponeringslejlighed. Baggrundskoncentration i kildelejligheden var i gennemsnit ca.11, UFP/m 3, og i eksponeringslejligheden var den ca. 6, UFP/m 3, 40 minutter inden cigaretter blev tændt i kildelejligheden. eksponeringslejligheden kildelejligheden 375 UFP /m 3 x :36 10:48 12:00 13:12 Tid Figur 4. Baggrundskoncentration og målte værdier af ultrafine partikler under målingerne i lejlighederne før tætning af gulvet i eksponeringslejligheden. udenfor eksponeringslejligheden eksponeringslejligheden-beregnede værdier UFP /m 3 x :36 10:48 12:00 13:12 Tid Figur 5. Resultat af måling og beregning af ultrafine partikler koncentrationen i eksponeringslejlighed før tætning af gulvet. Figur 5 viser målt og beregnet koncentration af ultrafine partikler i eksponeringslejligheden. Beregningerne er udført jf. ligning (1). Det er forudsat, at der er fuldstændig opblanding af partikler og luft. Denne forudsætning indebærer, at koncentrationen i udsugningsluften af ultrafine partikler er lig med koncentrationen i luften i lejligheden. Ligningen bruges til beregning af koncentrationen af ultrafine partikler i den undersøgte lejlighed. 10 Resultaterne viser, at partikeloverførslen før tætning var 16 %.

13 Efter tætning Efter tætningen blev luftskiftet i eksponeringslejligheden beregnet til 0,4 h -1. Figur 6 viser de målte koncentrationsforløb for cigaretrøg i kildelejlighed og eksponeringslejlighed. Baggrundskoncentration i kildelejligheden var i gennemsnit ca. 12,5 109 UFP/m 3 og i eksponeringslejligheden ca UFP/m 3. eksponeringslejligheden kildelejligheden 120 UFP /m 3 x :48 11:16 11:45 12:14 12:43 13:12 Tid Figur 6. Målt koncentration af ultrafine partikler koncentrationen eksponeringslejligheden og kildelejligheden efter tætning af gulvet. udenfor eksponeringslejligheden eksponeringslejligheden-beregnede værdier 20 UFP /m 3 x :48 11:16 11:45 12:14 12:43 13:12 Tid Figur 7. Resultat af måling og beregning af ultrafine partikler koncentrationen i eksponeringslejlighed efter tætning af gulvet. Figur 7 viser målt og beregnet koncentration af ultrafine partikler i eksponeringslejligheden. Til at beregne overførselsprocenten af ultrafine partikler fra kildelejligheden til eksponeringslejligheden anvendes ligning (1). Resultaterne viser, at efter tætningen blev partikeloverførslen reduceret fra 16 % til 7,6 %. Dette viser, at ctrap reducerer næsten 53 % af overførslen af ultrafine partikler. Supplerende undersøgelser i laboratoriet Der blev foretaget undersøgelser af overførslen af sporgas mellem kildelejligheden og eksponeringslejligheden. Desværre har måleresultaterne ikke kunnet analyseres på grund af tekniske problemer. Derfor blev der foretaget laboratorieundersøgelser i et prøvekammer med det formål at kvantificere overførslen af sporgas (N 2 O) sammen med overførslen af ultrafine partikler. 11

14 Prøvekammeret blev opdelt vandret i to dele. Den øverste del (det eksponerede rum) var 1,26 m 3 og den nederste del (kilderummet) var 0,62 m 3. De to rum var adskilt af et trægulv. Målingerne blev udført med og uden ctrap under gulvet. Resultaterne viser, at ctrap var i stand til at reducere overførslen af sporgas (N 2 O) med 87,5 % og overførslen af ultrafine partikler med 97 %. Figur 8. Prøvekammeret var opdelt i to dele med et trægulv som vandret adskillelse. 12

15 Diskussion Denne rapport udgør en del af resultaterne af anden fase af et projekt i to faser om brug af tætningsmetode for reduktion af overførsel af forureninger fra tobaksrøg mellem lejligheder i ældre etageboliger. Formålet med undersøgelsen var at kvantificere overførslen af ultrafine partikler (UFP) fra tobaksrøg og sporgas (N 2 O) gennem to membraner. Den ene af to membraner er ctrap og den anden membran er IcoVario. ctrap kan blandt andet adsorbere flygtige organiske forbindelser (VOC) og ultrafine partikler, mens vanddamp kan trænge igennem. På grundlag af undersøgelsen i fase 1 konkluderes det, at ctrap har en lav vanddampdiffusionsmodstand fra to sider, mens IcoVario har en lav vanddampdiffusionsmodstand fra én side. Det blev besluttet at installere, måle og evaluere ctrap i eksisterende etageboliger. Forsøg blev udført under kontrollerede betingelser ultrafine overførsel partikler 50% 45% 40% 35% 30% 25% 20% 15% 10% 05% 00% Forsøg blev udført i 15 May & 15 juni Lab Tests lejlighed 1 lejlighed 2 uden ctrap ctrap Figur 9. Overførsel af ultrafine partikler fra tobaksrøg før og efter tætning med ctrap. Tests blev udført hos 15 april og den 16. Jan Resultaterne fra denne undersøgelse er opsummeret i figur 9. Resultaterne er et vigtigt skridt til bedre at kunne forstå membranens ydeevne som en tætningsmetode mod forureninger fra tobaksrøg. Derimod er kvantificering af overførslen af ultrafine partikler fra tobaksrøg gennem membraner mellem lejligheder i ældre etageboliger afhængig af flere faktorer; hvoraf nogle er ukontrollerbare, især målinger på stedet. Derfor er der i den foreliggende undersøgelse en forskel mellem resultaterne af laboratorieundersøgelserne og feltundersøgelserne. 13

16 reduktion i overførsel ultrafine partikler 100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 00% 97% 60% 53% Lab Tests lejlighed 1 lejlighed 2 Figur 10. Reduktion af overførslen af ultrafine partikler og N2O mellem lejlighed 1 og 2 ved henholds laboratorieundersøgelser og feltundersøgelser. Måleresultaterne fra laboratorieundersøgelsen viser, at membranen ctrap var i stand til at reducere overførslen af ultrafine partikler med ca. 97 % og N 2 O med ca. 87 %, mens ctrap i lejlighed 1 og 2 var i stand at reducere overførslen af ultrafine partikler med ca. 53 % og ca. 60 %, se figur 10. Dette indebærer, at der i ældre etageboliger kan være utætheder, hvor partiklerne kan komme igennem. Utæthederne er fx ved rørføringer, i gulvet og langs væggene. Sammenfattende kan det konkluderes, at ctrap var i stand til at reducere overførslen af ultrafine partikler og sporgasser i de to undersøgte lejligheder med mellem 53 % og 60 %. Dette betyder, at anvendelse af ctrap ikke bare kan hjælpe med til at reducere koncentrationen af ultrafine partikler og gasser fra naborøg, men også til at undgå anvendelse af energikrævende, tekniske løsninger som fx luftrensere for at begrænse påvirkningen fra naboers rygning. På grund af tekniske problemer var det ikke muligt at undersøge overførslen af sporgas i feltundersøgelserne, og derfor blev der gennemført en undersøgelse i laboratoriet. Resultaterne viser, at ctrap var i stand til at reducere overførslen af sporgas (N 2 O) med 87,5 % og overførslen af ultrafine partikler med 97 %. Det kan konkluderes, at laboratorieundersøgelsen viser, at ctrap er i stand til at reducere overførslen af gasser (N 2 O) i samme størrelsesorden som ultrafine partikler. 14

17 Konklusion På grundlag af undersøgelsen i fase 2 konkluderes at: Ifølge feltundersøgelsen er ctrap i stand til at reducere overførslen af ultrafine partikler fra cigaretrøg med ca. 60 %. Ifølge laboratorieundersøgelsen er ctrap i stand til at reducere overførslen af gasser (N 2 O) i samme størrelsesorden som ultrafine partikler. Der er behov for at analysere langtidsydeevnen af membranerne i eksisterende etageboliger. 15

18 Litteratur Afshari, A., & Reinhold, C. (2008). Deposition of fine and ultrafine particles on indoor surface materials. Indoor and Built Environment, 17(3), Afshari, A., Ardkapan, S. R., Bergsøe, N. C., & Johnson, M. S. (2010). Technical solutions for reducing indoor residential exposures to ultrafine particles from second-hand cigarette smoke infiltration. Proceedings of Clima 2010, Antalya, Turkey. Afshari, A., Shi, B., Bergsøe, N. C., Ekberg, L., & Larsson, T. (2010). Quantification of ultrafine particles from second-hand tobacco smoke, Proceedings of Clima 2010 : 10th REHVA World Congress 'Sustainable Energy use in Buildings; Turkey - Antalya, 09/05/ /05/ Afshari, A., Shi, B., Bergsøe, N. C. and Ardkapan, S.R. (2014). Filtration of ultrafine particles from tobacco smoke using an ionizer in combination with an electrostatic fibrous filter, Indoor Air 2014China - Hong Kong, 07/07/ /07/ Afshari, A., Markowicz, P., Larssonn, L., Bergsøe, N. C.. and Ardkapan, S.R. (2014). Evaluating the effectiveness of two membranes in blocking chemicals, Proceedings Indoor Air - Hong Kong, 07/07/ /07/ Brandt. E, Møllerv E. B. (2013). Fugt I bygninger (2. udg.) (SBi-anvisning 224). Statens Byggeforskningsinstitute, Aalborg Universitet. ctrap. (2015). Ekberg, L.E. and Shi, B. (2009). Removal of ultrafine particles by ventilation air filters, Proceeding of Healthy Buildings 2009, Syracuse, USA 2009, pp. (Paper 97) 4 pages. Gunner, A., Ardkapan, S.R., Afshari, A., Bergsøe, N.C. (2012). Transfer of ultrafine particles and air in multi-storey buildings. Proceedings of AVIC 2012, Copenhagen, Denmark. Gunner, A., Ardkapan, S.R., Afshari, A., Bergsøe, N.C. (2014). Transfer of ultrafine particles and air in multi-storey buildings. Journal of Civil Engineering and Architecture, 8(4). Icopal. (2015). Markowicz, P. and Larsson, L. (2012). The surface emissions trap: A new approach in indoor air purification. Journal of microbiological methods, 91(2), pp Nilsson, P. (2003). Achieving the desired indoor climate: energy efficiency aspects of system design. Studentlitteratur. 16 Preining, O. (1998). The physical nature of very, very small particles and its impact on their behaviour. Journal of Aerosol Science, 29(5-6),

19 Shi, B., Ekberg, L. A., Afshari, A., & Bergsøe, N. C. (2010). The effectiveness of portable air cleaners against tobacco smoke in multizone residential environments. Proceedings of Clima 2010, Antalya, Turkey. 17

20

21 Bilag 1 Detailed report in English A

22

23 Reducing the transfer of contaminants among adjacent apartments April 2016 Ahsan Iqbal, Alireza Afshari, Niels Christian Bergsøe Danish Building Research Institute (SBi) Aalborg University Copenhagen SBi Statens Byggeforskningsinstitut, Aalborg Universitet 2016

24 Title Reducing the transfer of particles and gases among adjacent apartments Subtitle Experimental evaluation of the performance of ctrap Serial title Edition Final Year 2016 Author Ahsan Iqbal Language English and Danish (only summary) Pages References Key words Transfer of particles; transfer of gases; sealing membrane; ctrap ISBN Drawings Photos Cover Publisher Danish Building Research Institute (SBi), Aalborg University, A.C. Meyers Vænge 15, 2450 Copenhagen This publication is covered by the Danish Copyright Act.

25 Content Overordnet konklusion... 5 Executive summary... 6 Introduction... 7 AIM OF THE STUDY... 8 PHYSICS OF CONTAMINANTS TRANSFERS... 9 DEFINITION OF THE SELECTED MEMBRANE Laboratory experiments Method Findings Part Part In-situ measurements Method Findings Apartment 1 Irmingersgade 9, 2100 Copenhagen Apartment 2 Hørsholmgade 26, 2200 Copenhagen Problems, errors and sources of errors during the insitu measurements 27 Occupants perception DISCUSSION Future work CONCLUSIONS REFERENCES

26 4

27 Overordnet konklusion En unik type soft membran er blevet udviklet af et svensk firma. For at teste membranens ydeevne til at indfange luftbårne forureninger, har Statens Byggeforskningsinstitut (SBi) gennemført en undersøgelse. Undersøgelsen er baseret på laboratorieforsøg samt in-situ-målinger. Laboratorieforsøgene er udført i SBi s laboratorie, hvor to tilstødende lejligheder blev simuleret i et testkammer. En lejlighed blev simuleret som en kildelejlighed, der genererede de forurenende stoffer, og den anden lejlighed blev simuleret som en lejlighed, der var eksponeret for de forurenende stoffer, som blev skabt i kildelejligheden. I kildelejligheden blev forureninger skabt ved anvendelse cigaretrøg. Den eksponerede lejlighed var placeret ovenover kildelejligheden. Begge lejligheder havde samme etageplan og rumhøjde. De simulerede lejligheder var adskilt af trægulve. Når ultrafine partikler (UFP) fra cigaretrøg blev genereret i kildelejligheden, trængte omkring 48 % af UFP igennem til den eksponerede lejlighed. På samme måde når N 2 O i form af gaspartikler blev sprøjtet ind i kildelejligheden, her trængte 16,5 % af N 2 O igennem til den eksponerede lejlighed. Derefter blev forseglingsmembranen opsat under trægulvet i den eksponerede lejlighed. Det kunne konstateres, at opsætning af forseglingsmembranen reducerede overførslen af UFP med 97 % og reducerede overførslen af N 2 O med 87,5 % i forhold til overførslerne uden membranen. En lignende procedure til at måling af overførslen af UFP blev gennemført med in-situ-målinger. In-situ-målingerne blev udført i to lejligheder i København. Målingerne blev udført uden (før renovering) og med membran (efter renovering). Tætningsmembranen kunne in situ reducere overførslen af UFP med %. Der blev også gennemført en undersøgelse af beboernes oplevelse af effekten af forseglingsmembranen og det resulterende indeklima. Før renoveringen var beboerne konstant irriteret af cigaretlugt fra deres naboer. Men efter renoveringen oplever begge beboere et bedre indeklima, fordi der ikke længere lugter af cigaretter. 5

28 Executive summary A unique type of fabric membrane has been developed by a Swedish company. To test the performance of the membrane for trapping airborne contaminants, a study was conducted by the Danish Building Research Institute (SBi). The study is based on the laboratory experiments as well as in situ measurements. Laboratory tests were performed in the laboratory of SBi where two adjacent apartments were simulated in a test chamber. One apartment was simulated as a source apartment which generated the contaminants and the second apartment was simulated as an exposed apartment which was exposed to the contaminants generated by the source apartment. In the source apartment contaminates were generated using cigarette smoke. Exposed apartment was situated above the source apartment. Both apartments had the same plan area and height. The simulated apartments were separated by wooden flooring. When the ultrafine particles (UFP) from cigarette smoke were generated in the source apartment, around 48% of UFP migrated to the exposed apartment. Similarly when N 2 O as gas particles was sprayed in the source apartment, 16.5% of the N 2 O migrated to the exposed apartment. Then the sealing membrane was installed below the wooden flooring of the exposed apartment. It was noted that inclusion of the sealing membrane reduced the transfer of UFP down to 97% and reduced the transfer of N 2 O down to 87.5% in comparison with the transfers without the membrane. A similar procedure of measuring the transfer of UFP was adapted in situ measurements. In-situ measurements were performed in two apartments in Copenhagen. The measurements were carried out without (before renovations) and with membrane (after renovations). In situ the sealing membrane was able to reduce the transfer of UFP down to 53% to 60%. A survey regarding occupant s perception of the performance of the sealing membrane and the resulting indoor air quality was also conducted. Before the renovation the occupants were continuously irritated by the cigarette smells from their neighbours. However, after the renovations both occupants perceive better indoor air quality as they don t smell cigarettes anymore. 6

29 Introduction Air contaminants generally consist of particles and gases. Many contaminants may cause health problems. For instance scientific studies in the recent past have shown that the inhaling of volatile organic compounds (VOC) can cause health problems (US Department of Health and Human Services 2010, Goldman, Enewold et al. 2001, Hodgson, Wooley 1991). Likewise, exposure to fine and ultrafine airborne particles (UFP) has been identified as an important risk factor for human health (Pope III, Dockery 2006). In residential buildings, contaminants can transfer among adjacent apartments or from outside to inside for instance, tobacco smoke. Tobacco smoke, a great source of contaminants, contain more than several thousand chemical compounds including VOCs and UFP. Tobacco smoke may cause health problems not only for intended smokers but also for those who inhale these contaminants unintentionally i.e. passive smokers. Especially in multi-storey residential buildings, there is a risk of passive smoking due to active smoking of neighbours. There are several different ways in which contaminates can be transferred from source apartments (that generates contaminants) to exposed apartments (that receives contaminants from the source apartment). Some of the common openings where contaminants can infiltrates from source apartments to exposed apartments includes electrical outlets, cable or phone jacks, HVAC system, plumbing pipes, cracks in walls, floors, building services shafts etc. However, due to ultrafine sizes, particle and gases may transfer from source apartments to exposed apartments through walls and ceiling where there is no visible cracks/opening. Previous studies in Denmark have gathered information about technical solutions, such as sealing and air cleaner that prevent or reduce the transfer of contaminants in residential buildings. However, a very little attention has so far been paid to the technical solutions such as membrane for preventing or reducing the transfer of contaminants among neighbouring apartments. The transfer of contaminants from one apartment to another can be estimated by measuring the concentrations of traceable gases and ultrafine particle (UFP). Danish Building Research Institute (SBi) has been analysing the performance of different solution to stop and/or reduce the transfer of unwanted contaminants. Afshari et al. (2010) concluded that when source apartment is located below the exposed apartment the contaminants transfer from source apartment is significantly high. Similar results have also been published by Ekberg & Shi (2009) and Afshari et. al. (2014). However, less attention so far has been paid on the methods that stop the migration of particles instead of diluting the concentration. Markowicz & Larsson (2012) reported a novel concept for stopping and reducing unwanted emissions from building materials indoors by using a surface emissions trap membrane (also used in the present study). But the results did not show the performance of the membrane against UFP and gases. Gunner et al. (2014) showed that a plastic foil can reduce the significant amount of UFP transfer. Afshari et al. (2014) performed few lab experiments for evaluating the effectiveness of two types of commercially available membranes as a sealing against VOCs transfer. The experimental results of both membranes, showed the promising results in regards to stopping migration of VOCs. 7

30 In the present study the membrane used by Markowicz & Larsson (2012) is used as a sealing against the transfer of contaminants. The membrane captures the emissions at the source which immediately results in a fresh and healthier indoor air. The membrane does not release any emissions of its own. It does not use any energy and may allow a reduced ventilation rate while maintaining a satisfactory indoor air quality. The membrane is a longterm solution with a capacity of being used up to several decades after installation. The present study is based on lab tests as well as in-situ measurements. In-situ measurements were performed in 3 different apartments in Copenhagen however due to insufficient information from one of the apartments; results from only 2 apartments are included in the present study. In the last occupants perception regarding the performance of the membrane as a sealing against contaminants were obtained. From the findings of the present study a conference article is published. The article will be presented in INDOOR AIR 2016 The 14 th International Conference of Indoor Air Quality and Climate GHENT, BELGIUM July AIM OF THE STUDY Aim of the present study was to analyse the performance of the newly developed fabric membrane as sealing against contaminates in inhabited spaces. To analyse the contaminant transfer, UFP and N 2 O were used. The performance was tested and analysed in a controlled laboratory environment, real life measurement as well as occupants perception. 8

31 PHYSICS OF CONTAMINANTS TRANSFERS Contaminant transfer rate in an apartment can be evaluated by applying mass balance equation among possible transfer roots of contaminants. The phenomenon can be expresses as mentioned in Figure 1. The apartment which is affected by the contaminants is termed as exposed apartment. The apartment which is generating the contaminants is termed as source apartment. Figure 1 particle transfer schematic The exposed apartment in Figure 1 is receiving contaminants from outdoor and from the source apartment. To estimate the amount of contaminants in the exposed apartment, the mass balance equation in the exposed apartment can be used. By considering the balanced ventilation, the mass balance equation can be expressed as: (1) Where; air inflow/outflow rate in the exposed apartment in m 3 /h Inflow particle concentration in particles/m 3 Particle concentration in the exposed apartment in particles/m 3 Outflow particle concentration in particles/m 3 Particle source effect in particles/h Volume of the apartment in m 3 Particle sink effect in particles/h Sink Effect ( ) which cannot be ignored in some forms of contaminants e.g. UFP. Sink effect encompasses all the particle sinks other than air cleaning and ventilation for instance deposition of particles on the surfaces, agglomeration, chemical reaction etc. among these the particle deposition on horizontal surfaces due to the gravity can be approximated by: (2) Where is the downward velocity of the (during the surface deposition process) and is the characteristic length can be approximated as the average room height. is the ratio of the downward velocity and average room height. can be described as the total room particle sinking rate. By assuming that the airflow rates were constant during the experimental time period, inflow contaminants concentration ( ) is same as outdoor con- 9

32 taminants concentration ( ) and outflow particle concentration ( ) is same as indoor particle concentration ( ) Eq. (1) can be written as, Solving first order differential equation by considering integrating factor Multiply the integration factor on the both side of the differential equation Integrating both sides The above mentioned solution is a general solution for the equation. Particular solution at the initial value of can be derived as follows: (3) Or by simple re-arraigning (4) Where is the air change rates of the exposed apartment. is not the total air change rates. It is the air change rate caused by the outdoor air only. There have been studies e.g. Afshari et al. (2010) that suggest that the dominant source of contaminants is the apartment below the exposed apartment. Therefore, in such scenarios the Source effect ( ) can be approximated by: Where is the contaminants concentration in the exposed apartment and is the leakage from source apartment to the exposed apartment. By substituting the above equation in (4): C r {t} = V C o V + C sv Leak +Vγ V + V +Vγ V (C +Vγ o C sv Leak + V +Vγ C V V ri ) e ( C r {t} = λc o λ+γ + C sv Leak V(1+γ) + λ (C λ+γ o C sv Leak Vλ + λ+γ C λ r i ) e (λ+γ)t V +Vγ V )t Eq. (5) is the governing equation that describes the increase in the concentration of contaminants in exposed apartment due to the contaminants concentration of source apartment and the outdoor atmosphere. Reference to the whole section: PHYSICS OF CONTAMINANTS TRANSFERS: is Chapter 3 of (Nilsson 2003) (5) 10

33 DEFINITION OF THE SELECTED MEMBRANE The selected membrane (ctrap) in a commercially available membrane which is a multilayer and multifunctional cloth developed to trapping emissions from building materials. Figure 2 ctrap - a multilayer and multifunctional cloth The cloth consists of two functional layers, a polymer layer which acts as a contaminants barrier and an adsorption layer which binds the contaminants. These layers interact in a unique way to ensure maximum effect. Moreover there are two inner and outer protective layers. Hence the membrane consists of four layers in total. The membrane is applied with the adsorption layer facing the construction i.e. the surface from which the contaminants are spread. The cloth is flexible and can be installed on floors, walls, ceiling, over cavities etc. Moisture, i.e. water in the gaseous phase, passes easily through both of these layers while contaminates such as UFP, organic substances including odours are stopped and trapped irreversibly. Any flooring can then be laid above the membrane. When attached on a wall or ceiling the membrane cloth may be covered e.g. with a thin gypsum board. Source ( 11

34

35 Laboratory experiments Method Laboratory test setup was built in SBi s laboratory in Hørsholm. The test Chamber was consisting of two compartments separated by a wooden floor as shown in Figure 3. Figure 3 test chamber for the contaminant transfer lab tests The overall dimension of the test chamber was cm 3 (outer dimensions). The volume of the top chamber was 1.26 m 3 and the bottom chamber was 0.62 m 3. Tests were conducted in two parts. Part 1 were the tests with the existing wooden floor as shown in Figure 3. Part 2 were the tests when the sealing membrane was placed below the wooden floor. In Part 1 of the tests, both top and bottom compartments were ventilated and care was taken that the exhaust air is not recirculating by any means. Bottom compartment was simulated as a source apartment and top compartment was simulated as an exposed apartment. The air change rate in the exposed apartment was 3.8 ACH. The test steps were as follows: 1) Measurements of leakage through the floor a. Using blower door technique 2) Measurements of air temperatures and relative humidity in both simulated apartments and outside of the apartments 3) Turning on the radiator in the source apartment to create a pressure difference due to the difference in temperatures 4) Measurements of UFP in both apartments and outside 5) Measurements of tracer gas (N 2 O) in both apartments and outside 6) Measurements of air change rates (ACH) in both apartments 7) Lighting a cigarette in the source apartment 8) Spray of tracer gas N 2 O in the source apartment 9) Monitoring and logging of the data in step 2 to 6 unless steady state concentrations achieve in both apartments. UFP concentrations in both apartments were logged through two condensation based particle counters 1, outside concentrations was also measured by using condensation particle counter 2. All particle counters were cocalibrated before the use in order to reduce the errors related to measurements using different instruments. The concertation of N 2 O was measured 1 TSI CPC TSI P-Trak 13

36 and logged by using a multi-gas monitor 3. Temperatures were logged using portable temperature loggers 4. The measured contaminants transfer to the exposed apartment was then compared with the theoretical values in order to evaluate the approximate values of contaminants transfer. The theoretical values are achieved by using the equation derived in the chapter PHYSICS OF CONTAMINANTS TRANSFERS: V V VC t o V leakcs V V leakcs V V V Cr{ t} Co Cr e i V V V V V V V V Where C r {t} is the theoretical contaminants concentration at any instant in the exposed apartment. C r i is the initial/background contaminants concentration in the exposed apartment. are the volume flow rate and V & V volume of the exposed apartment, V was calculated from the measured value of air change rates (ACH). Tracer gas techniques were used to determine ACH. V is the leakage through the floor of the exposed apartment. C o is leak the outdoor contaminant concentration. Cs is the contaminant concentration in the source apartment. is the sink effect of the contaminants in the exposed apartment. For gases can be ignored. During the tests, was unknown. The theoretical of contaminants concentration in the exposed apartment i.e. C r {t} are then compared with the measured values by adjusting the value of. Then a hypothetical value of V leak contaminant concentration C { t} r, in the exposed apartment was ob- 0 tained when there were no leakage through the floor i.e. V 0. V V VC t o V V V V C r, V t Co Cr e leak 0 { } i V V V V V C r {t} is the concentration of contaminants which are migrated from the source apartment and from any other source e.g. outdoor. C { } in the leak t r, 0 t r, 0 concentration of contaminants which are from sources other than source apartment. Hence the difference in C r {t} and C { } is the actual concentration of the contaminants which are been transferred from the source apartment to the exposed apartment. The percentage of contaminants transferred is obtained by using the following formula: C r{ 0 t} C { t} t r, V leak 100 C t s The is the ratio of the actual transfer of particle to the maximum possible transfer of particle within the particular time span. Hence in Part 1 of the was obtained with existing wooden floor. lab test o Afterwards in Part 2, the sealing membrane was placed under the wooden floor to analyse the performance of the membrane as a sealing against the transfer of contaminants. In Part 2, all the 9 steps of Part 1 of the lab tests were repeated and the transfer of contaminants were analysed. Hence an- was obtained. other value of sealing The percentage decrease in contaminants transfer due to the addition of the sealing membrane was obtained as: V leak V leak (6) (7) (8) sealing (9) o 14 3 Brüel & Kjær multigas monitor type Tinytag data ultra TGU 1500

37 Billions UFP /m 3 Billions UFP /m 3 Billions Findings Part 1 Air change rates (ACH) in the exposed apartment was measured using tracer-gas-concentration decay method. The air change rate in the exposed apartment was 3.8 ACH. Leakage through the flooring was 2.8 m 3 /h. To test the transfer of contaminants, the transfer of UFP and N 2 O was examined. During Part 1 of the lab tests, after lightening the cigarettes, UFP concentrations in the source apartment, the exposed apartments and outdoor air were logged. The logged values of UFP concentration of both source apartment and the exposed apartment are mentioned in Figure :00 12:28 12:57 13:26 13:55 Real Time Exposed apartment Source apartment Figure 4 variation UFP in the source and the exposed apartments without the sealing membrane during the lab 300 tests UFP /m 3 The 200 vertical axis is UFP concentration in billions and the horizontal axis is time. 100 The average temperature difference between two apartments was 5K :00 12:28 12:57 13:26 13:55 80 Real Time :00 12:28 12:57 13:26 13: :00 12:28 12:57 13:26 13:55 Real Time Outdoor Exposed apartment Exposed apartment - calculated Figure 5 up to 48% of the UFP from source apartment were transferred to the exposed apartment without the membrane during the lab tests Real Time Figure 5 illustrates three curves, Outdoor values which is a single average value of outdoor concentration during the experimental period. Exposed apartment which is the measured values of UFP in the exposed apartment, and Exposed apartment - calculated which is a curve obtained using Eq. (6). Since UFP sinking rate was not known, the value of was chosen in a way that the calculated values of UFP concentration give the best possible correlation with the measured values of UFP concentration in the exposed apartment. Figure 5 is obtained by using 0. 4 which is equivalent to the particle removal rate (from the exposed apartment) of 4.3 per hour. The total percentage of transferred UFP in the exposed apartment was obtained using 15

38 N 2 O {mg/m 3 } in the exposed apartment N 2 O x 100 {mg/m 3 } in the source apartment Eq. (8). Hence during Part 1 of the lab test 48% of UFP were transferred from source apartment to the exposed apartment. Similar to UFP, N 2 O gas was also measured and logged in the source and exposed apartments. The measured values are mentioned in Figure 6. The concentration of N 2 O in the exposed apartment is mentioned on the primary vertical axis whereas concentration in the source apartment is mentioned in the secondary vertical axis exposed measured source measured :28 12:57 13:26 13:55 14:24 Real Time Figure 6 variations in the N2O in the source and the exposed apartments during the lab tests without the sealing membrane For N 2 O sink rate is negligible i.e. 0. Hence by using Eq. (6) the calculated values of N 2 O concentration in the exposed apartment can be obtained. The calculated and measured values of N 2 O concentrations in the exposed apartment are mentioned in Figure 7. Average outdoor concentration of N 2 O is also mentioned in Figure 7. By using Eq. (8), it was found that 16.5% of N 2 O were transferred into the exposed apartment from the source apartment. N 2 O in mg/m Outdoor 0 12:28 12:57 13:26 13:55 14:24 Real Time Figure 7 up to 16.5% of the N2O from source apartment were transferred to the exposed apartment without the membrane during the lab tests exposed - calculated exposed measured Part 2 In Part 2 of the lab test, the membrane was installed below the wooden flooring of the exposed compartment. In Part 2, a similar procedure was performed as of Part 1 i.e. experimental steps 1 to 9. In Part 2 of the lab test, ACH remained almost unchanged i.e. 3.8 ACH. However, leakage through the flooring was decreased to 0.1 m 3 /h. The measured concentrations of UFP in the source and the exposed apartments are illustrated in Figure 8. In Figure 8 vertical axis is UFP concentrations in billions and horizontal axis the time. 16

39 N 2 O {mg/m 3 } in the exposed apartment N 2 O x 100 {mg/m 3 } in the source apartment Billions UFP /m 3 Billions UFP /m 3 Billions :24 14:52 15:21 15:50 16:19 Real Time Exposed apartment Source apartment Figure 8 variation in UFP in the exposed and source apartments after installation of the sealing membrane 300 during the lab tests UFP /m 3 Using 200 Eq. (6) and the same sinking rate as of Part 1 i.e. 0. 4, calculated 100 values of UFP concentration in the exposed apartment were obtained. The calculated values and measured values of UFP concentrations are illustrated 12:00 in Figure 9. 12:28 12:57 13: : Real Time :00 12:28 12:57 13:26 13: :24 14:52 15:21 15:50 16:19 Real Time Outdoor Exposed apartment Exposed apartment - calculated Figure 9 only 1.4 % of UFP from the source compartment were transferred to the exposed compartment after installation of the sealing membrane during the Real lab Time tests From Eq. (8) it was calculated that only 1.4% of UFP were transferred into the exposed apartment from the source apartment. A similar procedure was also performed for N 2 O. Measured values of N 2 O in the source and exposed apartments are illustrated in Figure 10. The primary vertical axis is the concentration of N 2 O in the exposed apartment whereas secondary vertical axis is the concentration of N 2 O in the source apartment exposed measured source measured :24 14:52 15:21 15:50 16:19 16:48 Real Time Figure 10 variations in N2O in the source and the exposed apartments during the lab tests after the installation of the sealing membrane The estimated concentrations of N 2 O in the exposed apartment are obtained through Eq. (6) and using 0, and the concentrations are illustrat- 17

40 ed in Figure 11. Measured concentration of N 2 O in the exposed apartment and the outdoor concentrations are also mentioned in Figure 11. By using Eq. (8) it was calculated that only 2.1% of N 2 O was transferred from source apartment to the exposed apartment. N 2 O in mg/m Outdoor exposed - calculated exposed measured 0 14:24 14:52 15:21 15:50 16:19 16:48 Real Time Figure 11 only 2.1% of N2O from source compartment were transferred to the exposed compartment after installation of the sealing membrane during the lab tests From Eq. (9) it was calculated that inclusion of the sealing membrane reduced transfer of UFP down to 97%. Likewise inclusion of sealing membrane reduced the transfer of N 2 O down to 87%. 18

41 In-situ measurements Method In principle, contaminants in any apartment can migrated from any of the adjacent apartment as shown in Figure 12. Figure 12 schematic of particle transfer into one apartment from adjacent apartments and outside However, previous studies have shown that the dominant parts of contaminants transfer in any apartment is due to the apartment which is exactly below that apartment as shown in Figure 13 (Afshari et al. 2010). Figure 13 assumption that the main source of contaminants transfer are from the apartment below and outside Therefore to reduce the complexities involved in the real life measurements, some assumptions were made which are as follows: 1) The source apartment is situated exactly below the exposed apartment as shown in Figure 13 2) The temperature outside all the boundaries of the exposed apartment (except the floor) is outdoor temperature as shown in Figure 14 3) The contaminants concentration on one side of exposed apartment (where the measuring instrument was set-up) represents the average outdoor contaminants concentration 4) Contaminants concentration in the source apartment are uniformly distributed 19

42 5) Temperature in the source and exposed apartment is uniform 6) The ventilation rate obtained through passive tracer gas techniques represents the ventilation rate during the measurements. Figure 14 temperatures in the exposed apartment, source apartment and outdoor atmosphere To analyse the performance of the sealing membrane in-situ, three apartments were selected in Copenhagen Denmark. The residents were already planning to renovate their apartment because of the following two reasons. The apartment was in need of refurbishment The residents were smelling cigarette smoke in their apartment. However, due to insufficient results in one of the apartment, only two apartments are reported here in the present report. In-situ measurements were divided into two parts. Part 1 was the measurements of the transfer of contaminants in the existing floors of the apartments. Part 2 was the measurements of contaminant transfer after installation of the sealing membrane. In Part1 of the measurements, all radiators of the exposed apartment were turned off and windows were opened to reduce the temperatures. After one hour all the windows were closed. Radiators in the source apartment were set to maximum to create a temperature difference. Moreover, portable heaters were also placed in the source apartment. It was also make sure that all the internal doors in both apartments are open i.e. creating a single zone. Three temperature loggers were placed in the exposed apartment. Three loggers were placed in the source apartment and one outdoor in order to measure the outdoor temperature and relative humidity. One particle counter was placed in the source apartment, one particle counter in the exposed apartment and one outside in order to measure background concentration. The transfers of UFP were examined in the onsite measurements. All counters were co-calibrated before the use. The instruments used in-situ measurements were same as used in the lab tests. The measurement steps were as follows: 1) Measurements of leakage through the floor a. Using passive tracer gas techniques 5 b. It was done before the measurements for a week 2) Measurements of the air change rates a. Using passive tracer gas techniques b. It was done before the measurements for a week 3) Creation of a pressure difference a) Turning off the radiators in the exposed apartment and opening of the windows until the room temperature reaches approximately outdoor temperature then closing of the window 20 5 PFT Techniques

43 UFP /m 3 Billions a. Turn on the radiator in the source compartment to create a pressure difference due to the difference in temperatures 4) Measurements of temperatures and humidity in both apartments and in outdoor 5) Measurements of UFP in both apartment and outdoor 6) Lighting a cigarette in the source apartment 7) Using a portable fan, mixing of the air in the source apartment 8) Monitoring and logging of the data in step 5 and 6. Instruments used in-situ and in laboratory were same. During the measurements it was make sure that temperature in the source apartment is greater than the temperatures in the exposed apartment as shown in Figure 14. Afterwards, Part 2 of the onsite measurements was carried out. The measurement procedure in Part 2 was same as of Part 1. Findings Apartment 1 Irmingersgade 9, 2100 Copenhagen Part1 Part 1 of measurement (before the renovation) was conducted exactly in the same manner as mentioned in the Method section. During the measurements the temperature difference was approximately 3 K. The area of the apartment 1 was 37.3 m 2 with an average height of 2.72 m. UFP concertation in the source and the exposed apartment are shown in Figure 15. The increase in UFP concentration in the exposed apartment was due to the increase in UFP concentration in the source apartment :36 10:48 12:00 13:12 Real Time Figure 15 variations in UFP concentration in the source and the exposed apartment before the renovation of 300 Apartment 1 UFP /m 3 Exposed apartment Source apartment Using 200 Eq. (6) the calculated value of UFP concentration in the exposed apartment 100 was obtained. The leakage rate was V leak 20m 3 / h. The sink rate that 0 gave the best possible correlation with the measured values was 0.512:00. The calculated 12:28 and 12:57 measured 13:26values 13:55 of UFP concentrations in the exposed apartment are illustrated Real Timein Figure 16. Outdoor UFP concentrations are also mentioned in Figure 16. Using Eq. (8) it was calculated that the 16.2% of UFP from the source apartment was transferred into the exposed apartment. 21

44 Billions UFP /m 3 Billions :00 12:28 12:57 13:26 13:55 09:36 10:48 12:00 Real Time 13:12 Outdoor Exposed apartment Exposed apartment - calculated Figure 16 up to16.2% of UFP from the source apartment were transferred to the exposed apartment before the renovation of Apartment 1 Real Time Afterwards the apartment was renovated. The placement of the sealing membrane was carried out according to the guidelines provided by the manufacturer 6. Few photos that were taken during the renovation work are shown in Figure 17. Figure 17 condition of wooden flooring during the renovation Figure 18 shows how the sealing membrane was placed before final wooden flooring. During the renovation, SBi provided the required quantity of the sealing membrane for the apartments

45 Figure 18 installation of the sealing membrane (ctrap) Part 2 After installation of the sealing membrane and the complete renovation of Apartment 1, Part 2 of the measurements was carried out. The measurements in Part 2 were carried out in the similar manner as of Part 1. UFP concentration in the source and the exposed apartments are shown in Figure

46 Billions UFP /m 3 Billions UFP /m 3 Billions :48 11:16 11:45 12:14 12:43 13:12 Real Time Exposed apartment Source apartment Figure 19 variation in UFP concentrations of the source and the exposed apartment after the renovation of Apartment UFP /m 3 The 200 increase in UFP concentration in the exposed apartment due to the increase 100 in UFP concentration in the source apartment was not as high as it was before the renovation. However, for accurate analysis, the calculated values 0 of UFP concentrations in the exposed apartment were obtained using 12:00 12:28 12:57 13:26 13:55 Eq. (6) and are shown in Figure 20. The outdoor concentration and the measured UFP concentration Real Time in the exposed apartment are also shown in Figure 20. The calculated values are obtained by using V leak 15m 3 / h and 0.5 i.e. same value as used in Part 1. The difference in temperature during the measurement was 2K :00 12:28 12:57 13:26 13:55 10:48 11:16 11:45 12:14 12:43 13:12 Real Time Outdoor Exposed apartment Exposed apartment - calculated Figure 20 only 7.6% of UFP from the source apartment were transferred to the exposed apartment after the renovation of Apartment 1 Real Time Using Eq. (8) it was calculated that only 7.6% of UFP were migrated from the source apartment to the exposed apartment. Using Eq. (9) it was calculated that installation of the sealing membrane reduced the transfer of UFP down to 53%. 24

47 Billions UFP /m 3 Billions UFP /m 3 Billions Apartment 2 Hørsholmgade 26, 2200 Copenhagen Part 1 A set of measurement before the renovation was conducted exactly in the same manner as of Apartment 1. The average difference in temperature between the source and the exposed apartments were 5K. The area of the apartment 1 was 60.1 m 2 with an average height of 2.5 m. Similar to the Apartment 1, passive tracer gas techniques were used to determine the air change rates and the leakage through the floor. Figure 21 shows UFP concentration of exposed and the source apartment during Part 1 of the measurements :00 13:12 14:24 15:36 Real Time Exposed apartment Source apartment Figure 21 variations in UFP concentration in the source and the exposed apartments before the renovation of 300 Apartment 2 UFP /m 3 Using 200 Eq. (6) the calculated values of UFP concentration in the exposed apartment 100 were obtained which are illustrated in Figure 22 along with the measured UFP concentration and outdoor UFP concentration :00 12:28 12:57 13:26 13:55 14 Real Time :00 12:28 12:57 13:26 13:55 12:00 13:12 14:24 15:36 Real Time Outdoor Exposed apartment Exposed apartment - calculated Figure 22 up to 4% of UFP from the source apartment were transferred to the exposed apartment before the renovation of Apartment 2 Real Time The calculated values in Figure 22 are obtained from the measured value of leakage through the floor i.e. V leak 10m 3 / h and the particle sinking rate of From Eq. (8) it was calculated that 4% of UFP were transferred from the source apartment to the exposed apartment. Part 2 The membrane sealing was placed in the similar manner as shown in Apartment 1. After the renovation, Part 2 of the measurements was carried 25

48 Billions UFP /m 3 Billions UFP /m 3 Billions out using the same measurement procedure as of Part 1 of the measurements. UFP concentration in the source and the exposed apartments during Part 2 of the measurements are illustrated in Figure 23. The increase in UFP in the exposed apartments was due to the increase in UFP in the source apartment. The decrease in UFP with time is due to the ventilation rates. The difference in temperatures between the source and the exposed apartment was 4.8 K :31 13:55 16:19 Real Time Figure 23 variations in UFP concentrations of the source and the exposed apartments after the renovation of 300 Apartment 2 UFP /m 3 Exposed apartment Source apartment Using 200 Eq. (6) calculated concentrations of UFP in the exposed apartment were 100 obtained. Calculated concentrations and the measured concentrations in the exposed apartment are illustrated in Figure 24. Outdoor UFP concentration 0 is also mentioned in Figure 24. The calculated values are obtained 12:00 12:28 12:57 13:26 13:55 with the measured leakage rate of V m h Real Time leak 1 3 / and the particle sinking value of 0. 5 i.e. same as Part :00 12:28 12:57 13:26 13:55 11:31 12:43 13:55 15:07 16:19 Real Time Outdoor Exposed apartment Exposed apartment - calculated Figure 24 only 1.6% of UFP from the source apartment were transferred to the exposed apartment after the renovation of Apartment 2 Real Time Using Eq. (8) it was calculated that after renovation only 1.6% of UFP were transferred from the source apartment to the exposed apartment. Using Eq. (9) it was calculated that inclusion of the sealing membrane reduced the transfer of UFP down to 60%. 26

49 Problems, errors and sources of errors during the insitu measurements Insitu measurements were performed before the laboratory measurements. The purpose of laboratory measurements were reduced the uncertainties in understanding the insitu performance. During insitu measurements, certain data was lost due to mishandling of the instruments. Foremost are the leakage rates through the ceiling of the exposed apartments. The data for the leakage rates through the ceilings were only available for after renovation measurements. Therefore the leakage rate before the renovation was calculated in an indirect manner. First using the measured leakage rate (using PFT) after the renovation was used to estimate the approximate sink rates of the particle in Eq. (7). Then the sink rate of after renovation measurements was assumed to be the same for the particles in before renovation measurements. Afterwards the leakage rates before the renovations were obtained by choosing the value that fits the curve shown in Figure 16 and Figure 22. Similarly to measure the transfer of gases CO 2 was used in both apartments. However, due to some unknown errors in the measurements, results were discarded as it was impossible to make any conclusion out of them. Hence the laboratory experiments were performed for the analyses gas transfer as well as particle transfer in a controlled environment. 27

50 Occupants perception After four months of the renovation the occupants were asked to express their perception regarding the performance of the membrane in achieving the adequate indoor environment. An online questionnaire was distributed to the occupants. The questions and answers from the residents of each apartment are as follows: Questions Before the renovation To what extent were you bothered by the cigarette smoke before the renovation? Answers Apartment 1 Apartment 2 High High Did you experience any symptom of smoke on your or others in your apartment e.g. any disease or continuous illness? To what extent were you bothered by the other smells from other apartments e.g. cooking? Did you visualize the any dust particles coming from other apartment into your apartment? Low Low Low No Medium No After the renovation Have the installation of sealing membrane reduced the smell(s) neighboring apartments? Have the installation of sealing membrane changed the indoor air quality in any other ways, which are not associated with the smell of smoke? How? High Yes Low ventilation is required High Yes Better indoor air quality Would you like recommend others to use ctrap to stop odors from smoke or other types of odors? Yes Yes The residents of both apartments were bothered by the smell from their neighbors. Even the residents of Apartment 1 were also occasionally able to visualize the particles in their apartment. However after installation of the sealing membrane both residents are highly satisfied. Moreover the residents of both apartments also perceive that indoor air quality is improved after renovation. 28

51 Percentage of UFP transfer DISCUSSION Tests were conducted in controlled conditions 50% 45% 40% 35% 30% 25% 20% 15% 10% 05% 00% Tests were conducted inmay 15 & June 15 Lab Tests Apartment 1 Apartment 2 w/o ctrap ctrap Figure 25 summary of the performance of the sealing membrane at different locations Tests were conducted in April 15 and Jan 16 The findings from the present study are summarised in Figure 25. The findings from the present study are an important step towards the understanding of performance of the membrane as a sealing against contaminants. However, contaminants transfer depends on several factors; some are uncontrollable especially in-situ measurements. Therefore in the present study there was a difference in the performance of membrane sealing in the laboratory and in-situ. In laboratory, where the floor was the only possibility of transferring of particles, the sealing reduced the transfer of UFP down to 97% and transfer of N 2 O down to 87.5% from source to exposed apartment. Whereas; in-situ results showed that, in real life it is difficult to seal the floor as exactly as in the laboratory conditions. Therefore in real conditions the sealing membrane reduced the transfer of UFP down to 53% to 60% as shown in Figure 26. Concentrations of outdoor UFP were measured on the one side of the apartments. However, due to the fact that outdoor particle concentration fluctuates among different outdoor locations for instance UFP concentration on the north side could be different from UFP concentration on the south side. Therefore there is a possibility of uncertainty in the accurate values of particles that are being transferred from outdoor. Likewise there is a possibility that the particles in the source apartment are not uniformly distributed. 29

52 97% 53% 60% Lab Tests Apartment 1 Apartment 2 Figure 26 percentage of reduction in UFP transfer from source apartment to the exposed apartment during the study Other possible reasons of underperformance of the membrane in-situ were the fact that the difference in temperature between source and exposed apartment was different during the measurements before and after renovation. These are the limitations that cannot be overcome in the real life experiments. Another possible reason of the underperformance of the membrane (in comparison with the lab tests) is the fact that in real apartments, there is always a chance of particle transfer through passages other than floor e.g. crakes in walls, electrical sockets, exhaust ducts etc. The benefit of the studied sealing membrane over other solutions of contaminant reduction is that the sealing membrane stops and captures the contaminants before entering into the exposed zone instead of diluting the concentration of contaminants after they enter into the exposed zone. Therefore the occupants will be exposed to a reduced number of UFP whenever the ctrap will be used as sealing membrane against contaminants. A small occupants survey was conducted after the renovation which showed that the occupants, before the refurbishment, were continuously irritated by cigarette smell from their neighbours. However, the occupants are fully satisfied with the performance of the membrane sealing as the occupants are not smelling cigarettes anymore. Moreover, after installation of the sealing membrane occupants are perceiving better indoor air quality. Future work To fully understand the performance of the sealing membrane, there is a need to analyse the performance at several temperature differences i.e. between source and exposed, exposed and outdoor. Likewise there is a need to analyse the performance of the sealing membrane after few years of installation in real life. 30

53 CONCLUSIONS A novel sealing membrane was used to trap and stop the transfer of contaminants between two spaces. The study showed that the sealing membrane can trap the significant percentage of the UFP and N 2 O. In ideal situation, i.e. laboratory conditions, the membrane reduced the transfer of UFP down to 97% and N 2 O up to 87%. In real conditions i.e. in-situ, the membrane reduced the transfer of UFP down to 53% to 60%. A small occupant s survey was conducted after the renovation which shows that the users are fully satisfied with the performance of the membrane sealing and they perceive better indoor air quality. Hence it is concluded that the studied sealing membrane is an effective solution in trapping and stopping unwanted contaminants. 31

54

55 REFERENCES AFSHARI, A., BERGSØE, N.C. and ARDKAPAN, S.R., Filtration of ultrafine particles from tobacco smoke using an ionizer in combination with an electrostatic fibrous filter, Indoor Air 2014China - Hong Kong, 07/07/ /07/ AFSHARI, A., MARKOWICZ, P., LARSSON, L., BERGSØE, N.C. and ARDKAPAN, S.R., Evaluating the effectiveness of two membranes in blocking chemicals, Proceedings Indoor Air - Hong Kong, 07/07/ /07/ AFSHARI, A., SHI, B., BERGSØE, N.C., EKBERG, L.A. and LARSSON, T., Quantification of ultrafine particles from second-hand tobacco smoke, Proceedings of Clima 2010 : 10th REHVA World Congress 'Sustainable Energy use in Buildings; Turkey - Antalya, 09/05/ /05/ EKBERG, L.E. and SHI, B., Removal of ultrafine particles by ventilation air filters, Proceeding of Healthy Buildings 2009, Syracuse, USA 2009, pp. (Paper 97) 4 pages. GUNNER, A., ARDKAPAN, S.R., AFSHARI, A. and BERGSØE, N.C., Transfer of ultrafine particles and air in multi-storey buildings. Journal of Civil Engineering and Architecture, 8(4),. MARKOWICZ, P. and LARSSON, L., The surface emissions trap: A new approach in indoor air purification. Journal of microbiological methods, 91(2), pp NILSSON, P., Achieving the desired indoor climate: energy efficiency aspects of system design. Studentlitteratur. 33

56

57 Bilag 2 Produktblade ctrap B

58

59

SBi 2012:13. Overføring af ultrafine partikler og luft mellem to etageadskilte lejligheder

SBi 2012:13. Overføring af ultrafine partikler og luft mellem to etageadskilte lejligheder SBi 2012:13 Overføring af ultrafine partikler og luft mellem to etageadskilte lejligheder Overføring af ultrafine partikler og luft mellem to etageadskilte lejligheder Amalie Gunner Siamak Rahimi Ardkapan

Læs mere

The effects of occupant behaviour on energy consumption in buildings

The effects of occupant behaviour on energy consumption in buildings The effects of occupant behaviour on energy consumption in buildings Rune Vinther Andersen, Ph.D. International Centre for Indoor Environment and Energy Baggrund 40 % af USA's samlede energiforbrug sker

Læs mere

Statistical information form the Danish EPC database - use for the building stock model in Denmark

Statistical information form the Danish EPC database - use for the building stock model in Denmark Statistical information form the Danish EPC database - use for the building stock model in Denmark Kim B. Wittchen Danish Building Research Institute, SBi AALBORG UNIVERSITY Certification of buildings

Læs mere

Kort informativ sammenfatning af projektets resultater og konklusioner

Kort informativ sammenfatning af projektets resultater og konklusioner Kort informativ sammenfatning af projektets resultater og konklusioner Indledning Passiv rygning på grund af luftoverføring mellem lejligheder, såkaldt naborøg, er en vigtig sag for mange beboere i etageboliger.

Læs mere

Small Autonomous Devices in civil Engineering. Uses and requirements. By Peter H. Møller Rambøll

Small Autonomous Devices in civil Engineering. Uses and requirements. By Peter H. Møller Rambøll Small Autonomous Devices in civil Engineering Uses and requirements By Peter H. Møller Rambøll BACKGROUND My Background 20+ years within evaluation of condition and renovation of concrete structures Last

Læs mere

To the reader: Information regarding this document

To the reader: Information regarding this document To the reader: Information regarding this document All text to be shown to respondents in this study is going to be in Danish. The Danish version of the text (the one, respondents are going to see) appears

Læs mere

Basic statistics for experimental medical researchers

Basic statistics for experimental medical researchers Basic statistics for experimental medical researchers Sample size calculations September 15th 2016 Christian Pipper Department of public health (IFSV) Faculty of Health and Medicinal Science (SUND) E-mail:

Læs mere

Unitel EDI MT940 June 2010. Based on: SWIFT Standards - Category 9 MT940 Customer Statement Message (January 2004)

Unitel EDI MT940 June 2010. Based on: SWIFT Standards - Category 9 MT940 Customer Statement Message (January 2004) Unitel EDI MT940 June 2010 Based on: SWIFT Standards - Category 9 MT940 Customer Statement Message (January 2004) Contents 1. Introduction...3 2. General...3 3. Description of the MT940 message...3 3.1.

Læs mere

Dumped ammunition - an environmental problem for sediment management?

Dumped ammunition - an environmental problem for sediment management? 5th International SedNet Conference, 27th-29th May 2008, Oslo, Norway Dumped ammunition - an environmental problem for sediment management? Jens Laugesen, Det Norske Veritas Harald Bjørnstad, Forsvarsbygg

Læs mere

Datablad: Nature Impact Roof modul

Datablad: Nature Impact Roof modul 1 Datablad: Nature Impact Roof modul Modul: Modulmål: 535 X 405 mm. Højde grundmodul: 40 mm. Højde vækstlag: ca. 6 cm. Total byggehøjde: ca. 6 cm + planter Vægt fuld vandmættet: 45 kg./m 2. Vandtilbageholdelse:

Læs mere

Generalized Probit Model in Design of Dose Finding Experiments. Yuehui Wu Valerii V. Fedorov RSU, GlaxoSmithKline, US

Generalized Probit Model in Design of Dose Finding Experiments. Yuehui Wu Valerii V. Fedorov RSU, GlaxoSmithKline, US Generalized Probit Model in Design of Dose Finding Experiments Yuehui Wu Valerii V. Fedorov RSU, GlaxoSmithKline, US Outline Motivation Generalized probit model Utility function Locally optimal designs

Læs mere

Afprøvning af InVentilate Ventilationssystem

Afprøvning af InVentilate Ventilationssystem Afprøvning af InVentilate Ventilationssystem P. Heiselberg Udarbejdet for: InVentilate A/S DCE Contract Report No. 108 Department of Civil Engineering Aalborg University Department of Civil Engineering

Læs mere

Ventilation. Du skal selv være med til at holde din lejlighed sund You are responsible too: keep your apartment healthy

Ventilation. Du skal selv være med til at holde din lejlighed sund You are responsible too: keep your apartment healthy Ventilation Du skal selv være med til at holde din lejlighed sund You are responsible too: keep your apartment healthy Ventilation Ventilation Din lejlighed er renoveret, for at du skal have et sundt indeklima.

Læs mere

Project Step 7. Behavioral modeling of a dual ported register set. 1/8/ L11 Project Step 5 Copyright Joanne DeGroat, ECE, OSU 1

Project Step 7. Behavioral modeling of a dual ported register set. 1/8/ L11 Project Step 5 Copyright Joanne DeGroat, ECE, OSU 1 Project Step 7 Behavioral modeling of a dual ported register set. Copyright 2006 - Joanne DeGroat, ECE, OSU 1 The register set Register set specifications 16 dual ported registers each with 16- bit words

Læs mere

Trolling Master Bornholm 2014

Trolling Master Bornholm 2014 Trolling Master Bornholm 2014 (English version further down) Den ny havn i Tejn Havn Bornholms Regionskommune er gået i gang med at udvide Tejn Havn, og det er med til at gøre det muligt, at vi kan være

Læs mere

Bilag. Resume. Side 1 af 12

Bilag. Resume. Side 1 af 12 Bilag Resume I denne opgave, lægges der fokus på unge og ensomhed gennem sociale medier. Vi har i denne opgave valgt at benytte Facebook som det sociale medie vi ligger fokus på, da det er det største

Læs mere

The X Factor. Målgruppe. Læringsmål. Introduktion til læreren klasse & ungdomsuddannelser Engelskundervisningen

The X Factor. Målgruppe. Læringsmål. Introduktion til læreren klasse & ungdomsuddannelser Engelskundervisningen The X Factor Målgruppe 7-10 klasse & ungdomsuddannelser Engelskundervisningen Læringsmål Eleven kan give sammenhængende fremstillinger på basis af indhentede informationer Eleven har viden om at søge og

Læs mere

Kort informativ sammenfatning af projektets resultater og konklusioner

Kort informativ sammenfatning af projektets resultater og konklusioner Kort informativ sammenfatning af projektets resultater og konklusioner Indledning Passiv rygning på grund af luftoverføring mellem lejligheder, såkaldt naborøg, er en vigtig sag for mange beboere i etageboliger.

Læs mere

Mandara. PebbleCreek. Tradition Series. 1,884 sq. ft robson.com. Exterior Design A. Exterior Design B.

Mandara. PebbleCreek. Tradition Series. 1,884 sq. ft robson.com. Exterior Design A. Exterior Design B. Mandara 1,884 sq. ft. Tradition Series Exterior Design A Exterior Design B Exterior Design C Exterior Design D 623.935.6700 robson.com Tradition OPTIONS Series Exterior Design A w/opt. Golf Cart Garage

Læs mere

Slot diffusers. Slot diffusers LD-17, LD-18

Slot diffusers. Slot diffusers LD-17, LD-18 LD-17, LD-18 Application LD-17 and LD-18 are designed for supply of cold or warm air in rooms with a height between. m and 4 m. They allow easy setting of air deflectors for different modes of operation

Læs mere

On the complexity of drawing trees nicely: corrigendum

On the complexity of drawing trees nicely: corrigendum Acta Informatica 40, 603 607 (2004) Digital Object Identifier (DOI) 10.1007/s00236-004-0138-y On the complexity of drawing trees nicely: corrigendum Thorsten Akkerman, Christoph Buchheim, Michael Jünger,

Læs mere

Aktivering af Survey funktionalitet

Aktivering af Survey funktionalitet Surveys i REDCap REDCap gør det muligt at eksponere ét eller flere instrumenter som et survey (spørgeskema) som derefter kan udfyldes direkte af patienten eller forsøgspersonen over internettet. Dette

Læs mere

Vores mange brugere på musskema.dk er rigtig gode til at komme med kvalificerede ønsker og behov.

Vores mange brugere på musskema.dk er rigtig gode til at komme med kvalificerede ønsker og behov. På dansk/in Danish: Aarhus d. 10. januar 2013/ the 10 th of January 2013 Kære alle Chefer i MUS-regi! Vores mange brugere på musskema.dk er rigtig gode til at komme med kvalificerede ønsker og behov. Og

Læs mere

Engelsk. Niveau D. De Merkantile Erhvervsuddannelser September Casebaseret eksamen. og

Engelsk. Niveau D. De Merkantile Erhvervsuddannelser September Casebaseret eksamen.  og 052431_EngelskD 08/09/05 13:29 Side 1 De Merkantile Erhvervsuddannelser September 2005 Side 1 af 4 sider Casebaseret eksamen Engelsk Niveau D www.jysk.dk og www.jysk.com Indhold: Opgave 1 Presentation

Læs mere

USERTEC USER PRACTICES, TECHNOLOGIES AND RESIDENTIAL ENERGY CONSUMPTION

USERTEC USER PRACTICES, TECHNOLOGIES AND RESIDENTIAL ENERGY CONSUMPTION USERTEC USER PRACTICES, TECHNOLOGIES AND RESIDENTIAL ENERGY CONSUMPTION P E R H E I S E L BERG I N S T I T U T F OR BYGGERI OG A N L Æ G BEREGNEDE OG FAKTISKE FORBRUG I BOLIGER Fra SBi rapport 2016:09

Læs mere

Central Statistical Agency.

Central Statistical Agency. Central Statistical Agency www.csa.gov.et 1 Outline Introduction Characteristics of Construction Aim of the Survey Methodology Result Conclusion 2 Introduction Meaning of Construction Construction may

Læs mere

Engelsk. Niveau C. De Merkantile Erhvervsuddannelser September 2005. Casebaseret eksamen. www.jysk.dk og www.jysk.com.

Engelsk. Niveau C. De Merkantile Erhvervsuddannelser September 2005. Casebaseret eksamen. www.jysk.dk og www.jysk.com. 052430_EngelskC 08/09/05 13:29 Side 1 De Merkantile Erhvervsuddannelser September 2005 Side 1 af 4 sider Casebaseret eksamen Engelsk Niveau C www.jysk.dk og www.jysk.com Indhold: Opgave 1 Presentation

Læs mere

Help / Hjælp

Help / Hjælp Home page Lisa & Petur www.lisapetur.dk Help / Hjælp Help / Hjælp General The purpose of our Homepage is to allow external access to pictures and videos taken/made by the Gunnarsson family. The Association

Læs mere

KALK- OG TEGLVÆRKSFORENINGEN. CPR Sustainable Construction

KALK- OG TEGLVÆRKSFORENINGEN. CPR Sustainable Construction CPR Sustainable Construction 1 Tommy Bisgaard - Direktør i Kalk- og Teglværksforeningen - Formand for DS 417 (CEN TC350 & 351) - Formand for miljøkomiteen i TBE & CU (keramiske industrier i Europa) - Medlem

Læs mere

Mandara. PebbleCreek. Tradition Series. 1,884 sq. ft robson.com. Exterior Design A. Exterior Design B.

Mandara. PebbleCreek. Tradition Series. 1,884 sq. ft robson.com. Exterior Design A. Exterior Design B. Mandara 1,884 sq. ft. Tradition Series Exterior Design A Exterior Design B Exterior Design C Exterior Design D 623.935.6700 robson.com Tradition Series Exterior Design A w/opt. Golf Cart Garage Exterior

Læs mere

De tre høringssvar findes til sidst i dette dokument (Bilag 1, 2 og 3). I forlængelse af de indkomne kommentarer bemærkes følgende:

De tre høringssvar findes til sidst i dette dokument (Bilag 1, 2 og 3). I forlængelse af de indkomne kommentarer bemærkes følgende: NOTAT VEDR. HØRINGSSVAR København 2018.10.26 BAGGRUND: Kommunalbestyrelsen i Frederiksberg Kommune vedtog den 18. april 2016 at igangsætte processen omkring etablering af et fælles gårdanlæg i karré 41,

Læs mere

GUIDE TIL BREVSKRIVNING

GUIDE TIL BREVSKRIVNING GUIDE TIL BREVSKRIVNING APPELBREVE Formålet med at skrive et appelbrev er at få modtageren til at overholde menneskerettighederne. Det er en god idé at lægge vægt på modtagerens forpligtelser over for

Læs mere

Gusset Plate Connections in Tension

Gusset Plate Connections in Tension Gusset Plate Connections in Tension Jakob Schmidt Olsen BSc Thesis Department of Civil Engineering 2014 DTU Civil Engineering June 2014 i Preface This project is a BSc project credited 20 ECTS points written

Læs mere

X M Y. What is mediation? Mediation analysis an introduction. Definition

X M Y. What is mediation? Mediation analysis an introduction. Definition What is mediation? an introduction Ulla Hvidtfeldt Section of Social Medicine - Investigate underlying mechanisms of an association Opening the black box - Strengthen/support the main effect hypothesis

Læs mere

F o r t o l k n i n g e r a f m a n d a l a e r i G I M - t e r a p i

F o r t o l k n i n g e r a f m a n d a l a e r i G I M - t e r a p i F o r t o l k n i n g e r a f m a n d a l a e r i G I M - t e r a p i - To fortolkningsmodeller undersøgt og sammenlignet ifm. et casestudium S i g r i d H a l l b e r g Institut for kommunikation Aalborg

Læs mere

Udfordringer med indeklima ved energirenovering

Udfordringer med indeklima ved energirenovering Udfordringer med indeklima ved energirenovering Geo Clausen International Centre for Indoor Environment and Energy Department of Civil Engineering Technical University of Denmark Questionnaire survey Henrik

Læs mere

Trolling Master Bornholm 2012

Trolling Master Bornholm 2012 Trolling Master Bornholm 1 (English version further down) Tak for denne gang Det var en fornøjelse især jo også fordi vejret var med os. Så heldig har vi aldrig været før. Vi skal evaluere 1, og I må meget

Læs mere

Pollution from shipping in Denmark

Pollution from shipping in Denmark AARHUS UNIVERSITET Pollution from shipping in Denmark Thomas Ellermann, Helge R. Olesen, Jesper Christensen, Morten Winther, and Marlene Plejdrup National Environmental Research Institute, Aarhus University

Læs mere

frame bracket Ford & Dodge

frame bracket Ford & Dodge , Rev 3 02/19 frame bracket 8552005 Ford & Dodge ITEM PART # QTY DESCRIPTION 1 00083 8 NUT,.50NC HEX 2 00084 8 WASHER,.50 LOCK 3 14189-76 2 FRAME BRACKET 4 14194-76 1 411AL FRAME BRACKET PASSENGER SIDE

Læs mere

Childhood motor performance as predictor of physical activity and physical activity related injuries

Childhood motor performance as predictor of physical activity and physical activity related injuries Childhood motor performance as predictor of physical activity and physical activity related injuries The Childhood Health, Activity and Motor Performance School Study- DK The CHAMPS Study- DK Lisbeth Runge

Læs mere

Statistik for MPH: 7

Statistik for MPH: 7 Statistik for MPH: 7 3. november 2011 www.biostat.ku.dk/~pka/mph11 Attributable risk, bestemmelse af stikprøvestørrelse (Silva: 333-365, 381-383) Per Kragh Andersen 1 Fra den 6. uges statistikundervisning:

Læs mere

Avancerede bjælkeelementer med tværsnitsdeformation

Avancerede bjælkeelementer med tværsnitsdeformation Avancerede bjælkeelementer med tværsnitsdeformation Advanced beam element with distorting cross sections Kandidatprojekt Michael Teilmann Nielsen, s062508 Foråret 2012 Under vejledning af Jeppe Jönsson,

Læs mere

Evaluating Germplasm for Resistance to Reniform Nematode. D. B. Weaver and K. S. Lawrence Auburn University

Evaluating Germplasm for Resistance to Reniform Nematode. D. B. Weaver and K. S. Lawrence Auburn University Evaluating Germplasm for Resistance to Reniform Nematode D. B. Weaver and K. S. Lawrence Auburn University Major objectives Evaluate all available accessions of G. hirsutum (TX list) for reaction to reniform

Læs mere

Dendrokronologisk Laboratorium

Dendrokronologisk Laboratorium Dendrokronologisk Laboratorium NNU rapport 14, 2001 ROAGER KIRKE, TØNDER AMT Nationalmuseet og Den Antikvariske Samling i Ribe. Undersøgt af Orla Hylleberg Eriksen. NNU j.nr. A5712 Foto: P. Kristiansen,

Læs mere

Measuring the Impact of Bicycle Marketing Messages. Thomas Krag Mobility Advice Trafikdage i Aalborg, 27.08.2013

Measuring the Impact of Bicycle Marketing Messages. Thomas Krag Mobility Advice Trafikdage i Aalborg, 27.08.2013 Measuring the Impact of Bicycle Marketing Messages Thomas Krag Mobility Advice Trafikdage i Aalborg, 27.08.2013 The challenge Compare The pilot pictures The choice The survey technique Only one picture

Læs mere

applies equally to HRT and tibolone this should be made clear by replacing HRT with HRT or tibolone in the tibolone SmPC.

applies equally to HRT and tibolone this should be made clear by replacing HRT with HRT or tibolone in the tibolone SmPC. Annex I English wording to be implemented SmPC The texts of the 3 rd revision of the Core SPC for HRT products, as published on the CMD(h) website, should be included in the SmPC. Where a statement in

Læs mere

Design til digitale kommunikationsplatforme-f2013

Design til digitale kommunikationsplatforme-f2013 E-travellbook Design til digitale kommunikationsplatforme-f2013 ITU 22.05.2013 Dreamers Lana Grunwald - svetlana.grunwald@gmail.com Iya Murash-Millo - iyam@itu.dk Hiwa Mansurbeg - hiwm@itu.dk Jørgen K.

Læs mere

Immigration Housing. Housing - Renting. Stating that you want to rent something. Type of accommodation. Type of accommodation. Type of accommodation

Immigration Housing. Housing - Renting. Stating that you want to rent something. Type of accommodation. Type of accommodation. Type of accommodation - Renting English I am looking for a to rent. Stating that you want to rent something room flat / apartment studio flat / studio apartment detached house semi-detached house terraced house How much is

Læs mere

Portal Registration. Check Junk Mail for activation . 1 Click the hyperlink to take you back to the portal to confirm your registration

Portal Registration. Check Junk Mail for activation  . 1 Click the hyperlink to take you back to the portal to confirm your registration Portal Registration Step 1 Provide the necessary information to create your user. Note: First Name, Last Name and Email have to match exactly to your profile in the Membership system. Step 2 Click on the

Læs mere

Besvarelser til Lineær Algebra Reeksamen Februar 2017

Besvarelser til Lineær Algebra Reeksamen Februar 2017 Besvarelser til Lineær Algebra Reeksamen - 7. Februar 207 Mikkel Findinge Bemærk, at der kan være sneget sig fejl ind. Kontakt mig endelig, hvis du skulle falde over en sådan. Dette dokument har udelukkende

Læs mere

Global carbon cycle studies with LPJ-GUESS

Global carbon cycle studies with LPJ-GUESS Navn oplægsholder Navn KUenhed Global carbon cycle studies with LPJ-GUESS Guy Schurgers University of Copenhagen Introduction LPJ-GUESS The dynamic ecosystem model LPJ-GUESS simulates biogeography (geographical

Læs mere

Afsætning af sprøjtevæske gennem fiberdug

Afsætning af sprøjtevæske gennem fiberdug Afsætning af sprøjtevæske gennem fiberdug Projekt: udvikling af nye teknikker i behandling af havebrugskulturer English summery Title: Deposition on small plants when spraying through fleece with conventional

Læs mere

SKEMA TIL AFRAPPORTERING EVALUERINGSRAPPORT

SKEMA TIL AFRAPPORTERING EVALUERINGSRAPPORT SKEMA TIL AFRAPPORTERING EVALUERINGSRAPPORT OBS! Excel-ark/oversigt over fagelementernes placering i A-, B- og C-kategorier skal vedlægges rapporten. - Følgende bedes udfyldt som del af den Offentliggjorte

Læs mere

Midlertidig ændring af vandstand som redskab til vedligeholdelse af lobeliesøer

Midlertidig ændring af vandstand som redskab til vedligeholdelse af lobeliesøer Lake Skærsø, Denmark Midlertidig ændring af vandstand som redskab til vedligeholdelse af lobeliesøer Anna-Marie Klamt, Kasper Reitzel, Frede Ø. Andersen, Henning S. Jensen CLEAR temadag 24 May 2016 Syddansk

Læs mere

Trolling Master Bornholm 2014

Trolling Master Bornholm 2014 Trolling Master Bornholm 2014 (English version further down) Ny præmie Trolling Master Bornholm fylder 10 år næste gang. Det betyder, at vi har fundet på en ny og ganske anderledes præmie. Den fisker,

Læs mere

Vina Nguyen HSSP July 13, 2008

Vina Nguyen HSSP July 13, 2008 Vina Nguyen HSSP July 13, 2008 1 What does it mean if sets A, B, C are a partition of set D? 2 How do you calculate P(A B) using the formula for conditional probability? 3 What is the difference between

Læs mere

Luftskifte Hvad ved vi og hvad kan vi?

Luftskifte Hvad ved vi og hvad kan vi? Luftskifte Hvad ved vi og hvad kan vi? Geo Clausen Institut for Byggeri og Anlæg DTU Find Jacob Find Jacob igen Reflektioner. Risiko for konflikt mellem at reducere energiforbrug i bygninger og menneskers

Læs mere

Læs venligst Beboer information om projekt vandskade - sikring i 2015/2016

Læs venligst Beboer information om projekt vandskade - sikring i 2015/2016 Læs venligst Beboer information om projekt vandskade - sikring i 2015/2016 Vi er nødsaget til at få adgang til din lejlighed!! Hvis Kridahl (VVS firma) har bedt om adgang til din/jeres lejlighed og nøgler,

Læs mere

Geo Clausen. Center for Indeklima og Sundhed i Boliger Realdania Forskning. Center for Indeklima og Energi Danmarks Tekniske Universitet

Geo Clausen. Center for Indeklima og Sundhed i Boliger Realdania Forskning. Center for Indeklima og Energi Danmarks Tekniske Universitet Eksponeringsundersøgelser: Hvilke sammenhænge er der mellem beboernes adfærd og boligens indeklima, og hvilke forhold er vigtigst at holde øje med for at opnå et godt indeklima? Geo Clausen Center for

Læs mere

PARALLELIZATION OF ATTILA SIMULATOR WITH OPENMP MIGUEL ÁNGEL MARTÍNEZ DEL AMOR MINIPROJECT OF TDT24 NTNU

PARALLELIZATION OF ATTILA SIMULATOR WITH OPENMP MIGUEL ÁNGEL MARTÍNEZ DEL AMOR MINIPROJECT OF TDT24 NTNU PARALLELIZATION OF ATTILA SIMULATOR WITH OPENMP MIGUEL ÁNGEL MARTÍNEZ DEL AMOR MINIPROJECT OF TDT24 NTNU OUTLINE INEFFICIENCY OF ATTILA WAYS TO PARALLELIZE LOW COMPATIBILITY IN THE COMPILATION A SOLUTION

Læs mere

Fundamentals of HVAC Control Systems

Fundamentals of HVAC Control Systems ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 4 Sensors and Auxiliary Devices 2007 ASHRAE Hong

Læs mere

Strategic Capital ApS has requested Danionics A/S to make the following announcement prior to the annual general meeting on 23 April 2013:

Strategic Capital ApS has requested Danionics A/S to make the following announcement prior to the annual general meeting on 23 April 2013: Copenhagen, 23 April 2013 Announcement No. 9/2013 Danionics A/S Dr. Tværgade 9, 1. DK 1302 Copenhagen K, Denmark Tel: +45 88 91 98 70 Fax: +45 88 91 98 01 E-mail: investor@danionics.dk Website: www.danionics.dk

Læs mere

Rødsand laboratoriet et samarbejde mellem KU, Femern & DHI

Rødsand laboratoriet et samarbejde mellem KU, Femern & DHI Rødsand laboratoriet et samarbejde mellem KU, Femern & DHI Ulrik Lumborg DHI Rødsand laboratoriet I 2012 var det erkendt at Rødsand lagune ville være et fokusområde i forbindelse med etableringen af Femernforbindelsen

Læs mere

EA evaluering af DANAK Maj Erik Øhlenschlæger, DANAK april 2016

EA evaluering af DANAK Maj Erik Øhlenschlæger, DANAK april 2016 EA evaluering af DANAK Maj 2016 Erik Øhlenschlæger, DANAK april 2016 1 Omfang af peer evaluering for laboratorieområdet - 2 prøvningslaboratorier (1 aflyst pga. sygdom) - 2 kalibreringslaboratorier - 1

Læs mere

28 April 2003 Retrospective: Semicore Visit

28 April 2003 Retrospective: Semicore Visit 28 April 2003 Retrospective: Semicore Visit What is highest growth Industry? Rebuild versus remanufacture Importance of Documentation, blueprinting, spares What are barriers to high uptime? Review Homeworks

Læs mere

Special VFR. - ved flyvning til mindre flyveplads uden tårnkontrol som ligger indenfor en kontrolzone

Special VFR. - ved flyvning til mindre flyveplads uden tårnkontrol som ligger indenfor en kontrolzone Special VFR - ved flyvning til mindre flyveplads uden tårnkontrol som ligger indenfor en kontrolzone SERA.5005 Visual flight rules (a) Except when operating as a special VFR flight, VFR flights shall be

Læs mere

VENTILATION I EKSISTERENDE SKOLER HVORFOR OG HVORDAN?

VENTILATION I EKSISTERENDE SKOLER HVORFOR OG HVORDAN? VENTILATION I EKSISTERENDE SKOLER HVORFOR OG HVORDAN? STEFFEN PETERSEN ASSOCIATE PROFESSOR STP@ENG.AU.DK UNI VERSITET HVORFOR BYGGER VI HUSE? Hvorfor bygger vi huse? HVORFOR BYGGER VI HUSE? Indeklima who

Læs mere

DIVAR VIGTIGT! / IMPORTANT! MÅL / DIMENSIONS

DIVAR VIGTIGT! / IMPORTANT! MÅL / DIMENSIONS DIVAR VIGTIGT! / IMPORTANT! VIGTIGT læs vores anvisninger før du bruger produktet. Har du problemer med den elektriske installation, skal du kontakte en elektriker. Sørg for at altid slukke for strømmen

Læs mere

ESG reporting meeting investors needs

ESG reporting meeting investors needs ESG reporting meeting investors needs Carina Ohm Nordic Head of Climate Change and Sustainability Services, EY DIRF dagen, 24 September 2019 Investors have growing focus on ESG EY Investor Survey 2018

Læs mere

Nyhedsmail, december 2013 (scroll down for English version)

Nyhedsmail, december 2013 (scroll down for English version) Nyhedsmail, december 2013 (scroll down for English version) Kære Omdeler Julen venter rundt om hjørnet. Og netop julen er årsagen til, at NORDJYSKE Distributions mange omdelere har ekstra travlt med at

Læs mere

Hvordan kan vi bedre forudsige, hvilke problemer. påvirkninger beboerne i en given bolig vil blive udsat for. Geo Clausen

Hvordan kan vi bedre forudsige, hvilke problemer. påvirkninger beboerne i en given bolig vil blive udsat for. Geo Clausen Hvordan kan vi bedre forudsige, hvilke problemer beboerne i en given bolig vil blive udsat for? Geo Clausen Center for Indeklima og Energi Danmarks Tekniske Universitet Centre for indoor air and health

Læs mere

PEMS RDE Workshop. AVL M.O.V.E Integrative Mobile Vehicle Evaluation

PEMS RDE Workshop. AVL M.O.V.E Integrative Mobile Vehicle Evaluation PEMS RDE Workshop AVL M.O.V.E Integrative Mobile Vehicle Evaluation NEW - M.O.V.E Mobile Testing Platform Key Requirements for Measuring Systems Robustness Shock / vibrations Change of environment Compact

Læs mere

Skriftlig Eksamen Kombinatorik, Sandsynlighed og Randomiserede Algoritmer (DM528)

Skriftlig Eksamen Kombinatorik, Sandsynlighed og Randomiserede Algoritmer (DM528) Skriftlig Eksamen Kombinatorik, Sandsynlighed og Randomiserede Algoritmer (DM58) Institut for Matematik og Datalogi Syddansk Universitet, Odense Torsdag den 1. januar 01 kl. 9 13 Alle sædvanlige hjælpemidler

Læs mere

Privat-, statslig- eller regional institution m.v. Andet Added Bekaempelsesudfoerende: string No Label: Bekæmpelsesudførende

Privat-, statslig- eller regional institution m.v. Andet Added Bekaempelsesudfoerende: string No Label: Bekæmpelsesudførende Changes for Rottedatabasen Web Service The coming version of Rottedatabasen Web Service will have several changes some of them breaking for the exposed methods. These changes and the business logic behind

Læs mere

Hudevad P5 Easy Clean

Hudevad P5 Easy Clean Technical datasheet Key benefits Rengøring Unique tilting front Radiator front tilts away from the wall for easy access to cleaning the back of the radiator Classic Hudevad design Trademark Hudevad design

Læs mere

User Manual for LTC IGNOU

User Manual for LTC IGNOU User Manual for LTC IGNOU 1 LTC (Leave Travel Concession) Navigation: Portal Launch HCM Application Self Service LTC Self Service 1. LTC Advance/Intimation Navigation: Launch HCM Application Self Service

Læs mere

Observation Processes:

Observation Processes: Observation Processes: Preparing for lesson observations, Observing lessons Providing formative feedback Gerry Davies Faculty of Education Preparing for Observation: Task 1 How can we help student-teachers

Læs mere

Elite sports stadium requirements - views from Danish municipalities

Elite sports stadium requirements - views from Danish municipalities Elite sports stadium requirements - views from Danish municipalities JENS ALM Ph.d. student Malmö University jens.alm@mah.se Analyst Danish Institute for Sports Studies jens.alm@idan.dk Background Definitions

Læs mere

Dendrokronologisk Laboratorium

Dendrokronologisk Laboratorium Dendrokronologisk Laboratorium NNU rapport 5, 1997 STRANDGADE 3A, KØBENHAVN Nationalmuseets Marinarkæologiske Undersøgelser. Indsendt af Christian Lemée. Undersøgt af Aoife Daly og Niels Bonde. NNU j.nr.

Læs mere

Trolling Master Bornholm 2014?

Trolling Master Bornholm 2014? Trolling Master Bornholm 214? (English version further down) Trolling Master Bornholm 214? Den endelige beslutning er ikke taget endnu, men meget tyder på at vi kan gennemføre TMB i 214. Det ser nemlig

Læs mere

Financial Literacy among 5-7 years old children

Financial Literacy among 5-7 years old children Financial Literacy among 5-7 years old children -based on a market research survey among the parents in Denmark, Sweden, Norway, Finland, Northern Ireland and Republic of Ireland Page 1 Purpose of the

Læs mere

Info og krav til grupper med motorkøjetøjer

Info og krav til grupper med motorkøjetøjer Info og krav til grupper med motorkøjetøjer (English version, see page 4) GENERELT - FOR ALLE TYPER KØRETØJER ØJER GODT MILJØ FOR ALLE Vi ønsker at paraden er en god oplevelse for alle deltagere og tilskuere,

Læs mere

Sport for the elderly

Sport for the elderly Sport for the elderly - Teenagers of the future Play the Game 2013 Aarhus, 29 October 2013 Ditte Toft Danish Institute for Sports Studies +45 3266 1037 ditte.toft@idan.dk A growing group in the population

Læs mere

Molio specifications, development and challenges. ICIS DA 2019 Portland, Kim Streuli, Molio,

Molio specifications, development and challenges. ICIS DA 2019 Portland, Kim Streuli, Molio, Molio specifications, development and challenges ICIS DA 2019 Portland, Kim Streuli, Molio, 2019-06-04 Introduction The current structure is challenged by different factors. These are for example : Complex

Læs mere

Black Jack --- Review. Spring 2012

Black Jack --- Review. Spring 2012 Black Jack --- Review Spring 2012 Simulation Simulation can solve real-world problems by modeling realworld processes to provide otherwise unobtainable information. Computer simulation is used to predict

Læs mere

Remember the Ship, Additional Work

Remember the Ship, Additional Work 51 (104) Remember the Ship, Additional Work Remember the Ship Crosswords Across 3 A prejudiced person who is intolerant of any opinions differing from his own (5) 4 Another word for language (6) 6 The

Læs mere

Indeklima i danske skoler og kontorer. Jørn Toftum

Indeklima i danske skoler og kontorer. Jørn Toftum Indeklima i danske skoler og kontorer Jørn Toftum De kan jo bare åbne vinduerne! citat: Undervisningsministeren Men hvordan går det så med indeklimaet i de danske skoler? 2 DTU Byg, Danmarks Tekniske Universitet

Læs mere

Biocide resistance in Salmonella Typhimurium

Biocide resistance in Salmonella Typhimurium FACULTY OF HEALTH AND MEDICAL SCIENCES UNIVERSITY OF COPENHAGEN PhD thesis Mette Rørbæk Gantzhorn Biocide resistance in Salmonella Typhimurium Academic advisor: Line Elnif Thomsen This thesis has been

Læs mere

Sikkerhedsvejledning

Sikkerhedsvejledning 11-01-2018 2 Sikkerhedsvejledning VIGTIGT! Venligst læs disse instruktioner inden sengen samles og tages i brug Tjek at alle dele og komponenter er til stede som angivet i vejledningen Fjern alle beslagsdele

Læs mere

Tilmelding sker via stads selvbetjening indenfor annonceret tilmeldingsperiode, som du kan se på Studieadministrationens hjemmeside

Tilmelding sker via stads selvbetjening indenfor annonceret tilmeldingsperiode, som du kan se på Studieadministrationens hjemmeside Research Seminar in Computer Science Om kurset Subject Activitytype Teaching language Registration Datalogi master course English Tilmelding sker via stads selvbetjening indenfor annonceret tilmeldingsperiode,

Læs mere

DANSK INSTALLATIONSVEJLEDNING VLMT500 ADVARSEL!

DANSK INSTALLATIONSVEJLEDNING VLMT500 ADVARSEL! DANSK INSTALLATIONSVEJLEDNING VLMT500 Udpakningsinstruktioner Åben indpakningen forsigtigt og læg indholdet på et stykke pap eller en anden beskyttende overflade for at undgå beskadigelse. Kontroller at

Læs mere

VEDLIGEHOLDELSE AF SENGE

VEDLIGEHOLDELSE AF SENGE DK VEDLIGEHOLDELSE AF SENGE VEDLIGEHOLDELSE AF SENGE Sengen er typisk det møbel i hjemmet som bruges i flest timer gennem døgnet. Det betyder at sengen udsættes for et stort slid, og det er derfor vigtigt

Læs mere

Reexam questions in Statistics and Evidence-based medicine, august sem. Medis/Medicin, Modul 2.4.

Reexam questions in Statistics and Evidence-based medicine, august sem. Medis/Medicin, Modul 2.4. Reexam questions in Statistics and Evidence-based medicine, august 2013 2. sem. Medis/Medicin, Modul 2.4. Statistics : ESSAY-TYPE QUESTION 1. Intelligence tests are constructed such that the average score

Læs mere

ATEX direktivet. Vedligeholdelse af ATEX certifikater mv. Steen Christensen stec@teknologisk.dk www.atexdirektivet.

ATEX direktivet. Vedligeholdelse af ATEX certifikater mv. Steen Christensen stec@teknologisk.dk www.atexdirektivet. ATEX direktivet Vedligeholdelse af ATEX certifikater mv. Steen Christensen stec@teknologisk.dk www.atexdirektivet.dk tlf: 7220 2693 Vedligeholdelse af Certifikater / tekniske dossier / overensstemmelseserklæringen.

Læs mere

Skriftlig Eksamen Diskret matematik med anvendelser (DM72)

Skriftlig Eksamen Diskret matematik med anvendelser (DM72) Skriftlig Eksamen Diskret matematik med anvendelser (DM72) Institut for Matematik & Datalogi Syddansk Universitet, Odense Onsdag den 18. januar 2006 Alle sædvanlige hjælpemidler (lærebøger, notater etc.),

Læs mere

Den nye Eurocode EC Geotenikerdagen Morten S. Rasmussen

Den nye Eurocode EC Geotenikerdagen Morten S. Rasmussen Den nye Eurocode EC1997-1 Geotenikerdagen Morten S. Rasmussen UDFORDRINGER VED EC 1997-1 HVAD SKAL VI RUNDE - OPBYGNINGEN AF DE NYE EUROCODES - DE STØRSTE UDFORDRINGER - ER DER NOGET POSITIVT? 2 OPBYGNING

Læs mere

TMC - Klima

TMC - Klima NOTAT TMC Klima 97218 CO 2regnskab 217 Ifølge HøjeTaastrup Kommunes KlimaKommuneaftale med Danmarks Naturfredningsforening skal der udarbejdes og offentliggøres et årligt regnskab over kommunens CO 2 udledning.

Læs mere

(Text with EEA relevance)

(Text with EEA relevance) 24.4.2015 EN Official Journal of the European Union L 106/79 COMMISSION IMPLEMENTING DECISION (EU) 2015/646 of 23 April 2015 pursuant to Article 3(3) of Regulation (EU) No 528/2012 of the European Parliament

Læs mere

DENCON ARBEJDSBORDE DENCON DESKS

DENCON ARBEJDSBORDE DENCON DESKS DENCON ARBEJDSBORDE Mennesket i centrum betyder, at vi tager hensyn til kroppen og kroppens funktioner. Fordi vi ved, at det er vigtigt og sundt jævnligt at skifte stilling, når man arbejder. Bevægelse

Læs mere

GREEN KEY GREEN DREAMS

GREEN KEY GREEN DREAMS GREEN KEY GREEN DREAMS EN VI RON MENT 1 VI TÆNKER PÅ MILJØET OG DIN KOMFORT Du har valgt en Green Key (Grøn Nøgle) virksomhed. Det betyder, at du automatisk er med til at passe på miljøet, da vi lever

Læs mere